Home Silicone Rubber Insulated Control Cable

Silicone Rubber Insulated Control Cable

Standard Silicone rubber insulated control cable is manufactured according to Q/320411048.1 (refer to BS 7629) standards.
The flame-retardant cables comply with GB /T18380.3 (IEC60332-3) standards.
The low-smoke low-halogen cables comply with GB/T17650 (IEC60754-1), GB/T 17651(IEC61034) standards.
The low-smoke halogen-free cables comply with GB/T17650 (IEC60754-1), GB/T 17651(IEC61034) standards.
The fire-resistance cable (NH) can pass the test according to GB 19216(IEC 60331-21)



Application Silicone rubber insulated control cables are often used for sign transmission, controlling and measuring systems of the electric components and the power distribution in industries which have high flame-proof requirements.


Properties 1. Rated voltage: 300/500V
2. The Max. long-term operating temperature of conductor:-60℃~180℃
3. The permitted bending radius:
No less than 12 times of the overall diameter of the cable for which has armored or wrapped shield.
No less than 6 times of the overall diameter of the cable for the others.
4. The Min. laying temperature is:
-20℃ for PE sheathed cable;
0℃ for PVC or HFPO sheathed cable.
It should be pre-heated if it is below the Min. laying temperature.
5. Flame characteristics
5.1 The flame retardant cable can pass the test according to GB 18380.3(IEC 60332-3): Test method on electrical wires or cables under fire conditions Part 5: Test on bunched wires and cables.
5.2 The low-smoke low-halogen flame retardant cable can pass testing according to GB/T 17651(IEC61034): Test method on electrical wires or cables under fire conditions. The insulation and sheath material of the cable should be tested as per GB/T17650 (IEC60754-1). The HCl content of the emision gas in the firing test should be no more than 100mg/g.
5.3 The insulation and sheath material of the low-smoke halogen-free flame retardant cable can pass test according to GB/T 17651(IEC61034) : Test method on electrical wires or cables under fire conditions. The insulation and sheath material of the cable should be tested as per GB/T17650(IEC60754-2) , pH value shall be no less than 4.3 and conductivity should be less than 10ms/mm.
5.4 The fire-restance cable (NH) can pass the test according to GB/T 19216(IEC 60332-1)
6. The DC resistance of conductor and insulation resistance is shown in table 3.

Silicone Rubber Insulated Control Cable

Table 3



Nominal sectional DC resistance of conductor at 20 ℃ ≤Ω /km
Area Tinned Bare
mm2 Class 1 Class 2 Class 5 Class 1 Class 2 Class 5
0.5 36.0 36.0 39.0 36.7 36.7 40.1
0.75 24.5 24.5 26.0 24.8 24.8 26.7
1.0 18.1 18.1 19.5 18.2 18.2 20.0
1.5 12.1 12.1 13.3 12.2 12.2 13.7
2.5 7.41 7.41 7.98 7.56 7.56 8.21
4 4.61 4.61 -- 4.70 4.70 --
6 3.08 3.08 -- 3.11 3.11 --
10 -- 1.83 -- -- 1.84 --


For more details, please download the PDF!


Other search items: silicone insulated control cable


Recommended Products
Hot Products