This PVC insulated wire is applicable on the distribution of AC electricity with rated voltage below 450/750V. PVC insulated wire is an electrical wire coated with a PVC jacket to protect against moisture and physical damage to the conductor inside.
The PVC insulated wire is built to the standard
GB/T 5023-2008 PVC insulated cables with voltages no higher than 450/750V
JB/T PVC insulated cables and wires with voltages no higher than 450/750V
Characteristic of use
The maximum temperature of the conductor is 70°C and 90°C
Type | Description | Core number | Area (mm2) | Voltages (V) | Standard |
227IEC01 (BV) | Single-core hard drawn non-sheathed cable | 1 | 1.5~400 | 450/750 | GB5023.3 |
227IEC02 (RV) | Single-core soft drawn non-sheathed cable | 1 | 1.5~240 | 450/750 |
227IEC05 (BV) | Single-core solid conductor drawn non sheathed cable for internal wiring is 70°C | 1 | 0.5~1.0 | 300/500 |
227IEC06 (RV) | Single-core soft drawn non sheathed cable for internal wiring is70°C | 1 | 0.5~1.0 | 300/500 |
227IEC07 (BV-90) | Single-core solid conductor drawn non sheathed cable for internal wiring is 90°C | 1 | 0.5~2.5 | 300/500 |
227IEC08 (RV-90) | Single-core soft drawn non sheathed cable for internal wiring is 90°C | 1 | 0.5~2.5 | 300/500 | GB5023.3 |
227IEC10 (BVV) | Light PVC sheathed cable | 2~5 | 1.5~35 | 300/500 | GB5023.4 |
227IEC52 (RVV) | Light PVC sheathed soft wires | 2, 3 | 0.5/0.75 | 300/300 | GB5023.5 |
227IEC53 (RVV) | Ordinary PVC sheathed soft wires | 2~5 | 0.75~2.5 | 300/500 |
BV | Cu-core PVC insulated wires | 1 | 0.75/1.0 | 300/500 | JB8734.2 |
BLV | Al-core PVC insulated wires | 1 | 2.5~400 | 450/750 |
BVR | Cu-core PVC insulated soft wires | 1 | 2.5~70 | 450/750 |
BVV | Cu-core PVC insulated and sheathed circle type wires | 1 | 0.75~10 | 300/500 | JB8734.2 |
BLVV | Al-core PVC insulated and sheathed circle type cable | 1 | 2.5~10 | 300/500 |
BVVB | Cu-core PVC insulated and sheathed Flat type cable | 2, 3 | 0.75~10 | 300/500 |
BLVVB | Al-core PVC insulated and sheathed Flat type cable | 2, 3 | 2.5~10 | 300/500 |
RVVP | Cu-core PVC insulated and sheathed the Metallic shielded soft cable | 1~24 | 0.08~2.5 | 300/500 | JB8734.5 |
Rated cross area(mm2) | 0.5 | 0.75 | 1 | 1.5 | 2.5 | 4 | 6 | 10 |
Cu (Ω/km) | Non tinned | 36 | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 |
Tinned | 36.7 | 24.8 | 18.2 | 12.2 | 7.56 | 4.7 | 3.11 | 1.84 |
Al (Ω/km) | / | / | / | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 |
Rated cross area(mm2) | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 |
Cu (Ω/km) | Non tinned | 1.15 | 0.727 | 0.524 | 0.387 | 0.268 | 0.193 | 0.153 | 0.124 |
Tinned | 1.16 | 0.734 | 0.529 | 0.391 | 0.27 | 0.195 | 0.154 | 0.126 |
