Home Y5W, Y10W Series Porcelain Surge Arrester

Y5W, Y10W Series Porcelain Surge Arrester

Our company has provided porcelain surge arrester since the inception in 1991. We can now offer such product in a variety of specifications. Our product housing is made of porcelain from Jingdezhen, a city famous for high quality porcelain in northeastern Jiangxi province. Due to our long-term, large-quantity purchase, we have fixed material supplier, thus greatly reducing the production costs.


The key component of our porcelain surge arrester, zinc oxide-based metal oxidevaristor, is brand new and of high quality. It not only makes our products have excellent volt-ampere characteristics and fast steep wave response but also improves the product's overvoltage flow capacity and reduces discharge dispersion.


The varistor and aluminum pole are wound by multiple layers of weftless binding tape. The assembly is then heated in the energy-saving hot air circulation oven for 6 hours to cure the weftless binding tape, thus achieving the purpose of better protecting the varistor and aluminum pole. Also, there is no gap between the varistor and aluminum pole due to the adoption of an electrical strapping machine. This effectively prevents the glue in the weftless binding tape penetrating.

Y5W, Y10W Series Porcelain Surge Arrester

Manufactured in the cleanroom, our product is free from dust intrusion. The workers all have 7 or 8 years of experience in producing this type of product, thus ensuring product quality to some extent. In addition, our products with the rated voltage greater than 35kV are all subjected to at least 24 hours of water boiling experiment and the water temperature exceeds 80℃, so they enjoy high quality and achieve great lightning protection effect.


Our porcelain surge arrester is pollution-resistant, cleaning-free, explosion-proof, and quakeproof, but it is larger and heavier, thus inconvenient and costly to transport, than the product with polymeric housing. Customers can choose appropriate product according to their own needs.


Technical Parameter of Porcelain Surge Arrester
Service condition Model Rated Voltage(kV) System nominal voltage(kV) Continuous operating voltage(kV) U1mA reference voltage (kV) ≥ Max. residual voltage (kV) 2000μs square wave current impulse withstand(A) 4/10μs high current impulse(kA)
1/4μs steep current impulse 8/20 μs lightning current impulse 30/60 μs switching current impulse
Low voltage Y1.5W-0.28/1.3 0.28 0.22 0.24 0.6 / 1.3 / 75 25
Y1.5W-0.5/2.6 0.5 0.38 0.42 1.2 / 2.6 /
Distribution Y5WS-3.8/17 3.8 3 3.2 7.5 19.6 17.0 14.5 100 65
Y5WS-5/17 5 3 4.0 7.5 19.6 17.0 14.5
Y5WS-7.6/30 7.6 6 4.0 15 34.5 30.0 25.5
Y5WS-10/30 10 6 8.0 15 34.6 30.0 25.5
Y5WS-17/50 17 10 13.6 25 57.5 50.0 42.5
5KA Substation (Z) Y5WZ-3.8/13.5 3.8 3 3.2 7.2 14.5 13.5 11.5 200 65
Y5WZ-7.6/27 7.6 6 4.0 14.4 31 27 23
Y5WZ-10/27 10 6 8.0 14.4 31 27 23
Y5WZ-17/45 17 10 13.6 24 51.8 45 38.3
Y5WZ-42/134 42 35 23.4 73 154 134 114 400 100
Y5WZ-51/134 51 40.8 73 154 134 114
Y5WZ-52.7/134 52.7 42.2 73 154 134 114
Y5WZ-54/134 54 43.2 73 154 134 114
Y5WZ-84/221 84 66 67.2 121 254 221 188 600 100
Y5WZ-90/224 90 72.5 130 258 224 190
Y5WZ-94/224 94 75.5 134 270 234 198
Y5WZ-96/250 96 110 75 140 287 250 212 600 100
Y5WZ-100/260 100 78 145 299 260 221
Y5WZ-102/260 102 80 148 305 266 226
Y5WZ-108/281 108 84 157 323 281 239
Y5WZ-116/302 116 88.2 168 347 302 256
10KA Substation (Z) Y10WZ-51/134 51 35 40.8 73 154 134 114 400 100
Y10WZ-52.7/134 52.7 42.2 73 154 134 114
Y10WZ-72/184 72 66 57 105 211 184 165 600 100
Y10WZ-75/223 75 60 127 256 223 190
Y10WZ-75/230 75 60 127 265 230 196
Y10WZ-75/250 75 60 127 288 250 213
Y10WZ-84/215 84 67.2 122 245 215 181
Y10WZ-90/235 90 72.5 130 264 235 201
Y10WZ-96/250 96 110 75 140 280 250 212 600 100
Y10WZ-100/260 100 78 145 291 260 221
Y10WZ-102/266 102 79.6 148 297 266 226
Y10WZ-108/281 108 84 157 315 281 239
Y10WZ-116/302 116 88 168 338 302 257
Y10WZ-120/300 120 96 174 335 300 270
Y10WZ-126/328 126 95.8 183 367 328 279
Y10WZ-150/400 150 115 230 444 400 352

