Home High Frequency Online UPS

High Frequency Online UPS

General Introduction
The high frequency online UPS is a new generation intelligent product, and it is especially designed for IT equipment, network communication equipment and other devices that have strict requirements for power supply. Considering the practical needs of some customers that ask for extremely high reliability, we also provide long backup time UPS aside from conventional type. Moreover, for models whose capacities are over 6KVA, active/standby failover configuration is available, thus greatly lowering failure rate as well as improving working reliability. In this way, some important equipment is provided with safe and reliable power supply.

High Frequency Online UPS

Advantages
1. Double Conversion Technology
The online double conversion method is able to support the protected equipment with continuous green power supply, and this method refers to accepting AC input, rectifying to DC for passing through the rechargeable battery, then inverting back to AC output. Thus, the key electrical appliances will not be affected by power failure, instable voltage, frequency variation, harmonic distortion and other anomalies.


2. Sine Wave Output
For both battery mode and mains supply mode, this high frequency online UPS will offer sine wave output with low harmonic distortion, thus providing reliable power for connected loads.


3. Zero Transfer Time
Under the condition that mains supply fails or restores, there is no transfer time between battery mode and mains supply mode. Hence, the protected equipment will run continuously for some extra time.


4. Input Live Wire and Neutral Wire Detection
This function is available for models of 1~3K(S), and it is adopted to avoid reverse connection of live and neutral wires of mains supply.


5. Input Power Factor Correction
With the help of this function, the input power factor could reach up to over 0.95 at full load, thus ensuring excellent power quality.


6. DC Start
If our high frequency online UPS is needed to start up computers or other loads when mains supply fails, the storage battery could be directly used to realize DC start, making our product more reliable and convenient.


7. Bypass Protection
The bypass circuitry enhances our product's ability to deal with emergencies, and if the connected load has some special requirements for power supply, such as the input voltage shouldn't be too high, bypass overvoltage protection will be carried out to make the load get rid of the danger of overvoltage.


8. Auto Start
When mains supply is under abnormal state, our product will be switched to battery mode in order to provide power until it shuts down automatically as a result of the battery's low voltage. Then, when mains supply recovers, our product will be turned on automatically to supply power, avoiding the need of manual start up.


9. Long Backup Time Model
Aside from standard types, we could also provide customers with long backup time type online UPS. If appropriate battery is applied, 8 hours of backup power would be offered, which is long enough to meet practical applications. On the other hand, the long backup time type also has improved recharging property, and the initial charge current is about 5A~10A.


10. Compatible with Generator
Due to the wide voltage and frequency input ranges, our product is compatible with major generators on the market. It has a longer life span, and it can purify the power electricity produced by generators, thus supplying clean, safe and stable power for connected equipment.


Applications
Owing to the advantages demonstrated above, our high frequency online UPS is commonly accepted in different fields, such as server, bank, security system, medical system, voice over IP, laboratory equipment, precise instrument, network communication equipment, manufacturing and control systems, etc.





Technical Parameters
Model PR1K/1KS PR2K/2KS PR3K/3KS
Rated capacity 1KVA/0.7KW 2KVA/1.4KW 3KVA/2.1KW
Input Rated voltage 220VAC
Voltage range 115-300VAC
Frequency range 46-54Hz (adjustable by software)
Power factor >0.98
Output Voltage 220VAC±2%
Frequency 50Hz±0.1% (battery mode)
Waveform Pure sine wave
Total harmonic distortion (THD) ≤3% for linear load, ≤6% for non linear load
Overload capability Mains supply mode: After 30 seconds when overloaded with 105%-150%, or 300ms when overloaded with >150%, it will be switched to bypass mode and send alarm message.
Battery mode: After 30 seconds when overloaded with 105%-150%, or 300ms when overloaded with >150%, it will send alarm message and stop voltage output.
Crest factor 3:1
Battery Type Maintenance free valve-regulated lead-acid battery
Nominal DC voltage 36VDC 72VDC/96VDC 96VDC
Backup time (full load / half load) 5/15 minutes 5/15 minutes 5/15 minutes
Transfer time 0ms (mains supply and battery)
Protection functions Overload, overheating, short circuit, under voltage, over voltage
Display LED UPS running status, battery capacity, load
LCD UPS running status, input/output voltage and frequency, battery voltage and capacity, load, temperature
Alarm Audible and visual alarm for abnormal mains supply, low battery voltage, overload and failure
Noise level 1 meter <45dB <50dB
Communication interface RS232 port RS-232 (standard)
Intelligent slot SNMP card (optional)
Working environment Ambient temperature 0~40℃
Relative humidity 0%-95%, non-condensing
Weight Net weight 15/9kg 26/13.5kg (72V), 34/17kg (96V) 35/18kg
Product size W×L×H 145×400×220mm 192×460×340mm
Packing size W×L×H 500×250×340mm 590×330×510mm
Note: Either LCD or LED display is provided.