Al (Ω/km) | 1.91 | 1.2 | 0.868 | 0.641 | 0.443 | 0.32 | 0.253 | 0.206 |
Rated cross area(mm2) | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 |
Cu (Ω/km) | Non tinned | 0.0991 | 0.0754 | 0.0601 | 0.047 | 0.0366 | 0.0283 | 0.0221 | 0.0176 |
Tinned | 0.1 | 0.0762 | 0.0607 | 0.0475 | 0.0369 | 0.0286 | 0.0224 | 0.0177 |
Al (Ω/km) | 0.164 | 0.125 | 0.1 | 0.0778 | 0.0605 | 0.0469 | 0.0367 | 0.0291 |
Nominal Area(mm2) | 0.5 | 0.75 | 1 | 1.5 | 2.5 | 4 | 6 |
silk biggest diameter(mm) | 0.21 | 0.21 | 0.21 | 0.26 | 0.26 | 0.31 | 0.31 |
resistances | No tin-plated | 39 | 26 | 19.5 | 13.3 | 7.98 | 4.95 | 3.3 |
(Ω/km) | Tin- plated | 40.1 | 26.7 | 20 | 13.7 | 8.21 | 5.09 | 3.39 |
Nominal Area(mm2) | 10 | 16 | 25 | 35 | 50 | 70 | 95 |
silk biggest diameter(mm) | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.51 | 0.51 |
resistances | No tin-plated | 1.91 | 1.21 | 0.78 | 0.554 | 0.386 | 0.272 | 0.206 |
(Ω/km) | Tin- plated | 1.95 | 1.24 | 0.795 | 0.565 | 0.393 | 0.277 | 0.21 |
Nominal Area(mm2) | 120 | 150 | 185 | 240 | 300 | 400 | 500 |
silk biggest diameter(mm) | 0.51 | 0.51 | 0.51 | 0.51 | 0.51 | 0.51 | 0.61 |
resistances | No tin-plated | 0.161 | 0.129 | 0.106 | 0.0801 | 0.0641 | 0.0495 | 0.0391 |
(Ω/km) | Tin- plated | 0.164 | 0.132 | 0.108 | 0.0817 | 0.0654 | 0.0495 | 0.0391 |
TableA-1: The current-carrying capacity is on 750V or lower PVC insulate power wire(cable) Applythe model number: BV BLV BVV BLVV
Limit the term : Environment temperature 25°C at air
Area (mm2) | 2-core | 3-core | 4-core |
Cu | Al | Cu | Al | Cu | Al |
1.0 | 12 | / | 11 | / | 10 | / |
1.5 | 16 | / | 15 | / | 13 | / |
2.5 | 24 | 18 | 21 | 16 | 19 | 14 |
4 | 31 | 24 | 28 | 22 | 25 | 19 |
6 | 41 | 31 | 36 | 27 | 32 | 25 |
10 | 56 | 42 | 49 | 38 | 44 | 33 |
16 | 72 | 55 | 65 | 49 | 57 | 44 |
25 | 95 | 73 | 85 | 65 | 75 | 57 |
35 | 120 | 90 | 105 | 80 | 93 | 70 |
50 | 150 | 114 | 132 | 102 | 117 | 90 |
70 | 185 | 145 | 167 | 130 | 148 | 115 |
95 | 230 | 175 | 205 | 158 | 185 | 140 |
120 | 270 | 200 | 240 | 180 | 215 | 160 |
150 | 305 | 230 | 275 | 207 | 250 | 185 |
185 | 355 | 265 | 310 | 235 | 280 | 212 |
Nominal Area (mm2) | category | Insulate thickness (mm) | Inside a thickness (mm) | Coat thickness (mm) | Biggest Diameter (mm) | 70°C Least insulates resistance MΩ·km |
2×1.5 | 1 | 0.7 | 0.4 | 1.2 | 10.0 | 0.011 |
2 | 0.7 | 0.4 | 1.2 | 10.5 | 0.010 |
2×2.5 | 1 | 0.8 | 0.4 | 1.2 | 11.5 | 0.010 |
2 | 0.8 | 0.4 | 1.2 | 12.0 | 0.009 |
2×4 | 1 | 0.8 | 0.4 | 1.2 | 12.5 | 0.0085 |
2 | 0.8 | 0.4 | 1.2 | 13.0 | 0.0077 |
2×6 | 1 | 0.8 | 0.4 | 1.2 | 13.5 | 0.0070 |
2 | 0.8 | 0.4 | 1.2 | 14.0 | 0.0065 |
2×10 | 1 | 1.0 | 0.6 | 1.4 | 16.5 | 0.0070 |
2 | 1.0 | 0.6 | 1.4 | 17.5 | 0.0065 |
2×16 | 2 | 1.0 | 0.6 | 1.4 | 20.0 | 0.0052 |
