Air Cooled Chiller (Screw Water Chiller)
Air cooled chiller absorbs the heat from the processing water through the ventilation. The condenser's fans expel heat to the atmosphere from the evaporator, cooling compressor and the pipes.
Our air cooled chiller adopts imported copper pipes and automatic welding elbow, which improves the air tightness and eradicates the emission of freezing medium.
Our air cooled chiller adopts fins for heat dissipation punched by high-speed punch machine. Because the rims of good quality are flanged twice, fins attach to copper pipes more closely and enable the high heat exchange efficiency.
Technical Parameters of Fan Cooling Spiral Long Rod Freezing Unit
Single Compressor Series
Type Parameters | PC-40 ASCS | PC-50 ASCS | PC-60 ASCS | PC-70 ASCS | PC-80 ASCS | ||
Rated Cooling Capacity | 50HZ | Btu/h | 391927 | 498103 | 564334 | 654464 | 756542 |
Kcal/h | 98710 | 125451 | 142132 | 164832 | 190542 | ||
KW | 114.8 | 145.9 | 165.3 | 191.7 | 221.6 | ||
USRT | 32.6 | 41.5 | 47.0 | 54.5 | 63.0 | ||
Input Power Supply | ~380V/3PHASE/HZ | ||||||
Input Power(KW) | 35.5 | 44.2 | 45.6 | 52.9 | 60.5 | ||
Cooling Loop | 1 | 1 | 1 | 1 | 1 | ||
Coolant Flow Control | Heat Expansion Value Elecitronic Expansion Valve(Optional) | ||||||
Cooling Media | R22/407C/134A | ||||||
Compressor | Pattern | Semi-sealed Spiral Long Rod Style | |||||
Quantity | 1 | 1 | 1 | 1 | 1 | ||
Starting Method | Y-△ Starting | ||||||
Capacity Control(%) | 100-75-50-25 | ||||||
Condenser | Pattern | High Effective Red Copper Pipes Covered Into Aluminum Fins | |||||
Air flow(CMH) | 50340 | 63690 | 69570 | 80670 | 93030 | ||
Enine Power(KW) | 3.44 | 5.16 | 5.16 | 5.16 | 6.88 | ||
Evaporator | Pattern | High Effective Inner Grooved Copper Pole Shell and Pole condenser Made in Kobe | |||||
Quantity | 1 | 1 | 1 | 1 | 1 | ||
Presure Loss(Kpa) | 72 | 72 | 72 | 72 | 72 | ||
Water Flow(m3/h) | 22.5 | 28.5 | 31.5 | 36.5 | 42.2 | ||
Temperature Controller | CAREL micro-computer controlled system for refrigeration | ||||||
Safety Device | High/Low Voltage Switch, Exhausting Overheat Protection, Fusible Plug Anti-Freezing Temperature Controller Compressor Heat Protector, Overcurrent Relay, Phase Sequence Protector/Lack Phase Protector, Lack Pressure Protection | ||||||
Pipes Connection | Freezing Water Flow In/Out(Inch) | 2.5 | 2.5 | 3 | 3 | 3 | |
Machine Weight(Kg) | 925 | 1080 | 1200 | 1500 | 1680 | ||
Machine Weight(Kg) | 990 | 1160 | 1300 | 1600 | 1800 |
Type Parameters | PC-100 ASCS | PC-120 ASCS | PC-140 ASCS | PC-160 ASCS | PC-180 ASCS | ||
Rated Cooling Capacity | 50HZ | Btu/h | 930315 | 1120475 | 1334533 | 1491235 | 1682078 |
Kcal/h | 234308 | 282201 | 336113 | 375580 | 423646 | ||
KW | 272.5 | 328.2 | 390.9 | 436.8 | 492.7 | ||
USRT | 77.5 | 93.3 | 111.1 | 124.2 | 140.1 | ||
Input Power Supply | ~380V/3PHASE/HZ | ||||||
Input Power (KW) | 73.1 | 88.0 | 103.5 | 114.6 | 128.7 | ||
Cooling Loop | 1 | 1 | 1 | 1 | 1 | ||
Coolant Flow Control | Heat Expansion Value Elecitronic Expansion Valve(Optional) | ||||||
Cooling Media | R22/407C/134A | ||||||
Compressor | Pattern | Semi-sealed Spiral Long Rod Style | |||||
Quantity | 1 | 1 | 1 | 1 | 1 | ||
Starting Method | Y-△ Starting | ||||||
