Home ZGQ2Y Automatic Transfer Switches (ATS)

ZGQ2Y Automatic Transfer Switches (ATS)

ZGQ2Y Automatic Transfer Switches CB-class

 


Rated current: 63A~800A
Poles: 3P, 4P
Functions of ZGQ2Y Automatic TransferSwitch CB-class:
Matchable controller:
Y:YCM-Ⅰcontroller. Installation type: integrated type;
YCM-Ⅰcontroller
Electric Capabilities and Functions of YCMseries Controller in ZGQ2Y Automatic Transfer Switch:
1. Voltage detection of main and backup power supply(under-voltage 60%-85% isavailable over-voltage of 120%)
2. Free interchange among the three modes(self-transferself-recovery; self-transfer non self-recovery; electric grid-generator)
3. Fire fighting alarming linkage shift to 0 (insulated contact input)
4. Automatic/manual operation options
5. Issue generator starting signals under electricgrid-generator mode
6. Can set switch on and switch off delay period individually(freelyadjustable range 0.5-30)
Functions of YCM series Controller Used inZGQ2Y Automatic Transfer Switches
(1) Self-transfer and self-recovery(R)
The acquiescent initialization tense is main power supply, when main powersupply goes wrong, the switch will automatically shift to 0 after delay period,and then it will switch to backup power supply after closing and past the delayperiod. The switch will switch to main power supply while it recovers normal.
(2) Self-transfer and non self-recovery(s)
The controller will detect and shift between the normal and backup mode oftwo-way power supply and the acquiescent initialization tense is main powersupply. When voltage of power supply appears abnormal (any path power supplyappears over-voltage, lack phase) the switch will automatically shift to 0position after switching on delay time and transfer to backup power supplyafter switching off delay time, but once main power supply recovers the switchwill not automatically recover, only backup power supply goes wrong will itswitch to main power supply again.
(3) Electric grid-generator (F)
The controller will detect the main power supply, for the main power supplywill not start generating electricity under normal voltage if backup powersupply is being used as a generator. This system will automatically assign agenerator control interface to issue a generating signal (as a set of N.C.contacts) when the electric grid and voltage appears abnormal. After thegenerator starts as usual, the switch will automatically transfer to the backuppower supply after the delay intervals. And while the electric grid voltagerecovers normal the intelligent system will automatically disconnect frombackup power supply after the delay intervals and switch to main power supplythen stop generating.
Structure and Characteristics of ZGQ2Automatic Transfer Switch
ZGQ2 series of Digital Dual Power Automatic Transfer Switch consists of two3-electrode or 4-electrode molded case circuit-breaker and some otheraccessories (assistance, alarming contacts) such as mechanical interlockingsetup and controllers and so on. This series automatic transfer switch isdivided into two types: integrated and split. Controller and implementary device of integrated type are installed on thesame base integrated types while for the split type, the controller is set onthe cabinet panel and the implementary device seatedon the base is installed in the cabinet by the users. There should be a 2-meterlong cable connecting the controller and the implementarydevice.
Characteristics of ZGQ2 Automatic TransferSwitch:
-The reliable mechanical interlocking device and electrical interlockingprotection between two breakers can thoroughly prevent two breakers closing atthe same time
-Intelligent controller applies single chip as controlling core and havefunctions such as compact hardware, powerful functions, easy-expandingcapabilities and high reliabilities
-Have several functions such as short circuit, over-voltage protection,under-voltage, lack phase, automatic transfer and intelligent alarmingabilities etc
- Automatic transfer parameters can be set freely outside
-Intelligent protection abilities of generators
-This automatic transfer switch is equipped with fire control circuits, oncethe fire control center issued a control signal into intelligent controller thetwo breakers will close respectively
-Generator can start signal-issuing abilities and when main power supply goeswrong, ATS controller will issue starting signals and activate the generatorautomatically
Order Notice
While ordering our automatic transfer switch please note the following specs:
-Name. model. specifications, rated current ofbreaker, short circuit identifying capabilities, poles of  circuit breaker(3p/4p), type of circuit breaker(with/without short circuit over-voltage protection)
-Controller mode: (YCM-I or YCM-II)
-Transfer modes: self-transfer and self-recovery<R>self-transferand non self-recovery〈S〉orelectric grid-generator〈F〉
If you have some special requirements or needing to match any otherplastic-shell breakers domestic and abroad, please make it clear in your orderas they are all available from our company.
e.g.: To order an automatic transfer dual power switch, electric grid-generatormode, optional breaker 100Arated current80A 3Pintegrated type
As:ZGQ2Y-100/80A/3P(F)
This conversion device controller applies single chip program. The parameterswe set are based on the types and capabilities of different types. If you needto rectify the parameters please contact with our Technology Dept. or localagent.