Home THT8 Series Time Delay Relay

THT8 Series Time Delay Relay

Single-function time relay, on delay/off delay

THT8 Series Time Delay Relay
Features

The single-function relay utilizes a potentiometer to set time for accurate performance Delay function is optional Time is divided into 10 scales within a wide range of 0.1s to 10 days Relay status is indicated by built-in LED 1-module, DIN-rail mounted






Applications

Suitable for applications with specified function and time requirements.
Time switch for pump delay after switching off heaters or fans.

Technical parameters
Technical parameters THT8-A1/B1 THT8-A2/B2
Function delay on delay off
Supply terminals A1-A2
Voltage range AC/DC 12-240V (50-60Hz)
Load AC 0.7-3VA/DC 0.5-1.7W
Voltage range AC 230V (50-60Hz)
Power input AC max.12VA/1.3W AC max.12VA/1.9W
Supply voltage tolerance -15%; +10%
Supply indication green LED
Time ranges 0.1s-10days, on, off
Time setting potentiometer
Time deviation 5%-mechanical setting
Repeat accuracy 0.2%-set value stability
Temperature coefficient 0.05%℃, at=20℃ (0.05%℉, at=68℉)
Output 1*SPDT 2*SPDT
Current rating 16A/AC1
Switching voltage 250VAC/24VDC
Min. breaking capacity DC 500mW
Output indication red LED
Mechanical life 1*107
Electrical life (AC1) 1*106
Reset time max. 200ms
Operating temperature -20℃ to +55℃ (-4℉ to 13℉)
Storage temperature -35℃ to +75℃ (-22℉ to 158℉)
Mounting/DIN rail DIN rail EN/IEC60715
Protection degree IP40 for front panel I/I P20 terminals
Operating position any
Overvoltage category III
Pollution degree 2
Max. cable size (mm²) solid wire max. 1*2.5or 2*1.5/with sleeve max.1*2.5(AWG 12)
Dimensions 90*18*64 mm
Weight 1 X SPDT: W240-60g, A230-59g
2 X SPDT: W240-81g, A230-79g
Standards IEC/EN61812-1, IEC/EN61010-1


Functions diagram

Wiring diagram

Time range

Dimensions (mm)