Structure Stainless steel tube Aluminum clad steel wire Preservative oil Aluminum wire
Description OPGW fiber integrates ground electrode and photo-communication functions all in cable one unit. This product is mainly applied to 35kV, 110kV, 220kV, 500kV, 750kV telecommunication lines of high voltage transmission systems built on stilts. OPGW fiber is also suitable for replacing old ground wires of high voltage transmission system built on stilts to add to existing optical communication lines, conduct short circuit current and protect the system from lightning strikes.
SPFO will carefully design the structure of the optical cable according to the specific service environment (like distance between towers, requirement of sag, ice load, wind load, allowed tensile force at the suspension point, message capacity, short circuit current and so on). Users can specify the structure as well.
Parameter Technical parameterItem | Content | Typical value |
Quantity of optical fiber | 2~144 |
Protecting tube | Material | stainless steel tube |
Quantity | Customer's requirement |
Outer diameter/mm | 1.5~6 |
Stranded single wire | Material | Aluminum clad steel, aluminum, aluminum rod |
Diameter/mm | 1.5~6 |
Maximum outer diameter | mm | 30 |
Maximum tensile force | kN | 1000 |
Maximum sectional area | mm² | 800 |
Maximum short circuit current | 400-200℃(Ka²*S) | 2000 |
Operating temperature | ℃ | -40~+65 |
Compressive resistance | N/100mm | 3000 |
* The structure of optical cable and quantity of core can be custom-made according to customer requirements. |
Characteristic of optical fiber | G.652.D | G.655 | 50/125μm | 62.5/125μm |
Attenuation | @850nm | - | - | ≤3.0dB/km | ≤3.0dB/km |
@1300nm | - | - | ≤1.0dB/km | ≤1.0dB/km |
@1310nm | ≤0.36dB/km | ≤0.36dB/km | - | - |
@1550nm | ≤0.22dB/km | ≤0.23dB/km | - | - |
Bandwidth | @850nm | - | - | ≥500MHz·km | ≥200MHz·km |
@1300nm | - | - | ≥1000MHz·km | ≥600MHz·km |
Fiber cutoff wavelength | | ≤1260nm | ≤1260nm | - | - |
Polarization mode dispersion | Single optical fiber | ≤0.20ps/√km | ≤0.20ps/√km | - | - |
Link value (M=20, Q=0.01%) | ≤0.10ps/√km | ≤0.10ps/√km | - | - |
Main machinery and environment performanceItem | Inspection standard | procedure of inspection | Requirements |
tension | IEC 60794-4-10 | According to the change of optical cable's structure | Additional attenuation≤0.05dB |
pressure | IEC 60794-20-9.4.5 | 2200N/100mm, 10min, 3 times interval 1m | Additional attenuation≤0.1dB, non-mechanical damage |
Backward and forward bending | IEC 60794-4-20-9.4.3 | R=15~20*D | Additional attenuation≤0.05dB, non-mechanical damage |
seepage test | IEC 60794-4-10-9.8 | Length of sample:0.5m, 20±5℃, height of the water: 1m, 1h | Non-seepage |
dripping test | IEC 60794-4 | Length of sample:0.3m, 70±1℃, 24h | The filler and composition won't outflow or drip out. |
temperature recycle test | IEC 60794-4-20-9.6 | -40℃~+70℃ | Additional attenuation≤0.1dB |
Features This product is a stranded loose tube cable with large sectional area and higher tensile strength. This optical fiber is suitable for low or high voltage communication lines of different spans. Aerial installed.