Three core XLPE insulated copper tape screen armored cable with aluminum conductor
Construction:
Conductor - Class 2 compacted aluminum
Conductor screen – Semi-conductive compound
Insulation - Cross linked polyethylene (XLPE)
Insulation screen - Semi-conductive compound
Metallic screen - Plain annealed copper tape
Filler - Non-hygroscopic material
Binder tape - Non-hygroscopic material tape
Separation layer - Polyvinyl chloride compound (PVC)
Armor - Galvanized steel wire wires
Binder tape - Non-hygroscopic material tape
Outer sheath - Polyvinyl chloride compound (PVC)
Application:
Medium voltage cables are used for power distribution in medium voltage, as transformer feeders in distribution substations. These lines can be found in many installations, such as in power plants, residential areas and mining operations, suitable for use in both dry and wet locations. They can be laid in air or directly buried in the ground or in ducts, providing good mechanical protection.
Temperature characteristics:
Conductor operating temperature: -15℃~90℃
Min. installation temperature: 0℃
Conductor emergency operating temperature: 105℃
Conductor short-circuit operating temperature (5s): 250℃
Color:
Core identification: Red, yellow, blue strip along the phase core or according to the customer's request
Outer sheath: Black or according to customer requirements
Electrical characteristics:
Rated voltage: 26/35(40.5) kV
AC High voltage test: 2.5 U0 for 30min
Partial Discharge at 1.73 U0: 5pC or better
Standard:
Cable design: IEC 60502-3
Conductor: IEC 60228
Cross section:
3 core; 50~400mm2