Fan Coil Unit is a kind of end equipment of air conditioning system, consists of small fan, electric motor and coil. Chilled or hot water exchanges heat with air outside the pipe when flowing through the coil, to cool or heat air indoor. WARM provide ceiling ducted type, cassette type and high wall mounted type of Fan Coil Unit sorted by different installing methods for you to choose.
Features of Fan Coil UnitTypes Comparison | Type | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
Rated Air Flow Rate (m³/h) | High | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 | |
Medium | 255 | 383 | 510 | 638 | 765 | 1020 | 1275 | 1530 | 1785 | ||
Low | 170 | 255 | 340 | 425 | 510 | 680 | 850 | 1020 | 1190 | ||
Cooling Capacity (W) | High Speed | Total Heat | 1888 | 2795 | 3709 | 4625 | 5518 | 7046 | 8838 | 10578 | 12318 |
Sensible Heat | 1310 | 1926 | 2528 | 3149 | 3722 | 4863 | 6073 | 7242 | 8389 | ||
Medium Speed | Total Heat | 1661 | 2432 | 3251 | 4030 | 4785 | 6182 | 7739 | 9158 | 10716 | |
Sensible Heat | 1099 | 1603 | 2133 | 2629 | 3148 | 4072 | 5082 | 6002 | 7040 | ||
Low Speed | Total Heat | 1321 | 1933 | 2568 | 3182 | 3778 | 4900 | 6136 | 7281 | 8472 | |
Sensible Heat | 839 | 1231 | 1623 | 2005 | 2379 | 3120 | 3895 | 4609 | 5408 | ||
Heating Capacity (W) | High Speed | 3143 | 4556 | 5997 | 7378 | 8707 | 11410 | 14254 | 16789 | 19476 | |
Medium Speed | 2567 | 3732 | 4915 | 6054 | 7154 | 9395 | 11731 | 13845 | 16064 | ||
Low Speed | 1879 | 2746 | 3622 | 4471 | 5295 | 6975 | 8731 | 10296 | 11953 | ||
Noise dB(A) | Low Static Pressure | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 | |
High Static Pressure | 40 | 42 | 44 | 46 | 47 | 48 | 50 | 52 | 54 | ||
Extremely High Static Pressure | 41 | 44 | 46 | 47 | 48 | 50 | 52 | 54 | 56 | ||
Water Flowing Rate(L/h) | 325 | 481 | 638 | 796 | 949 | 1212 | 1520 | 1819 | 2119 | ||
Electric Motor | Power Supply | 220V 1ph 50Hz | |||||||||
Motor Number | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | ||
Low Static Pressure Input Power(W) | 37 | 52 | 62 | 76 | 96 | 134 | 152 | 189 | 228 | ||
High Static Pressure Input Power(W) | 44 | 59 | 72 | 87 | 108 | 156 | 174 | 212 | 253 | ||
Extremely High Static Pressure Input Power(W) | 49 | 66 | 84 | 100 | 118 | 174 | 210 | 250 | 300 |