Home 6/10(12)kV CU/XLPE/CTS/PVC/AWA/PVC Single core armored cable

6/10(12)kV CU/XLPE/CTS/PVC/AWA/PVC Single core armored cable

Single core XLPE insulated copper tape screen armored cable with copper conductor


Construction:



Conductor - Plain annealed class 2 compacted copper
Conductor screen – Semi-conductive compound
Insulation - Cross linked polyethylene (XLPE)
Insulation screen - Semi-conductive compound
Metallic screen - Plain annealed copper tape
Binder tape - Non-hygroscopic material tape
Separation layer - Polyvinyl chloride compound (PVC)
Armor - Hard drawn aluminum wires
Binder tape - Non-hygroscopic material tape
Outer sheath - Polyvinyl chloride compound (PVC)




Application:

Medium voltage cables are used for power distribution in medium voltage, as transformer feeders in distribution substations. These lines can be found in many installations, such as in power plants, residential areas and mining operations, suitable for use in both dry and wet locations. They can be laid in air or directly buried in the ground or in ducts, providing good mechanical protection.

6/10(12)kV CU/XLPE/CTS/PVC/AWA/PVC Single core armored cable


Temperature characteristics:

Conductor operating temperature: -15℃~90℃
Min. installation temperature: 0℃
Conductor emergency operating temperature: 105℃
Conductor short-circuit operating temperature (5s): 250℃



Color:

Core identification: Nature or according to the customer's request
Outer sheath: Black or according to customer requirements



Electrical characteristics:

Rated voltage: 6/10(12) kV
AC High voltage test: 2.5 U0 for 30min
Partial Discharge at 1.73 U0: 5pC or better




Standard:

Cable design: IEC 60502-2
Conductor: IEC 60228


Cross section:
1 core; 25~800mm2