Work Principle
The water cooled refrigerant dryer uses the principle of refrigeration drying to pass the wet, hot compressed air flow through the refrigerant for heat transfer. As a result, the water vapor contained in the air condenses into a liquid. The liquid water is then filtered out via the separator, attaining the goal of water drying.
This kind of dryer requires setting up a water tower.
Design Standard and Operating Condition
1. Inlet temperature: ≤80℃
2. Refrigerant: R22/R134a/R407c
3. Cooling Water Temperature: 5~40℃
4. Cooling Water Pressure: 0.2~0.7Mpa
5. Compressed Air Temperature: ≤1.1Mpa
6. Pressure Dewpoint: 2~8℃
7. Atmospheric Dewpint: -17~-23℃
8. Volumetric Flow Rate of Cooling Water: 0.157t/h.Q
Model | Air Volume (m3/min) | Power Source | Power (Kw) | Current(A) | Air Pipe Diameter(DN) | Water-Cooling Pipe Diameter(DN) | Dimensions(mm) | Weight(Kg) | ||
Length L | WidthW | HeightH | ||||||||
P-50W | 7.2 | 220V/50HZ | 1.3 | 6 | 50 | ZG1" | 900 | 500 | 920 | 120 |
P-75W | 10 | 220V/50HZ | 2.0 | 9 | 60 | ZG1" | 1200 | 550 | 1100 | 188 |
P-100W | 16 | 220V/50HZ | 3.3 | 6 | 60 | ZG1" | 1200 | 550 | 1100 | 218 |
P-150W | 22 | 380V/50HZ | 3.8 | 7 | 80 | ZG1-1/2" | 1200 | 550 | 1100 | 306 |
P-200W | 30 | 380V/50HZ | 5 | 9.1 | 100FL | ZG1-1/2" | 1300 | 600 | 1200 | 380 |
P-300W | 45 | 380V/50HZ | 6.5 | 12 | 100FL | ZG1-1/2" | 1500 | 650 | 1300 | 466 |
P-400W | 62 | 380V/50HZ | 8 | 15 | 125FL | ZG2-1/2" | 1600 | 700 | 1800 | 628 |
P-500W | 76 | 380V/50HZ | 10 | 18.5 | 160FL | ZG2-1/2" | 1900 | 800 | 2000 | 808 |
P-600W | 85 | 380V/50HZ | 12.5 | 23 | 160FL | ZG2-1/2" | 2200 | 950 | 2600 | 906 |