ACRYLIC CAULK KTR800
Duct Sealant for Air conditioning ducts
The acrylic sealant is fire-resistive, fibrated, water based, indoor/outdoor vapor barrier duct sealant for low, medium and high velocity heating and air conditioning ducts. It should perform as a tough and flexible adhesive and sealant, forming a durable seal against air leakage when used with or without reinforcing tape or membrane.
Specifications
1. Color: Light Gray
2. Base material: Synthetic latex emulsion
3. Consistency: Paste
4. Application consistency: Brush, Trowel, Caulking Gun, or Power Extrusion.
5. Average weight / U.S. GALLON (FSTM 3): 11.6 lbs. (1.35 kg/l)
6. Average non-volatile (FSTM 9A): 55% by volume (69% by weight)
7. Viscosity: soft buttery gel with a typical viscosity range of 130,000 - 160,000 cps.
8. Coverage range (FSTM 72)
A.Brush: 25-50 sq. ft./gal (.6-1.2 m2/l)
B.0.064 in. (1.6 mm) -0.032 in. (0.8 mm) wet film thickness
C.Caulking Gun: 125 lineal ft. per 10.5 fluid oz. tube, 1/8 in. bead (38 m per .31 l tube, 3.2 mm bead.)
D.30 lineal ft. per 10.5 fluid oz. rube, 1/4 in. bead (9 m per .31 tubes, 6.4 mm bead).
9. Temperature resistance: -30ºC to 110ºC
10. Service temperature limits (FSTM 165): 20ºF to 200ºF (-7ºC to 93ºC)
11. Storage temperature of acrylic sealant: 5ºC to 35ºC
12. Application temperature: 5ºC to 50ºC
13. Drying time 73ºF (23ºC) 50% RH (ASTM D 1640)
A.Set to Touch: 1 hour
B.Dry Through: 24 hours
14. Water vapor permeance: ASTM D 3278 Procedure A, 0.45 perms (0.30 metric perms) at 35 mils (.9 mm) dry
15. Wet flammability (ASTM D 3278): No flash to boiling, over 210ºF (99ºC)
16. Surface burning characteristics (ASTM E 84)
A.Flame Spread: 5
B.Smoke Developed: 0
17. Pressure testing: acrylic sealant can be pressure tested within 16 hours dry time above 70ºF (21ºC) and below 60% RH. It should forms a strong bond to galvanized, aluminum or mild steel metal ducts.
18. BS 476 Parts 6 7: Class "O"