Download Technical Parameters
Air Cooled Scroll Hot Water Heat Pump |
Unit model | RLSFW -(D) | RLSFW10 | RLSFW20 | RLSFW30 | RLSFW40 | RLSFW80 |
Heating capacity | kW | 11.2 | 19.8 | 36.3 | 40.7 | 81.4 |
Healing input power | kW | 4.3 | 7.3 | 11 | 12.6 | 25.2 |
Max. running Current | A | 19.5 | 11 | 16.7 | 19.1 | 38.3 |
Max. running Current | A | 22 | 16 | 25 | 32 | 61 |
Cable diameter (copper water distance≤20 meters) | mm2 | 3*6 | 3*4 2*2.5 | 3*6 2*2.5 | 3*10 2*6 | 3*25 2*16 |
Power Voltage | 220V/50HZ | 380V/50HZ |
Compressor Qty | 1 | 1 | 1 | 1 | 2 |
Starting mode | Directly |
Refrigerant | R22 |
Refrigerant charge | kg | 4.5 | 6.5 | 10 | 10.5 | 10.5*2 |
Refrigerant charging device | Thermal expansion valve |
Evaporator | Type | Plate type |
Water pipe Dia. | DN | DN32 | DN32 | DN40 | DN40 | DN50 |
Water flow | m3/h | 1.8 | 3.1 | 5.7 | 6.4 | 12.7 |
Water flow | | | | | |
Condenser fan | Type | Axial type |
Fan Qty | 1 | 1 | 1 | 1 | 2 |
Noise level | dB(A) | 69 | 69 | 69 | 69 | 69 |
Power | kW | 0.37/0.55 | 0.37/0.55 | 0.37/0.55 | 0.37/0.55 | 0.37/0.55 |
Air flow | m3/h | 8000 | 8000 | 10000 | 10000 | 20000 |
Air discharge | Top |
Dimensions (mm) | L | 1180 | 1180 | 1180 | 1180 | 2110 |
W | 1080 | 1080 | 1080 | 1080 | 1080 |
H | 1870 | 1870 | 1870 | 1870 | 1870 |
Net weight | kg | 300 | 320 | 350 | 380 | 700 |
Running weight | kg | 330 | 350 | 380 | 420 | 760 |
Noise level | dB(A) | 69 | 70 | 72 | 72 | 73 |
Remarks |
1. Test conditions: ambient temperature 20℃ DB/15℃ WB; the actual heating capacity will vary with the outdoor environment temperature and humidity; |
2. The maximum outlet temperature of hot water can reach 60℃. |
3. Operating environment temperature range: -25℃~46℃; outlet water temperature: 55℃ |
Features Mini type air cooled water chiller and heat pump has the advantages of high efficiency, energy saving, low noise level, reasonable structure, easy operation and maintenance. It is widely used in the central air-conditioning system of construction facilities such as villas, hotels, shopping malls, supermarkets, office buildings, workshops and business clubs. The unit can meet different requirements of air conditioning systems.
The air cooled water chiller and heat pump has cooling only type and heat pump type. Among them, the heat pump type unit features cooling and heating function switch, which can achieve cooling in summer and heating in winter.
When the scroll chilling unit is equipped with a heat recovery device, it can also provide domestic hot water during cooling operation. This can meet the needs of domestic hot water in villas, restaurants, clubs and other places.
Intelligent defrost control system is equipped to avoid extra loss of heat.
The water chiller and heat pump has many functions such as energy management, antifreeze detection, and voltage detection. The unit adopts well-known brand scroll compressor featuring few moving parts and long service life.