Home Temperature Responsive Expansion Valves

Temperature Responsive Expansion Valves

Temperature Responsive Expansion Valve Type & Data of Temperature Responsive Expansion Valve
Model Intermediate pressure (Pi) Operating temperature (tb ) range Connection Capillary length
(MPa) (℃) Inlet×Outlet (m)
(in.)
WTVA WTVB 0.1 50→75 1/2×5/8 SAE&ODF 1.5
0.2 75→85
0.3 80→90
0.4 85→95
0.5 90→101
0.6 94→105
0.7 100→110
0.8 106→115
0.9 111→119
Model Intermediate pressure (Pi) Operating temperature (tb ) range Connection Capillary length
(MPa) (℃) Inlet×Outlet (m)
(in.)
WTVC 0.1 55→85 3/8×1/2 SAE&ODF 1
0.2 65→90
0.3 75→95
0.4 85→100
0.5 90→110
0.6 95→114
0.7 101→116
0.8 106→119
0.9 111→123
Model Opening temperature (tb) range (℃ ) Factory setting opening temperature (℃ ) Connection Inlet×Outlet (in.) Capillary length (m)
WTVA WTVB 65 ~ 105 85 1/2×5/8 SAE & ODF 1.5
WTVC 75 ~ 120 95 3/8×1/2 SAE & ODF 1
Liquid Injection Valve Type & Data of Liquid Injection Valve
Model Opening temperature (tb) range (℃ ) Factory setting opening temperature (℃ ) Connection Inlet×Outlet (in.) Capillary length (m)
WTVP Stationary type. Liquid injection temperature can be customized. 3/8×1/2 SAE 1


Description of Temperature Responsive Expansion Valve
WTV series temperature responsive expansion valves (liquid injection) are usually installed suction side of compressor in refrigeration system to protect the refrigeration system from too high discharge gas or oil temperature.
The capacities of WTVA, WTVB series temperature responsive expansion valve (liquid injection) are large and usually used for large refrigerant system.
WTVP series temperature responsive expansion valve (liquid injection) can work under no influence by suction pressure change, The liqiud injection temperature need to be sent in factory, and no adjusted in using.

Temperature Responsive Expansion Valves

Operating Principle of Liquid Injection Valve
When the discharge gas or oil temperature in refrigeration system is too high, the valve will open. Liquid refrigerant will be fed into the suction side and compression cavity after temperature drop yhrough the valve, and then cool the motor coil and the mixture of refrigerant and oil, which makes the liquid refrigerant entering the evaporator in lower temperature.


Technical Data of Temperature Responsive Expansion Valve
Max. working pressure: 3MPa
Max. testing pressure: 3.5MPa