The surge protector is suitable for use in the power supply system or communication system with the frequency of AC 50 or 60 Hz and the rated voltage not exceeding 380 V. It offers protection against the surge caused by direct and indirect lightning or other transient overvoltage.
This surge suppressor satisfies the demand for surge protection in the home, tertiary industry, and industrial areas. It provides several protection modes, including phase to phase, phase to ground, phase to neutral, neutral to ground, and their combinations.
Note
Maximum continuous operating voltage Ue: 320V, 385V, 420V
Test level: I
Voltage protection level: Up<2.0, 2.5, 3.0kV
Maximum discharge current (8/20us) Imax: 60, 80, 100KA
Nominal discharge current (8/20us) In: 30, 40, 60KA
Code: ND10-C
a. Altitude: not exceeding 2000m
Ambient air temperature: Normal range: -5 ~ 40℃
Extended range: -40 ~ 80℃
Relative humidity: room temperature 30%-90%
b. No significant shake and vibration in the installation place
c. No risks of explosion in the medium, medium non-metal corrosion, or damage to the insulation of gas and dust (including conductive dust)
Conforming to GB18802.1 or IEC61643-1, the ND10-B series surge protective device, hereinafter referred to as SPD, is suitable for use in the power supply system with the rated voltage below AC 380V and the frequency of 50 or 60 Hz. It is used for protection against surge resulting from direct or indirect lightning or other transient voltages. SPD offers common mode protection and differential mode protection.
Model Specification | ND10-B/100 | ND10-B/80 | ND10-B/60 | ND10-B/120 | ||||||||||||
Grid operation voltage Un (V) | 2P | 1P N | 4P | 3P N | 2P | 1P N | 4P | 3P N | 2P | 1P N | 4P | 3P N | 2P | 1P N | 4P | 3P N |
Maximum continuous operating voltage Uc (V) | 275/420 | 275/420 | 140/275 | 275/420 | 140/275 | 275/420 | 275/420 | 275/420 | ||||||||
Voltage protection level Up (kV)< | 2.8/3.0 | 2.4 | 2.4 | 3.0/3.5 | ||||||||||||
Maximum discharge current | 100 | 80 | 60 | 120 | ||||||||||||
Nominal discharge current | 60 | 40 | 30 | 80 | ||||||||||||
Response time ns | <25 | |||||||||||||||
Protection class | IP20 | |||||||||||||||
Use | Line Protection |
Our surge protector is built with a disconnector. When it fails due to overheat or breakdown, the disconnector can automatically disconnect the SPD from the power grid and issue an indication signal. When the surge protector works normally, the visual window displays white; when it fails, the window shows red.
Installation
1. This SPD is installed in the LPZOB or the junction of LPZ1 area and LP22 area with a 35mm standard rail. Multi-strand copper wire with the cross-section of 2.5 to 35 mm2 is used for connection.
2. Each pole of SPD must be set with protective device, such as a fuse or miniature circuit breaker.
The ND15 series surge protector is used for protection against surge caused by direct or indirect lightning or other transient voltages in the power supply systems, like IT, TT, TN-C, TN-S, and TN-CS, with the frequency of AC 50 or 60 Hz and the rated voltage of 380V.
This surge protection device is in line with GB18802.1 or IEC61643-1. According to the IEC 61643-1: 1998-02, it belongs to a Class B surge protector, suitable for use in high lightning-risk areas.
Model Specification | ND15-D/15 | ND15-C/40 | ND15-B/65 |
Grid operation voltage Un (V) | 380 | 380 | 380 |
Maximum continuous operating voltage Uc (V) | 420 | 420 | 420 |
Voltage protection level Up (kV)< | ≤1.8 | ≤1.8 | ≤1.8 |
Maximum discharge current | 15 | 40 | 65 |
Nominal discharge current | 8 | 20 | 35 |
Response time ns | <25 | ||
Protection class | IP20 | ||
Installation | 35mm Track | ||
Case material | Flame-retardant PC | ||
Remote telesignalling contact type | Normally open contact | ||
Terminal performance | AC220V 1A DC30V 1A COS Φ=1 | ||
Cross-section of terminal conductor for remote signaling | 1.5mm2 single strand/double strand |
Number of poles: 1, 2 ,3, 4
Main Technical ParametersModel Specification | |||||
Grid operation voltage Un (V) | 200V380V | 220V 380V | 220V 380V | 220V 380V | 220V 380V |
Maximum continuous operating voltage Uc (V) | 385V 420V | 385V 420V | 385V 420V | 385V 420V | 385V 420V |
Voltage protection level Up (kV) | ≤4.0 ≤4.5 | ≤3.4 ≤3.7 | ≤2.8 ≤3.2 | ≤2.4 | ≤1.8 ≤2.2 |
Maximum discharge current | 150 | 120 | 100 | 80 | |
Nominal discharge current | 100 | 80 | 60 | 40 | |
Response time ns | <100 | ||||
Access wire cross-sectional are a L/N (mm ²) | 20, 35 | 16, 25 | 16, 25 | 16, 25 | |
Access ground wire cross-sectional Are a PE(mm ²) | 35 | 20, 35 | 25, 35 | 25, 35 | |
Fuse or circuit breaker selection | 63A, 35A | 63A, 100A | 63A, 100A | 63A | |
Cross-sectional area of the communication, alarm line | ≥1.5 | ||||
Work environment | -40 ℃~ 85 ℃ | ||||
Relative humidity | ≤95% | ||||
Installation | Standard to the track | ||||
Case material | Glass fiber reinforced plastic |