Descriptions
Cleanroom FFU
Fan filter units (FFU) draw in air from the top of the module and then exhaust filtered air in a unidirectional air stream at its base. FFUs are perfect for self-contained air purification applications used in cleanroom operations. The FFU is installed on the ceiling of a clean room (25% to 100% cover rate), with general dimensions of 2’*4’ or 4’*4’. These particular units are suitable for the construction of Class 1 to Class 100,000 clean rooms.
Description | CP0601 | CP0602 | CP0603 |
Size | 1170*570*230 | 1170*1170*230 | 570*570*230 |
Air flow(m3/h) | 1400 | 2300 | 800 |
Air speed(m/s) | 0.45 ± 20% | 0.45 ± 20% | 0.45 ± 20% |
Filtration efficiency | HEPA over 99.99%@0.3um | ||
ULPA over 99.99%@0.1um | |||
Noise | ≤ 55dB | ≤ 55dB | ≤ 55dB |
Power supply | 220v,50Hs,Single phase | ||
Power | 0.12KW | 0.25KW | 0.12KW |