Introduction to SF6 Gas Insulated Load Break Switch
The FLN36-12 SF6 load break switch is a double fracture rotary switch that uses sulfur hexafluoride gas as the insulating and arc quenching medium, suitable for 10KV distribution system XGN15-12 RMU. Each load break switch is filled with SF6 gas in pressure of 0.4bar and the gas is permanently sealed.
No. | Item | Unit | Value | |||
FLN36 | FLRN36 | |||||
1 | Rated voltage | KV | 12 | |||
2 | Rated frequency | Hz | 50 | |||
3 | Rated current | A | 630 | 125 | ||
4 | Rated insulation level | 1 min power frequency withstand voltage | phase-to-phase, phase to earth | KV | 42 | |
fracture | 48 | |||||
Lightning impulse withstand voltage (peak) | phase-to-phase, phase to earth | 75 | ||||
fracture | 85 | |||||
5 | Auxiliary circuit 1min power frequency withstand voltage | V | 2000 | |||
6 | Rated short-time withstand current / duration | main switch | KA | 20/3 | ||
earthing switch | 20/2 | |||||
7 | Peak withstand current and short-circuit breaking current | KA | 50 | 125 | ||
8 | Rated closed circuit breaking current | A | 630 | |||
9 | Rated active load breaking current | A | 630 | |||
10 | Rated cable charging breaking current | A | 10 | |||
11 | Rated breaking no-load transformer capacity | KVA | 1250 | |||
12 | Breaking transfer current | A | — | 1700 | ||
13 | Expected short-circuit breaking current | KA | — | 50 | ||
14 | Mechanical life | times | 2000 | |||
15 | SF6 gas rated inflation pressure (20 ℃gauge pressure) | MPa | 0.04 | |||
16 | SF6 gas highest pressure (20 ℃gauge pressure) | MPa | 0.045 | |||
17 | Dimensions (width × height × depth) | mm | 345 × 420× 730 |
No. | Rated Voltage (KV) | Fuse Rated Current (A) | Fuse Link Rated Current (A) | Rated Breaking Current (KA) |
1 | 12 | 40 | 6.3, 10, 16, 20, 25, 31.5, 40 | 40 |
2 | 100 | 50, 63, 80, 100 | 40 | |
3 | 125 | 125 | 50 |
Main switch function: manual and electrical opening and closing operations are both allowed. The closing is only allowed when the earthing switch is in open state.
Earthing switch function: the opening and closing operation can only be done manually. When the main switch is in closed state, the earthing switch is not available.
Auxiliary switch:
Closing position: 2 normally open -2 normally closed;
Opening position: 2 normally open -2 normally closed;
Grounding position: 2 normally open -2 normally closed.
Mechanism indication:
Main switch and earthing switch status indication (K-type operating mechanism)
Main switch and earthing switch status indication, blown fuse indication (A-type operating mechanism)
Shunt trip coil is for A type operating mechanism.
2. Electric operation: automatic opening and closing can be achieved through motor drive and control unit. The motor operating voltage can be AC220V, DC220V, DC48V, DC24V.