Service condition Model Rated voltage(kV) System nominal voltage(kV) Continuous operating voltage(kV) U1mA reference voltage (kV) Max. residual voltage (kV) 2000μs square wave current impulse withstand(A) 4/10μs high current impulse(kA)
1/4μs steep current impulse 8/20 μs lightning current impulse 30/60 μs switching current impulse
10KA Substation (Z) Y10WZ-192/500 192 220 150 280 560 500 426 600,800, 1000 100
Y10WZ-200/520 200 156 290 582 520 442
Y10WZ-204/532 204 159 296 594 532 452
Y10WZ-216/562 216 168.5 314 630 562 478
20KA Substation Y20WZ-200/566 200 220 152 304 634 566 464 1200 100
Transformer neutral point Y1.5W-55/132 55 110 43 79 / 132 126 400 65
Y1.5W-60/144 60 48 85 / 144 135
Y1.5W-72/186 72 58 103 / 186 174
Y1.5W-73/200 73 58 105 / 200 174
Y1.5W-96/260 96 500 77 137 / 260 243 600 100
Y1.5W-144/320 144 220 116 205 / 320 299
Y1.5W-207/440 207 330 166 292 / 440 410
Capacitor (R) Y5WR-3.8/13.5 3.8 3 2.0 7.2 / 13.5 10.5 400 65
Y5WR-5/13.5 5 3.8 7.2 / 13.5 10.5
Y5WR-10/27 10 6 8.0 14.4 / 27 20.8
Y5WR-17/45 17 10 13.6 24 / 45 38.3
Y5WR-51/134 51 35 40.8 73 / 134 105
Y5WR-84/221 84 66 67.2 121 / 221 176
Y5WR-90/235 90 72.5 130 / 235 190
Motor (D) Y2.5WD-4/9.5 4 3.15 3.2 5.7 10.7 9.5 7.6 400 65
Y2.5WD-8/18.7 8 6.3 6.3 11.2 21.0 18.7 15
Y2.5WD-12.7/31 12.7 9.8 9.8 18.6 34.7 31 25
Y2.5WD-13.5/31 13.5 10.5 10.5 18.6 34.7 31 25.0
Motor neutral point (D) Y1.5WD-2.4/6 2.4 3.2 1.9 3.4 / 6 5 200, 300, 400 65, 100
Y1.5WD-4.8/12 4.8 6.3 3.8 6.8 / 12 10
Y1.5WD-8/19 8 10.5 6.4 11.4 / 19 15.9
Y1.5WD-12/26 12 15.75 9.6 17 / 26 21.6
Y1.5WD-13.7/29.2 13.7 18 11 19.5 / 29.2 24.3
Generator (D) Y5WD-4/9.5 4 3.15 3.2 5.7 10.7 9.5 7.6 400 65
Y5WD-8/18.7 8 6.3 6.3 11.2 21.0 18.7 15.0
Y5WD-13.5/31 13.5 10.5 10.5 18.6 34.7 31 25.0
Y5WD-17.5/40 17.5 13.8 13.8 24.4 44.8 40 32.0
Y5WD-20/45 20 15.8 15.8 28.0 50.4 45 35.0
Y5WD-23/51 23 18 18 31.9 57.2 51 40.8
Y5WD-25/56.2 25 20 20 35.4 62.9 56.2 45.0
Electrified railway Y5WT-17/45 17 10 13.6 24.0 51.8 45 38.3 200 65
Y5WT-42/105 42 27.5 34 60 118 105 89 400 65
Y5WT-42/120 42 34 65 138 120 98
Y10WT-42/120 42 34 65 138 120 98
Y5WT-84/240 84 55 68 130 276 240 196
Y10WT-100/260 100 110 73 145 291 260 221 600 100
Y10WT-200/520 200 220 146 290 582 520 442


Note:
The products listed above are for reference. We can make suitable porcelain surge arresters for customers according to their specific requirements or the drawings provided by them.


Other Picture


Related Names
Lightning Surge Arrester | Lightning Suppressor | Electric Power System Lightning Protector