Home Low Frequency Online UPS

Low Frequency Online UPS

General Introduction
The PTT series low frequency online UPS takes advantage of the static switch, state-of-the-art DSP technology, high speed microcontroller unit (MCU), complex programmable logic device (CPLD), and the 6th-generation low consumption high power insulated gate bipolar transistor (IGBT) to deliver stable and reliable performance. Moreover, it has large power capacity, and audible alarm is also achieved.


This is a world-class product, and it shows some remarkable properties as illustrated below.


1. Fully Digital Control Technology
a. Ultra stable digital circuit: Our product use advanced digital circuit to replace traditional analog circuit, realizing a great breakthrough in this field. With the help of this digital circuit, the MCU and CPLD could execute circuitry control, parameter setting and operation management in a perfect way, while the self-checking function is also beyond expectation. Moreover, sampling is carried out as long as our product works, and this technique is not only beneficial for self-checking and failure analysis of all the independent circuits on the circuit board, but also ensures stable and pure sine wave output, thus both our product and connected equipment will run in a stable way.


b. Intelligent battery management: This low frequency online UPS introduces an advanced battery management system to realize intelligent control of the battery. This management system adjusts the charge current according to battery configuration, and it also fits for equalizing charge and float charge switch, temperature compensated charging and discharge management. Aside from these, on the monitoring interface, operator could detect the running status of battery to ensure its working efficiency. In general, this intelligent battery management system helps operator manage the battery, and it can prolong battery life by 55% or even longer.


c. Intelligent detection system: The MCU will on-line detect power status, breaker state, fuse condition and working condition of all circuits in a continuous manner. If any failure occurs, the detection system will send alarm message to operator, and activate protection measures at the same time.


d. Parallel redundancy network: With the help of fully digital control technology, a parallel redundancy network of two or more UPS units is established.


2. Advanced Management Software
Our low frequency online UPS comes with a piece of management software to help users program this machine to realize flexible start up and shut down at predetermined time, and this software is also capable of battery discharge, equalizing charge, float charge and other functions. In this way, users will find it is very easy and convenient to manipulate this product.


3. High Precision SMD
Instead of conventional plug-in circuit, PTT series adopts high precision SMD to save space and eliminate undesired defects that are commonly seen for the traditional technology, thereby ensuring safe, reliable and precise running of the integrated circuit.


The combination of 4-layer circuit board and high precision SMD fully avoids interference of high-frequency signals that is generated by the chip itself to other chips, so every chip could work normally without being influenced by other ones, showing improved anti-interference property.


Moreover, due to the application of SMD technology, this online UPS shows the features of high accuracy, good resistance to high temperature, excellent filtering performance as well as stable overall performance, and its service life is extended by 80%.


In addition, the IGBT is characterized by high-speed switch, high working voltage and high working current, and the voltage type driving method requires small control power. The work efficiency of inverter is enhanced, and its temperature rise is small, realizing better reliability.


4. Information Processing Technology for Ultra Clear Interface
a. Audible alarm function is achieved.
b. The humanized large LCD screen allows users to view data in English or Chinese, and the running state of our product could be revealed directly. The touch button, and table-type data and event log facilitate your work greatly.
c. The LED indicators displays work flow status in an intuitive way.


5. Environmentally Friendly and Energy Saving Technology
As shown by the scientific life-cycle assessment which is a technique to assess environmental impacts associated with all the stages of a product's life from-cradle-to-grave, the PTT series online UPS possesses some outstanding properties when it comes to environment protection and energy conservation.


a. The touch panel shows superb resistance to ageing, and the machine body is processed by fluorocarbon paint. Hence, our product is durable and environmentally friendly.
b. The detachable modular design allows simple maintenance, and it also saves resources to a large extent.
c. A new kind of bearing is applied for the fan, and it has unrivaled heat dissipation effect and good energy saving performance.
d. The DLC consumes a little electricity during working, realizing the purpose of energy saving performance.
e. This low frequency online UPS is able to provide green energy with the help of rectification and inversion technologies.


6. Other Advantages
a. Excellent load characteristic: When load changes from 0% to 100%, our product is capable of providing stable and reliable output without being switched to the bypass circuit.
b. Perfect protections: Different kinds of protection functions are achieved, such as over temperature protection, input voltage surge protection, input/output overvoltage and under voltage protections, overcharge and overdischarge protections for battery, output overload and short circuit protections, etc.
c. High-performance dynamic characteristic: This online UPS adopts instantaneous control, effective value and other feedback controls to realize high-performance dynamic control, and the harmonic distortion of output voltage is cut down.
d. Optional input harmonic filter: This device could effectively suppress input harmonic pollution, thus enhancing input power factor and reducing input harmonic current.
e. Optional battery checking module: This module is able to detect parameters of the battery, and then reveals them on the display screen. If there is something wrong with the battery, it will alarm immediately to inform operators.
f. Individualized setting: According to practical applications, our product could be set at different work modes, including UPS working mode, ECO working mode, and EPS working mode.

