I. Control Panel
No AC (under-voltage) Auto-Start Control Panel
Features
1. Auto / Stop / manual function selection
2. Start-up delay: 3-5 seconds, adjustable
3. Stop delay: 0-270 seconds, adjustable
4. Three times automatic start function
5. Alarm indication: underspeed or overspeed, malfunction, low oil pressure, overcurrent, startup failure, high water temperature, high oil temperature pre-alarm, power failure
6. Protection function: underspeed or overspeed, startup failure, low oil pressure, high water temperature, high oil temperature, overcurrent, low frequency, high frequency.
Kaixun controller | Deep - sea controller |
II. ATS Control Cabinet
In the home or other application environments, an automatic transfer switch (ATS) is essential. ATS can achieve the switching between the main power (utility power) and the emergency power (generator set) without operator. When the main power fails or when the voltage drops below 80% of the normal voltage, the ATS will start the emergency generating set within 10 seconds (adjustable), and transfer the load from the main power to the generator set. Conversely, when the main power returns to normal, the ATS will transfer the load from the emergency power (generator set) to the main power, and then stop the emergency power.
Kaihua provides many kinds of ATS control cabinets that match different generator set control systems. Their features are described below.
1. Three functional operation positions: OFF, AUTO, MANUAL
2. Generator set available indicator
3. Main power available indicator
4. Main power or generator set voltage indicator
III. Automatic Remote Monitoring Control Panel
Features
1. The running steps, status, faults and various parameters of the generator set are displayed on the liquid crystal screen.
2. With RS232 or 485 interface, and remote control, telemetry and remote signaling functions
3. Protection function
The generator will be shut down when the following conditions happen:
Start-up failure, overspeed, low speed, high water temperature, low fuel pressure, overcurrent, high or low voltage, velocity transducer with no signal, charging failure, and so on
IV. Parallel Cabinet
Automatic Generator Control Cabinet
Features
1. A special device for parallel operation of generator sets
2. The synchronizing modules from U.S. GAC and the highly integrated controller from Danish DEIF are selectable for parallel operation of diesel generator sets.
3. Manual / automatic multi-parallel, centralized control, easy operation
4. Automatically average active load and reactive load, load imbalance ratio adjustment
5. The number of the generator sets used can be adjusted according to the load capacity changes
6. Automatic frequency tracking, automatic synchronization control
7. No-difference distribution of active and reactive loads
8. Soft-loading, unloading input
9. Reverse power, super-power detection and shutdown protection
10. Short-circuit and over-current protection
Related Names