Capacity Control(%) | 100-75-50-25 | ||||||
Condenser | Pattern | High Effective Red Copper Pipes Covered Into Aluminum Fins | |||||
Air flow(CMH) | 113970 | 137280 | 163080 | 181890 | 207240 | ||
Enine Power(KW) | 6.88 | 8.6 | 10.32 | 12.04 | 13.76 | ||
Evaporator | Pattern | High Effective Inner Grooved Copper Pole Shell and Pole condenser Made in Kobe | |||||
Quantity | 1 | 1 | 1 | 1 | 1 | ||
Presure Loss(Kpa) | 85 | 85 | 85 | 85 | 85 | ||
Water Flow(m3/h) | 51.9 | 62.5 | 74.5 | 83.2 | 95.7 | ||
Temperature Controller | CAREL micro-computer controlled system for refrigeration | ||||||
Safety Device | High/Low Voltage Switch, Exhausting Overheat Protection, Fusible Plug Anti-Freezing Temperature Controller Compressor Heat Protector, Overcurrent Relay, Phase Sequence Protector/Lack Phase Protector, Lack Pressure Protection | ||||||
Pipes Connection | Freezing Water Flow In/Out(Inch) | 4 | 4 | 4 | 4 | 4 | |
Machine Weight(Kg) | 2000 | 2360 | 2800 | 3000 | 3700 | ||
Machine Weight(Kg) | 2100 | 2600 | 3000 | 3200 | 4000 |
Double Compreesor Series
Type Parameters | PC-80 ASCS | PC-100 ASCS | PC-120 ASCS | PC-160 ASCS | ||
Rated Cooling Capacity | 50HZ | Btu/h | 784196 | 996205 | 1129010 | 1513426 |
Kcal/h | 197506 | 250903 | 284351 | 381169 | ||
KW | 229.7 | 291.8 | 330.7 | 443.3 | ||
USRT | 65.3 | 83.0 | 94.0 | 126.0 | ||
Input Power Supply | ~380V/3PHASE/HZ | |||||
Input Power (KW) | 71.0 | 88.4 | 91.2 | 121.0 | ||
Cooling Loop | 2 | 2 | 2 | 2 | ||
Coolant Flow Control | Heat Expansion Value Elecitronic Expansion Valve(Optional) | |||||
Cooling Media | R22/407C/134A | |||||
Compressor | Pattern | Semi-sealed Spiral Long Rod Style | ||||
Quantity | 2 | 2 | 2 | 2 | ||
Starting Method | Y-△ Starting | |||||
Capacity Control(%) | 100-75-50-25 | |||||
Condenser | Pattern | High Effective Red Copper Pipes Covered Into Aluminum Fins | ||||
Air flow(CMH) | 100680 | 127380 | 139140 | 186060 | ||
Enine Power(KW) | 6.88 | 5.16 | 8.6 | 12.041 | ||
Evaporator | Pattern | High Effective Inner Grooved Copper Pole Shell and Pole condenser Made in Kobe | ||||
Quantity | 1 | 1 | 1 | 1 | ||
Presure Loss(Kpa) | 85 | 85 | 85 | 85 | ||
Water Flow(m3/h) | 44.9 | 57.1 | 63.0 | 84.4 | ||
Temperature Controller | CAREL micro-computer controlled system for refrigeration | |||||
Safety Device | High/Low Voltage Switch, Exhausting Overheat Protection, Fusible Plug Anti-Freezing Temperature Controller Compressor Heat Protector, Overcurrent Relay, Phase Sequence Protector/Lack Phase Protector, Lack Pressure Protection | |||||
Pipes Connection | Freezing Water Flow In/Out(Inch) | 4 | 4 | 4 | 4 | |
Machine Weight(Kg) | 1800 | 2000 | 2400 | 3200 | ||
Machine Weight(Kg) | 2000 | 2200 | 2600 | 3500 |
Notice
Cooling output is based on the temperature conditions regulated in JIS B8613 standard
Inlet temperature of freezing water: 12℃
Outlet temperature of freezing water: 7℃
Inlet temperature of cooling water: 30℃
Outlet temperature of cooling water: 35℃
Besides the types in the form above, our company welcomes consumers to have various needs and we will produce and offer new types according to your needs. Our company reserves the right to adjust the product design and norm without notification.