Low Frequency Online UPS

Applications
Depending on the properties above, this low frequency online UPS has been widely accepted in variety of places, such as banking offices, automatic teller machines, communication base stations, billing centers of communication industry, as well as offices for power, transportation, securities, manufacturing and other industries.





Technical Parameters
Single-phase input single-phase output 1K 2K 3K 4K 6K 8K 10K 15K 20K
Rated capacity 800W 1600W 2400W 3200W 4800W 6400W 8000W 12000W 16000W
Product type Low frequency double conversion online UPS
Phase number Single phase (L N G)
Rectifier Nominal input voltage 220VAC
Input voltage range ±25%
Nominal input frequency 50Hz±10%
Input power factor ≥0.85
Ripple factor <2%
Soft start 0~100%, 5 seconds
Charge process Charge mode Charge at constant current first, and then at constant voltage. Temperature compensated charging, automatic switch between float charge and equalizing charge are also provided.
Float charge voltage 55VDC 220VDC
Equalizing charge voltage 56.8VDC 227VDC
Temperature compensating voltage -3mV/℃ (single)
Charge current 0.1C (Automatically adjusted according to settings of battery capacity)
Charge power 40% of rated capacity
Battery Type Maintenance free lead-acid battery
Capacity Adjustable within 7~999Ah (the capacity range changes with power)
Quantity 8pcs of 12V-battery (total 96V) 16pcs of 12V-battery (total 192V)
Inverter Phase number Single phase
Nominal voltage 220VAC
Output voltage stability ±1% for steady load, ±5% for fluctuated load
Frequency stability 50Hz±0.5% (out of synchronization)
Crest factor >3:1
Output waveform and harmonic distortion Sine wave, <3% for linear load, <5% for non-linear load
Dynamic characteristic Transient voltage <±5% (change from 0% to 100%), recovery time<10ms
Overload protection 115%: normal working
125%: 10 minutes, 150%: 1 minute
200%: 1 second
Efficiency >93% at full load
Bypass Phase number Single phase (L N)
Nominal voltage 220VAC
Transfer time 0ms (static switch)
Protection Input Over/under voltage and frequency
Output Over current, short circuit, low power factor
Battery Overcharge, overdischarge
Temperature High ambient/inverter temperature
Hardware Abnormal auxiliary power supply, circuit breaker tripping, fuse break down, over current and overvoltage for power devices
System parameters Work environment Ambient temperature: 0℃~40℃ Relative humidity: 30%~90% Altitude: <1000m (the power drops by 1% with every increase of 100m in altitude, and the maximum height is 4000m)
Cooling method Forced air cooling
Communication interface RS232 and RS485. Dry contact interface and SNMP card are optional.
Current sharing unevenness for parallel operation ≤3%
Redundancy Series or parallel connected hot standby
Resistance to surge 10/700μS, 5KV 8/20μS, 20KA
IP rating IP20
Safety performance 3000VAC between input/output and ground, leakage current is lower than 3.5mA, and insulation resistance is over 2MΩ (500VDC).
Noise level 45~50dB 50~55dB 55~60dB 55~60dB
Size (W×D×H) 210×520×530mm 220×520×640mm 220×500×760mm 450×600×1200mm
Weight 51kg 58kg 65kg 70kg 73kg 85kg 108kg 265kg 300kg




