Structure Stainless steel tube Aluminum clad steel wire Preservative oil Aluminum wire Description

OPGW fiber integrates ground electrode and photo-communication functions all in cable one unit. This product is mainly applied to 35kV, 110kV, 220kV, 500kV, 750kV telecommunication lines of high voltage transmission systems built on stilts. OPGW fiber is also suitable for replacing old ground wires of high voltage transmission system built on stilts to add to existing optical communication lines, conduct short circuit current and protect the system from lightning strikes.

Industrial Cable Manufacturer

SPFO will carefully design the structure of the optical cable according to the specific service environment (like distance between towers, requirement of sag, ice load, wind load, allowed tensile force at the suspension point, message capacity, short circuit current and so on). Users can specify the structure as well.

Parameter Technical parameter
Item Content Typical value
Quantity of optical fiber 2~144
Protecting tube Material stainless steel tube
Quantity Customer's requirement
Outer diameter/mm 1.5~6
Stranded single wire Material Aluminum clad steel, aluminum, aluminum rod
Diameter/mm 1.5~6
Maximum outer diameter mm 30
Maximum tensile force kN 1000
Maximum sectional area mm² 800
Maximum short circuit current 400-200℃(Ka²*S) 2000
Operating temperature -40~+65
Compressive resistance N/100mm 3000
* The structure of optical cable and quantity of core can be custom-made according to customer requirements.
Characteristic of optical fiber
G.652.D G.655 50/125μm 62.5/125μm
Attenuation @850nm - - ≤3.0dB/km ≤3.0dB/km
@1300nm - - ≤1.0dB/km ≤1.0dB/km
@1310nm ≤0.36dB/km ≤0.36dB/km - -
@1550nm ≤0.22dB/km ≤0.23dB/km - -
Bandwidth @850nm - - ≥500MHz·km ≥200MHz·km
@1300nm - - ≥1000MHz·km ≥600MHz·km
Fiber cutoff wavelength ≤1260nm ≤1260nm - -
Polarization mode dispersion Single optical fiber ≤0.20ps/√km ≤0.20ps/√km - -
Link value (M=20, Q=0.01%) ≤0.10ps/√km ≤0.10ps/√km - -
Main machinery and environment performance
Item Inspection standard procedure of inspection Requirements
tension IEC 60794-4-10 According to the change of optical cable's structure Additional attenuation≤0.05dB
pressure IEC 60794-20-9.4.5 2200N/100mm, 10min, 3 times interval 1m Additional attenuation≤0.1dB, non-mechanical damage
Backward and forward bending IEC 60794-4-20-9.4.3 R=15~20*D Additional attenuation≤0.05dB, non-mechanical damage
seepage test IEC 60794-4-10-9.8 Length of sample:0.5m, 20±5℃, height of the water: 1m, 1h Non-seepage
dripping test IEC 60794-4 Length of sample:0.3m, 70±1℃, 24h The filler and composition won't outflow or drip out.
temperature recycle test IEC 60794-4-20-9.6 -40℃~+70℃ Additional attenuation≤0.1dB