With the rated current up to 2,500A, the short-circuit breaking current of 31.5KA, the capacitor bank switching current of 630A and the mechanical life of 10,000 times, the ZN12-27.5B/2500-31.5 indoor single pole vacuum circuit breaker is developed on the basis of the 3AF technology introduced from German Siemens Company in 1983.
This first domestically produced vacuum circuit breaker dedicated to electrified railway was put into operation in the Chawu supply segment of Beijing Railway Bureau in 1990. So far, this indoor vacuum circuit breaker has been widely used in lots of domestic railway projects, such as the Beijing - Shijiazhuang line, Wuhan-Guangzhou line, Beijing-Qinhuangdao line, Shijiazhuang - Taiyuan line, Baotou-Xi'an line, Baoji-Lanzhou line, Guizhou-Guangxi line, Fuzhou-Xiamen line, and other railway trunk lines.
Our indoor single pole vacuum circuit breaker has been adopted by Beijing Railway Bureau, Shanghai Railway Bureau, Taiyuan Railway Bureau, Zhengzhou Railway Bureau, Wuhan Railway Bureau, Lanzhou Railway Bureau, Xi'an Railway Bureau, Chengdu Railway Bureau, Kunming Railway Bureau, Nanning Railway Bureau, and Guangzhou Railway Group.
Item | Unit | Value |
Rated Voltage | kV | 27.5 |
Max. Voltage | kV | 31.5 |
Rated Current | A | 1,250 1,600 2,000 2,500 |
Rated Short-circuit Breaking Current | kA | 25 31.5 |
Dynamic Stable Current (Peak) | kA | 63 80 |
4s Thermal Stable Current | kA | 25 31.5 |
Rated Short-circuit Closing Current (Peak) | A | 63 80 |
Rated Short-circuit Current Breaking Times | times | 20 |
Rated Current of Closing Capacitor Bank | A | 630 |
Rated Operating Sequence | O-0.3s-co-180s-co | |
Rated Lightning Impulse Withstand Voltage (Full Wave) | kV | 185 (218) |
Rated Short-time Power Frequency Withstand Voltage (1min) | kV | 80 (95) |
Closing Time | s | ≤0.09 |
Opening Time | s | ≤0.08 |
Mechanical Life | times | 10,000 |
Rated Current Breaking Times | times | 10,000 |
Power of the Energy Storage Motor | W | 275 |
Rated Voltage of the Energy Storage Motor | V | 110 220 |
Energy Storage Time | s | 15 |
Rated Voltage of the Closing Electromagnet | V | 110 220 |
Rated Voltage of the Opening Electromagnet | V | 110 220 |
Rated Current of the Overcurrent Release | A | 5 |
Rated Current of the Auxiliary Switch | A | AC 10 DC 5 |
As a professional indoor single pole vacuum circuit breaker manufacturer and supplier in China, we provide a wide range of products, including gas insulated metal enclosed switchgear, high voltage vacuum contactor, outdoor vacuum circuit breaker, withdrawable low voltage switchgear, and more.