As a temperature measuring device, the MIC201 temperature transmitter can convert input signals of resistance temperature detector (pt100, pt1000, Cu50, Cu100) and temperature couple (Type K, E, J, T, N, R, S, B) into a scalable signal of 4 to 20mA. It can be directly installed to RTD Form B. Equipped with a special card, the transmitter can follow the DIN35 guide rail installation method.
Features of MIC201 Temperature Transmitter
1. As a temperature sensor, its structure is compact.
2. With the central open hole, you can choose any installation method as you want.
3. The transmitter can monitor the opens-and-shorts.
4. A self-monitoring function is well designed.
5. The transmitter can be controlled by PC or hand.
6. Configurable information memorized.
7. Other features include high precision, low power dissipation, wide range of using environment temperature, and stable work performance. Interfaces to all standard thermocouples and RTDs are available.
8. The electromagnetic compatibility is in accordance with GB/T17626.4-2008 (EN61000-4-4: 2004).
Input | |
Measured variable | Temperature |
Measurement accuracy | 0.2% |
Cold junction compensation temperature range | -40℃~ 85℃ |
Compensation precision | ±1 ℃ |
Output | |
Output signal | 4~ 20mA |
Load resistance | R L ≤ (U e -7.5) /0.021A |
Signal on alarm | I H = 20.08mA ; I L = 3.92mA |
Input sensor break, output current | 20.16mA |
Sensor open-circuit, output current | 3.84mA |
Sampling period | Rating value 0.25s |
Protection | Reverse polarity protection |
Essential parameter | |
Supply voltage | 7.5~ 45V, DC |
Temperature drift | 0.01% F.S./ ℃ |
Damping time | 5-45s (reaching 99% of the final value) |
Insulation strength (between input and output) | 1500V, AC, 1 min |
Insulation resistance (between input and output) | ≥100MΩ |
Electromagnetic compatibility | GB/T17626.4-2008(IEC61000-4-4:2004) |
Minimum range | 50℃ |
Weight | 32g |
Rated operating condition | |
Storage temperature | -50℃~ 105℃ |
Operating temperature | -40℃~ 85℃ |
Relative humidity | ≤85% |
Reference operating conditions | 23℃ |
Input | Type | Measurements range | Output accuracy |
Thermocouples (TC) | T | -200℃~ 400℃ | 1℃/0.2% |
E | -50 ℃~ 1000℃ | 1℃/0.2% | |
J | 0℃~ 1200℃ | 1℃/0.2% | |
K | 0℃~ 1300℃ | 1℃/0.2% | |
N | 0℃~ 1300℃ | 1℃/0.2% | |
R | 0℃~ 1768 ℃ | 2℃/0.2% | |
S | 0℃~ 1768 ℃ | 2℃/0.2% | |
B | 600℃~ 1820℃ | 2℃/0.2% | |
Resistance temperature (RT) | Pt100 | -200℃~ 850℃ | 0.4℃/0.2% |
Pt1000 | -200℃~ 300℃ | 0.4℃/0.2% | |
Cu50 | -50℃~ 150℃ | 0.4℃/0.2% | |
Cu100 | -50℃~ 150℃ | 0.4℃/0.2% | |
The output accuracy error takes the greater one of the two values |
Reference conditions: 23℃ (73.4℉) ± 5℃
Function declaration of MIC201 Temperature Transmitter
Output limits:
Underranging linear drop to 3.92 mA
Overranging linear rise to 20.08 mA
Signal on alarm:
Sensor break drop to 20.16mA
Sensor short-circuit drop to 3.84mA
Configuration of MIC201 Temperature Transmitter
MICC201 PC software (configurable)
MICC201 USB connector
Configuration equipment: MICC201 handheld operator
Configuration parameter: input sensor type and measuring range, output damping time and demarcate smart transmitter.
Electrical connections of MIC201 Temperature Transmitter