DUCS Telecom Rectifier System
DUCStelecom rectifier system is designed for applications of small telecommunication. For detailedinformation, this product is composed of three DES rectifier modules, onemonitor module and power distribution section and the depth of 19”2U sub-rack is 255mm. With regard to configuration, it can supplymaximum 48VDC 90A 4.8kwwith one AC input MCB, four MCBsprotected outputs and one battery MCB. Besides that, RS485 and 6 groups of drycontacts are available for customers to choose.
Detailed Specifications:
Model No. | DucS4890 | |
AC Input | ||
Nominal voltage | 220/230Vac with dreading to 110Vac | |
AC input range | Voltage | 90 – 280V AC |
Frequency | 45 – 66Hz | |
Power Factor | >0.99 | |
Max input current | 30A | |
DC Output | ||
Nominal output voltage | 48VDC | |
Range | 42V – 58V | |
Rated output current | 176-290VAC | 90A, 5.4KW |
151-175VAC | 50A | |
90-150VAC | 33A | |
DC Outputs (with MCB protected) | 30A x 2 | |
10A x 2 | ||
Efficiency | 220V AC input | ≥91% |
110VAC input | ≥85% | |
Voltage variation | ≤±1% | |
Current balance | ≤±5% | |
Dynamic Response Time | ≥10ms | |
Battery Output | ||
Nominal voltage | 48VDC | |
Battery Output (with MCB protected) | 1 x 80A | |
Others | ||
Protection | Input over/under voltage | Shutdown with auto recovery |
Power limitation | Adjustable | |
Shortcut | Shutdown with auto recovery | |
Over temperature | auto recovery | |
Output over/under voltage | Shutdown with manual recovery | |
Low battery | Shutdown with auto recovery | |
Isolation | Input to output | 3kV AC/10mA/1min |
Input to ground | 1.5kV AC/10mA/1min | |
Output to ground | 500V AC/10mA/1min | |
Others | ||
Dimension | 482.6mm*255mm*88.1mm - 19"2U | |
Weight | 11kg | |
Ventilation | Twin thermal control fans | |
Working temperature | -20℃~ 55℃ (full load) | |
Storage temperature | -40℃~ 85℃ | |
Standard | ||
LVD | EN60950 | |
EMC | EN 61000-3-2, EN 61000-3-3, CISPR22, CISPR 24 |
Because AC input is available, DUCS telecom rectifier system can workaccording to the configurations set by the monitor. And battery can supplypower until reaching its preset LVD level if there is an AC failure. After theproblem is fixed, the machine will work automatically.