Welcome to Leshan, a specialist Chinese power cable provider. This page is dedicated to the PVC insulated power cable. The 6/1kV PVC insulated power cable is used to transmit and distribute electricity on AC rated voltage 0.6/1kV power lines U0/U.
Standards compliance for PVC insulated power cable
GB/T12706.1-2008 (Reference standard: IEC60502-1) Rated Voltage 1kV (Um=1.2kV)
Working conditions for PVC insulated power cable
1. Maximum working temperature: 70℃
2. In case of a short (lasting less than 5 seconds) maximum temperature of the cable conductor will not exceed 160℃
3. Environment temperature should be no lower than 0℃ when laying the cable
4. Bending radius allowance of the insulated cable: Single core cable: Unarmored cable 20D; Steel tape armored cable 15D; Triple core cable: Unarmored cable 15D; Steel tape armored cable 12D
Notes: D= practical external diameter of cable.
Rated cross area(mm2) | 0.5 | 0.75 | 1 | 1.5 | 2.5 | 4 | 6 | 10 | ||
Cu | Non tinned | 36 | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 | |
(Ω/km) | Tinned | 36.7 | 24.8 | 18.2 | 12.2 | 7.56 | 4.7 | 3.11 | 1.84 | |
Al(Ω/km) | / | / | / | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | ||
Rated cross area(mm2) | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | ||
Cu | Non tinned | 1.15 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 | |
(Ω/km) | Tinned | 1.16 | 0.734 | 0.529 | 0.391 | 0.27 | 0.195 | 0.154 | 0.126 | |
Al(Ω/km) | 1.91 | 1.2 | 0.868 | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 | ||
Rated cross area(mm2) | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 | ||
Cu | Non tinned | 0.0991 | 0.0754 | 0.0601 | 0.047 | 0.0366 | 0.0283 | 0.0221 | 0.0176 | |
(Ω/km) | Tinned | 0.1 | 0.0762 | 0.0607 | 0.0475 | 0.0369 | 0.0286 | 0.0224 | 0.0177 | |
Al(Ω/km) | 0.164 | 0.125 | 0.1 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
Type | Description | Application Occasion | |
Cu | Al | ||
VV | VLV | PVC insulation PVC sheath power cable | These cables can be laid indoors, in tunnels, cable furrows or pipes. It cannot bear an outside mechanical force. |
VV22 | VLV22 | PVC insulation, steel tape armor, PVC sheath power cable | These cables are applicable for use underground, and can bear a limited mechanical force. |
VV62 | VV62 | PVC insulation, has none of the magnetism steel tape armor does, PVC sheath power cable. | |
VV32 | VLV32 | PVC insulation, thin steel-wire armor, PVC sheath power cable | These cables are applicable for wells or underwater in bodies of water. They can bear a larger pressure with a lead to pull the force. |
VV72 | VLV72 | PVC insulation, has none of the magnetism thick steel-wire armor does, PVC sheath power cable | |
VV42 | VLV42 | PVC insulation, thick steel-wire armor, PVC sheath power cable | |
Hint specially | The single-core magnetism material that packs the cable is not applicable for use with AC power supply packs. The necessary hour limit uses a single-core 62 or 72 type power pack for the cable. In order to prevent a decrease in the cable’s electric current transport ability, it does not allow the (cent) [GF1] to cross the magnetism piping when used with a single core cable. |
Cross No | 1 | 2 | 3 | 3 1 | 4 | 3 2 | 4 1 | 5 |
Area | 4~500 | 2.5~500 | 2.5~300 | 4~300 | 2.5~300 | 2.5~300 | 4~300 | 2.5~95 |