Table 2
Model PR6K/6KS PR10K/10KS PR10KS3 PR15KS3 PR20KS3
Rated capacity 6KVA/4.2KW 10KVA/7KW 15KVA/10.5KW 20KVA/14KW
Input Rated voltage 220VAC/230VAC 380VAC
Voltage range 176-276VAC 304-478VAC
Frequency range 46-54Hz
Power factor 0.98 0.95
Output Voltage 220VAC±1%
Frequency 50Hz±0.05Hz (battery mode), mains supply frequency tracking
Power factor 0.7
Waveform Sine wave
Total harmonic distortion (THD) ≤2% for full linear load
Overload capability Mains supply mode: After 30 seconds when overloaded with 105%-150%, or 300ms when overloaded with >150%, it will be switched to bypass mode and send alarm message.
Battery mode: After 30 seconds when overloaded with 105%-150%, or 300ms when overloaded with >150%, it will send alarm message and stop voltage output.
Crest factor 3:1
Battery Type Maintenance free valve-regulated lead-acid battery
Nominal DC voltage 240VDC
Transfer time 0ms (mains supply and battery)
Protection functions Overload, overheating, short circuit, under voltage, over voltage
Display LED UPS running status, battery capacity, load
LCD UPS running status, input/output voltage and frequency, battery voltage and capacity, load, temperature
Alarm Audible and visual alarm for abnormal mains supply, low battery voltage, overload and failure
Noise level 1 meter <55dB <60dB
Communication interface RS232 port RS-232 (standard)
Intelligent slot SNMP card and AS400 card (optional)
Working environment Ambient temperature 0~40℃
Relative humidity 20%-90%, non-condensing
Weight Net weight 90/35kg 93/38kg 39kg 52kg 52kg
Product size W×L×H 260×570×717 mm
Packing size W×L×H 980×730×450 mm
Note: Either LCD or LED display is provided.




Table 3
Model PR 1K PR 1KS PR 2K PR 2KS PR 3K PR 3KS
Type High frequency online UPS (standard configuration with LCD)
Rated capacity 1KVA/800W 2KVA/1600W 3KVA/2400W
Input Voltage range 115-300VAC
Frequency range 40-60Hz (adjustable)
Power factor 0.99
Output Voltage range 220VAC (1±2%)
Frequency Mains supply mode: the same as mains supply frequency
Battery mode: 50Hz±0.2%
Power factor 0.8
Overload capability 125% for 50 seconds
Battery Type Maintenance free valve-regulated lead-acid battery
Backup time >11 minutes when at half load
Nominal DC voltage 36VDC 72VDC 96VDC
Transfer time 0
Working environment Temperature: 0~40℃
Humidity: 20%-90%
Product size (L×W×H) 350×144×236mm 425×190×336mm
Net weight 12kg 6.5kg 23kg 10.5kg 28kg 11.5kg
Packing size (L×W×H) 450×250×360mm 550×330×500mm




Table 4
Model PR 6K PR 6KS PR 10K PR 10KS PR 10KS3 PR 15KS3 PR 20K3
Type High frequency online UPS (standard configuration with LCD)
Rated capacity 6KVA 10KVA 15KVA 20KVA
Input Voltage range 120-275VAC 210-475VAC, 3P4W G
Frequency range 40-60Hz / 50-70Hz 40-60Hz (adjustable)
Power factor 0.99
Output Voltage range 220VAC (1±1%)
Frequency Mains supply mode: the same as mains supply frequency
Battery mode: 50/60Hz±0.2%
Power factor 0.8
Overload capability 125% for 1 minute
Battery Type Maintenance free valve-regulated lead-acid battery
Quantity 16
Nominal DC voltage 192VDC
Transfer time 0
Working environment Temperature: 0~40℃
Humidity: 20%-90%
Product size (L×W×H) 250×500×620mm 250×500×460mm 250×500×620mm 250×500× 460mm 260×560 ×717mm
Net weight 58kg 18kg 68kg 20kg 39kg 55kg 55kg
Packing size (L×W×H) 675×400×830mm 675×400×670mm 675×400×830mm 675×400× 670mm 725×465 ×980mm



Note: Table 1 and Table 2 are for PR series, while Table 3 and Table 4 are for PR series. Compared with PR, PR series increases the output power factor from 0.7 to 0.8, and the advanced DSP technology enhances load capacity of our online UPS.