CJX2-DAC Contactor
Standard Conformity: This AC contactor conformsto IEC: 60947-4-1 standard.
Insulation Voltage Ui: 750V
Operation Voltage Ue: 690V
Ambient Temperature Range:The AC contactor is suitable for use in temperatures ranges from -5℃ to 55℃.
Operating Altitude:3000m
Mounting Position: ±30° (Vertical Plane)
Specifications
Contactor | CJX2-D RDC6 | 09 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
Nominal Current Rating at 415V 50Hz AC3 le | A | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
NO. of Poles | 3P NO/NC | 3P NO/NC | 3P NO/NC | 3P NO/NC | 3P NO/NC | 3P 1NO 1NC | 3P 1NO 1NC | 3P 1NO 1NC | 3P 1NO 1NC | 3P 1NO 1NC | |
Impulse withstand voltage Uimp | KV | 6 | 6 | 6 | 6 | 6 | 8 | 8 | 8 | 8 | 8 |
Making Capacity | A | 250 | 250 | 330 | 350 | 560 | 760 | 900 | 950 | 1100 | 1120 |
Breaking Capacity at 415V | A | 250 | 250 | 330 | 350 | 560 | 760 | 900 | 950 | 1100 | 1120 |
AC1 duty: Rated Operational Current le Max. Power Rating at 415V | A | 25 | 25 | 32 | 40 | 50 | 60 | 80 | 80 | 125 | 125 |
KW | 11 | 11 | 18 | 22 | 25 | 33 | 45 | 45 | 63 | 63 | |
AC2/AC3duty: Rated Operational Current le Max. Power Rating at 415V Electrical life AC-3 (Refer. Electrical life plot) | A | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
KW/HP | 4/5 | 5.5/7.5 | 9/12.5 | 11/15 | 15/20 | 22/30 | 25/35 | 37/50 | 45/60 | 45/60 | |
*103 Operations | 2000 | 2000 | 2000 | 2000 | 1500 | 1500 | 1500 | 1500 | 1500 | 1500 | |
AC4 Duty: Rated Operational current le Max. Power Rating at 415V (Refer. Electrical life plot) | A | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
KW/HP | 4/5 | 5.5/7.5 | 9/12.5 | 11/15 | 15/20 | 22/30 | 25/35 | 37/50 | 45/60 | 45/60 | |
Mechanical life | Million Ops. | 10 | 10 | 10 | 10 | 10 | 8 | 8 | 8 | 8 | 8 |
Switching Frequency (No Load) | OPS./Hr. | 3600 | 3600 | 3600 | 3600 | 3600 | 3000 | 3000 | 3000 | 2000 | 2000 |
Impedence Per Pole | m.ohm. | 2.5 | 2.5 | 2.5 | 2 | 2 | 1.5 | 1.5 | 1 | 0.8 | 0.8 |
Short Time Current at 40℃(1sec) | A | 245 | 245 | 320 | 435 | 545 | 735 | 875 | 920 | 1045 | 1065 |
Short circuit back Up Fuse Rating | A | 20 | 20 | 32 | 40 | 50 | 63 | 80 | 80 | 100 | 125 |
Max. Cable size | Sq.mm | 4 | 4 | 6 | 10 | 10 | 16 | 25 | 25 | 50 | 50 |
Tightening Torque | Nm | 0.8 | 0.8 | 0.8 | 1.2 | 1.2 | 3.5 | 3.5 | 3.5 | 4 | 4 |
Weight 3P/4P | KG | 0.34/ | 0.34/ | 0.35/ | 0.5/ | 0.52/ | 1.08/ | 1.08/ | 1.08/ | 1.3/ | 1.3/ |
Over all Dimension(W*H*D) | mm | 45*74*82 | 45*74*82 | 47*76*87 | 57*83*95 | 57*83*100 | 77*120*116 | 77*120*116 | 77*120*116 | 87*120*127 | 87*120*127 |
Operating Voltage Range | V | 0.7-1.1 | 0.7-1.1 | 0.7-1.1 | 0.7-1.1 | 0.7-1.1 | 0.7-1.1 | 0.7-1.1 | 0.7-1.1 | 0.75-1.1 | 0.75-1.1 |
Power Consumption (inrush /hold) 50Hz | VA | 70/8 | 70/8 | 110/11 | 110/11 | 110/11 | 200/20 | 200/20 | 200/20 | 200/20 | 200/20 |
Power Consumption (inrush /hold) 60Hz | VA | 80/8 | 80/8 | 115/11 | 115/11 | 115/11 | 200/20 | 200/20 | 200/20 | 200/20 | 200/20 |
Heat Dissipation 50/60Hz | W | 1.8-2.7 | 1.8-2.7 | 2.5-3.5 | 3.0-4.0 | 6.0-10.0 | 6.0-10.0 | 6.0-10.0 | 6.0-10.0 | 6.0-10.0 | 6.0-10.0 |
Coil pick up time Drop out time | ms | 12-22 5-12 | 12-22 5-12 | 12-22 5-12 | 15-24 5-20 | 15-24 5-20 | 20-25 8-15 | 20-25 8-15 | 20-25 8-15 | 20-25 8-15 | 20-25 8-15 |
AC Coils | |||||||
Code | A | C | E | G | H | J | K |
AC Voltage | 24V | 48V | 110V | 220V | 240V | 380V | 415V |
As a China-based primary AC contactor manufacturer, People Group canprovide our worldwide customers with superior quality circuit breaker, relay,master switch and metering instrument, and more. All these productsare CE, CB, UL, KEMA, SEMKO and SAA certified, so you can feel secured inplacing orders from us.