Table 2
Three-phase input single-phase output 6K 10K 15K 20K 30K 40K 60K 80K
Rated capacity 6KVA 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA
Product type Double conversion online UPS
Phase number Three phase (L N G)
Input power factor >0.8 (>0.95 when with filter or 12-pulse rectifier)
Rectifier Nominal input voltage 220/380VAC, 230/400VAC, 240/415VAC
Input voltage range ±25%
Nominal input frequency 50Hz±10%, 60Hz±10%
Ripple factor <2%
Soft start 0~100%, 5 seconds
Charge process Charge mode Charge at constant current first, and then at constant voltage. Temperature compensated charging, automatic switch between float charge and equalizing charge are also provided.
Float charge voltage 405VDC
Equalizing charge voltage 432VDC
Temperature compensating voltage -3mV/℃ (single)
Charge current 0.1C (Automatically adjusted according to settings of battery capacity)
Charge power 20% of rated capacity
Battery Type Maintenance free lead-acid battery
Capacity Adjustable within 7~999Ah (the capacity range changes with power)
Quantity 30pcs of 12V-battery or 180pcs of 2V-battery (nominal voltage of 360VDC)
Inverter Phase number Single phase (L N G)
Rated power Rated capacity × 0.8
Nominal voltage 220VAC, 230VAC, 240VAC
Output voltage stability ±1% for steady load, ±3% for fluctuated load
Frequency stability 50Hz/60Hz±0.5% (out of synchronization)
Crest factor >3:1
Output waveform and harmonic distortion Sine wave, < 3% for linear load, < 5% for non-linear load
Dynamic characteristic Transient voltage < ±5% (change from 0 to 100), recovery time<10ms
Overload protection 115%: normal working
125%: 10 minutes, 150%: 1 minute
200%: 1 second
Efficiency >93% at full load
Bypass Phase number Single phase (L N)
Nominal voltage 220VAC (230VAC, 240VAC)
Transfer time 0ms (static switch)
Protection Input Over/under voltage and frequency, phase loss and fault
Output Over current, short circuit, low power factor
Battery Overcharge, overdischarge
Temperature High ambient/inverter temperature
Hardware Abnormal auxiliary power supply, circuit breaker tripping, fuse break down, over current and overvoltage for power devices
System parameters Work environment Ambient temperature: 0℃~40℃ Relative humidity: 30%~90% Altitude: < 1000m (the power drops by 1% with every increase of 100m in altitude, and the maximum height is 4000m)
Cooling method Forced air cooling
Communication interface RS232 and RS485. Dry contact interface and SNMP card are optional.
Current sharing unevenness for parallel operation ≤3%
Redundancy Series or parallel connected hot standby
Resistance to surge 10/700μS, 5KV 8/20μS, 20KA
IP rating IP21
Safety performance 3000VAC between input/output and ground, leakage current is lower than 3.5mA, and insulation resistance is over 2MΩ (500VDC).
Noise level 45~50dB 50~55dB 55~58dB 55~60dB
Size (W×D×H) 450×600×1200 600×720×1520 980×800×1800
Weight 108kg 146kg 162kg 178kg 239kg 318kg 445kg 498kg




Table 3
Three-phase input single-phase output 6K 10K 15K 20K 30K 40K 60K 80K
Rated capacity 6KVA 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA
Product type Double conversion online UPS
Phase number Three phase (L N G)
Input power factor >0.8 (>0.95 when with filter or 12-pulse rectifier)
Rectifier Nominal input voltage 220/380VAC, 230/400VAC, 240/415VAC
Input voltage range ±25%
Nominal input frequency 50Hz±10%, 60Hz±10%
Ripple factor <2%
Soft start 0~100%, 5 seconds
Charge process Charge mode Charge at constant current first, and then at constant voltage. Temperature compensated charging, automatic switch between float charge and equalizing charge are also provided.
Float charge voltage 405VDC
Equalizing charge voltage 432VDC
Temperature compensating voltage -3mV/℃ (single)
Charge current 0.1C (Automatically adjusted according to settings of battery capacity)
Charge power 20% of rated capacity
Battery Type Maintenance free lead-acid battery
Capacity Adjustable within 7~999Ah (the capacity range changes with power)
Quantity 30pcs of 12V-battery or 180pcs of 2V-battery (nominal voltage of 360VDC)
Inverter Phase number Single phase (L N G)
Rated power Rated capacity × 0.8
Nominal voltage 220VAC, 230VAC, 240VAC
Output voltage stability ±1% for steady load, ±3% for fluctuated load
Frequency stability 50Hz/60Hz±0.5% (out of synchronization)
Crest factor >3:1
Output waveform and harmonic distortion Sine wave, < 3% for linear load, < 5% for non-linear load
Dynamic characteristic Transient voltage < ±5% (change from 0 to 100), recovery time < 10ms
Overload protection 115%: normal working
125%: 10 minutes, 150%: 1 minute
200%: 1 second
Efficiency >93% at full load
Bypass Phase number Single phase (L N)
Nominal voltage 220VAC (230VAC, 240VAC)
Transfer time 0ms (static switch)
Protection Input Over/under voltage and frequency, phase loss and fault
Output Over current, short circuit, low power factor
Battery Overcharge, overdischarge
Temperature High ambient/inverter temperature
Hardware Abnormal auxiliary power supply, circuit breaker tripping, fuse break down, over current and overvoltage for power devices
System parameters Work environment Ambient temperature: 0℃~40℃ Relative humidity: 30%~90% Altitude: < 1000m (the power drops by 1% with every increase of 100m in altitude, and the maximum height is 4000m)
Cooling method Forced air cooling
Communication interface RS232 and RS485. Dry contact interface and SNMP card are optional.
Current sharing unevenness for parallel operation ≤3%
Redundancy Series or parallel connected hot standby
Resistance to surge 10/700μS, 5KV 8/20μS, 20KA
IP rating IP21
Safety performance 3000VAC between input/output and ground, leakage current is lower than 3.5mA, and insulation resistance is over 2MΩ (500VDC).
Noise level 45~50dB 50~55dB 55~58dB 55~60dB
Size (W×D×H) 450×600×1200 600×720×1520 980×800×1800
Weight 108kg 146kg 162kg 178kg 239kg 318kg 445kg 498kg