2×25 | 2 | 1.2 | 0.8 | 1.4 | 24.0 | 0.0050 |
2×35 | 2 | 1.2 | 1.0 | 1.6 | 27.5 | 0.0044 |
3×1.5 | 1 | 0.7 | 0.4 | 1.2 | 10.5 | 0.011 |
2 | 0.7 | 0.4 | 1.2 | 11.0 | 0.010 |
3×2.5 | 1 | 0.8 | 0.4 | 1.2 | 12.0 | 0.010 |
2 | 0.8 | 0.4 | 1.2 | 12.5 | 0.009 |
3×4 | 1 | 0.8 | 0.4 | 1.2 | 13.0 | 0.0085 |
2 | 0.8 | 0.4 | 1.2 | 13.5 | 0.0077 |
3×6 | 1 | 0.8 | 0.4 | 1.4 | 14.5 | 0.0070 |
2 | 0.8 | 0.4 | 1.4 | 15.5 | 0.0065 |
3×10 | 1 | 1.0 | 0.6 | 1.4 | 17.5 | 0.0070 |
2 | 1.0 | 0.6 | 1.4 | 19.0 | 0.0065 |
3×16 | 2 | 1.0 | 0.8 | 1.4 | 21.5 | 0.0052 |
3×25 | 2 | 1.2 | 0.8 | 1.4 | 26.0 | 0.0050 |
3×35 | 2 | 1.2 | 1.0 | 1.6 | 29.0 | 0.0044 |
4×1.5 | 1 | 0.7 | 0.4 | 1.2 | 11.5 | 0.011 |
2 | 0.7 | 0.4 | 1.2 | 12.0 | 0.010 |
4×2.5 | 1 | 0.8 | 0.4 | 1.2 | 13.0 | 0.010 |
2 | 0.8 | 0.4 | 1.2 | 13.5 | 0.009 |
4×4 | 1 | 0.8 | 0.4 | 1.4 | 14.5 | 0.0085 |
2 | 0.8 | 0.4 | 1.4 | 15.0 | 0.0077 |
4×6 | 1 | 0.8 | 0.6 | 1.4 | 16.0 | 0.0070 |
4×6 | 2 | 0.8 | 0.6 | 1.4 | 17.0 | 0.0065 |
4×10 | 1 | 1.0 | 0.6 | 1.4 | 19.0 | 0.0070 |
2 | 1.0 | 0.6 | 1.4 | 20.5 | 0.0065 |
4×16 | 2 | 1.0 | 0.8 | 1.4 | 23.5 | 0.0052 |
4×25 | 2 | 1.2 | 1.0 | 1.6 | 28.5 | 0.0050 |
4×35 | 2 | 1.2 | 1.0 | 1.6 | 32.0 | 0.0044 |
5×1.5 | 1 | 0.7 | 0.4 | 1.2 | 12.0 | 0.011 |
2 | 0.7 | 0.4 | 1.2 | 12.5 | 0.010 |
5×2.5 | 1 | 0.8 | 0.4 | 1.2 | 14.0 | 0.010 |
2 | 0.8 | 0.4 | 1.2 | 14.5 | 0.009 |
5×4 | 1 | 0.8 | 0.6 | 1.4 | 16.0 | 0.0085 |
2 | 0.8 | 0.6 | 1.4 | 17.0 | 0.0077 |
5×6 | 1 | 0.8 | 0.6 | 1.4 | 17.5 | 0.0070 |
2 | 0.8 | 0.6 | 1.4 | 18.5 | 0.0065 |
5×10 | 1 | 1.0 | 0.6 | 1.4 | 21.0 | 0.0070 |
2 | 1.0 | 0.6 | 1.4 | 22.0 | 0.0065 |
5×16 | 2 | 1.0 | 0.8 | 1.6 | 26.0 | 0.0052 |
5×25 | 2 | 1.2 | 1.0 | 1.6 | 31.5 | 0.0050 |
5×35 | 2 | 1.2 | 1.2 | 1.6 | 35.0 | 0.0044 |
Nominal Area (mm2) | Insulate thickness (mm) | Coat thickness (mm) | Biggest Diameter (mm) | 70 °C Least insulates resistance MΩ·km |
2×0.5 | 0.5 | 0.6 | 6.0/3.6×6.0 | 0.012 |
2×0.75 | 0.5 | 0.6 | 6.4/9×6.4 | 0.010 |
3×0.5 | 0.5 | 0.6 | 6.2 | 0.012 |
3×0.75 | 0.5 | 0.6 | 6.8 | 0.010 |
Nominal Area (mm2) | Insulate thickness (mm) | Coat thickness (mm) | Biggest Diameter (mm) | 70 °C Least insulates resistance MΩ·km |
2×0.75 | 0.6 | 0.8 | 7.6 | 0.011 |
5.2×7.6 |
2×1.0 | 0.6 | 0.8 | 8.0 | 0.010 |
2×1.5 | 0.7 | 0.8 | 9.0 | 0.010 |
2×2.5 | 0.8 | 1.0 | 11.0 | 0.009 |
3×0.75 | 0.6 | 0.8 | 8.0 | 0.011 |
3×1.0 | 0.6 | 0.8 | 8.4 | 0.010 |
3×1.5 | 0.7 | 0.9 | 9.8 | 0.010 |
3×2.5 | 0.8 | 1.0 | 12.0 | 0.009 |
4×0.75 | 0.6 | 0.8 | 8.6 | 0.011 |
4×1.0 | 0.6 | 0.9 | 9.4 | 0.010 |
4×1.5 | 0.7 | 1.0 | 11.0 | 0.010 |
4×2.5 | 0.8 | 1.1 | 13.0 | 0.009 |
5×0.75 | 0.6 | 0.9 | 9.6 | 0.011 |
5×1.0 | 0.6 | 0.9 | 10.0 | 0.010 |
5×1.5 | 0.7 | 1.1 | 12.0 | 0.010 |
5×2.5 | 0.8 | 1.2 | 14.0 | 0.009 |