1. Application
The TKDB miniature circuit breaker is used for the control and isolation of low voltage terminal distribution in the civilian areas, industrial areas, and other areas. It can protect the distribution lines and electrical equipment from the impact of overload and short circuit. It can also be used for infrequent switching operations.
Instantaneous tripping range | |
B type | (3~5) In |
C type | (5~10) In |
D type | (10~14) In |
Note: In denotes the rated current.
3. Technical Parameters
a. Rated working current: 3, 6, 10, 16, 20, 25, 32, 40, 50, 63
b. Rated working voltage: AC230, 400V
c. Breaking capacity
Tripping characteristics | Rated current (A) | Breaking capacity (kA) |
C type | 1~40 | 6 |
50~63 | 4.5 | |
D type | 1~40 | 4.5 |
d. Mechanical life: 10000 times
4. Standard Compliant
IEC60898-1, GB10963.1
Altitude of installation site | ≤2000m |
Ambient temperature | -35℃~ 70℃ |
Damp heat resistance | Class 2 relative humidity of 95% at 55℃ |
Protection class | IP20 |
No significant vibration or shock |
6. Wiring Capacity
Cables with cross section area of 25mm2 and below
7. Installation Method
TH35mm standard rail, simple and easy installation