Table 4
Three-phase input three-phase output 80KVA 100KVA 120KVA 160KVA 200KVA 250KVA 300KVA 400KVA
Rated capacity 80KVA 100KVA 120KVA 160KVA 200KVA 250KVA 300KVA 400KVA
Product type Low frequency double conversion online UPS
Phase number Three phase (L N G)
Input power factor ≥0.85 when with 6-pulse rectifier, ≥0.99 when with 12-pulse rectifier and filter
Rectifier Nominal input voltage 380VAC
Input voltage range ±25%
Nominal input frequency 50Hz±10%, 60Hz±10%
Input harmonic current <30% for 6-pulse rectifier, <5% for 12-pulse rectifier and filter
Ripple factor <2%
Soft start 0~100%, 5 seconds
Charge process Charge mode Charge at constant current first, and then at constant voltage. Temperature compensated charging, automatic switch between float charge and equalizing charge, programmable automatic maintenance for charge and discharge at fixed time are also provided.
Float charge voltage 432VDC
Equalizing charge voltage 464VDC
Temperature compensating voltage 3mV/℃ (single)
Charge current 0.1C (Automatically adjusted according to settings of battery capacity)
Charge power 20% of rated capacity
Battery Type Maintenance free lead-acid battery
Capacity Adjustable within 7~999Ah (the capacity range changes with power)
Quantity 32pcs of 12V-battery or 192pcs of 2V-battery (nominal voltage of 384VDC)
Inverter Phase number Three phase N
Rated power Rated capacity × 0.9
Nominal voltage 380VAC
Output voltage stability ±1% for steady load, ±3% for fluctuated load
Frequency stability 50Hz/60Hz±0.5% (out of synchronization)
Crest factor >5:1
Output waveform and harmonic distortion Sine wave, <3% for linear load, <5% for non-linear load
Dynamic characteristic Transient voltage <±5% (change from 0% to 100%), recovery time<10ms
Unbalance load voltage ≤±5%
Overload protection 115%: normal work, 125%: 60 minutes, 150%: 10 minutes, 200%: 10 seconds
Efficiency >95% at full load
Bypass Phase Three phase N
Nominal input voltage 380VAC
Nominal output voltage 380VAC
Transfer time 0ms (static switch)
Protections Input Over/under voltage and frequency, phase loss and fault
Output Over current, short circuit, low power factor
Battery Overcharge, overdischarge
Temperature High ambient/inverter temperature
Hardware Abnormal auxiliary power supply, circuit breaker tripping, fuse break down, over current and overvoltage for power devices
System parameters Economical operation mode The overall efficiency when running under ECO mode could reach up to 98%.
Audible alarm Audible alarm is available if UPS failure occurs.
Working environment Ambient temperature: -30℃~50℃ Relative humidity: 30%~90% Altitude: <2000m (the power the power drops by 1% with every increase of 100m in altitude, and the maximum height is 4000m)
Cooling method Forced air cooling
Communication interface RS232 and RS485. Dry contact interface and SNMP card are optional.
Redundancy Series or parallel connected hot standby
Resistance to surge 10/700μS, 5KV 8/20μS, 20KA
IP rating IP31
Safety performance 3000VAC between input/output and ground, leakage current is lower than 3.5mA, and insulation resistance is over 2MΩ (500VDC).
Noise level 60~65dB 65~70dB
Size (W×D×H) 980×800×1800mm 1380×950×1800mm 1600×1150×1800mm
Weight 560kg 850kg 910kg 1320kg 1680kg 1750kg 1830kg 1980kg



Related Names