Scope of Application Model: WYJZWFY4
Suitable for outdoor environment with pollution class of IV
Rated voltage: 72.5kV (applicable to 120-1600mm²)
126kV (applicable to 240-1600mm²)
145kV (applicable to 240-1600mm²)
252kV (applicable to 400-2500mm²)
Download
Features The stress cone in the cable termination is made of imported EPDM through rubber injection molding, and is held in place by a spring cone to address problems caused by aging-induced relaxation; the cover of the stress cone isolates the cone from the insulating filler, ensuring good contact between the stress cone and the out semi-conducting layer of the cable. This guarantees the long-term and stable operation of the cable termination;
The cable termination is made using multilayer sealing structure to avoid water seepage and oil leakage during operation;
The outer insulator of the cable termination has rain sheds of different sizes, which help minimize the possibility of pollution and flashovers;
The outer insulator with silicone rubber rain sheds has the properties of anti-ultraviolet ray, anti-aging, and anti-explosion, and whose weight is less than half of the porcelain termination;
Test standard of IEC 60840, GB/T 11017, IEC 620607, and GB/T 18890; Cable Lug Specifications
Max. system voltage | Cable nominal cross-section | Lug hole distance C (mm) | Connecting hole of lug Q (mm) | Palm width of cable lug D (mm) | Palm length of cable lug L (mm) |
72.5kV | 120 mm2-400 mm2 | 35 | 14 | 63 | 80 |
500 mm2-800 mm2 | 45 | 14 | 80 | 100 |
1000 mm2-1600 mm2 | 50 | 17 | 100 | 110 |
126kV-145kV | 240 mm2-400 mm2 | 35 | 14 | 63 | 80 |
500 mm2-800 mm2 | 45 | 14 | 80 | 100 |
1000 mm2-1600 mm2 | 50 | 17 | 100 | 110 |
252kV | 400 mm2-800 mm2 | 45 | 14 | 80 | 100 |
1000 mm2-1600 mm2 | 50 | 17 | 100 | 110 |
2000 mm2-2500 mm2 | 50 | 18 | 125 | 140 |
Termination Dimensions
Max. system Voltage | 72.5kV | 126kV | 145kV | 252kV |
H (mm) | 1100 | 1400 | 1580 | 2700 |
A (mm) | 1600 | 1900 | 2080 | 3210 |
B (mm) | 1820 | 2120 | 2300 | 3395 |
Base Plate Mounting Dimensions
Max. system voltage | 72.5kV-145kV | 252kV |
N (mm) | 21 | 32 |
M (mm) | 30 | 40 |
K (mm) | 270 | 450 |
U (mm) | 318 | 566 |
X (mm) | 450 | 800 |
Notice When Ordering: Cable configuration and the cross-sectional area of earth wire shall be provided when ordering. Cable configuration and the cross-sectional area of earth wire shall be provided when ordering.