Indoor Vacuum Contactor, JCZ5-7.2/200/400/630 Technical Parameters
Model | Rated voltage (V) | Rated current | Main contact | Power frequency withstand voltage(V) |
Main circuit | Control circuit | (main circuit) A | Contact gap (mm) | Overtravel (mm) | Terminal pressure (N) | Main circuit | Auxiliary circuit | Control circuit |
JCZ5-7.2/200 | 6000 | 110,200 | 200 | 4.5 | 1.5±0.5 | >85N | 32000 | 2500 | 2000 |
JCZ5-7.2/400 | 6000 | 100,200 | 400 | 4.5 | 1.5±0.5 | >85N | 32000 | 2500 | 2000 |
JCZ5-7.2/630 | 6000 | 110,220 | 630 | 5 | 1.5±0.5 | >85N | 32000 | 2500 | 2000 |
Model | Making capacity | Breaking capacity | Max. breaking current (A) | Mechanical endurance (times) | Weight (kg) |
JCZ5-7.2/200 | 10le,100 times | 8le,25 times | 10le | 30X104 | 28 |
JCZ5-7.2/400 | 10le,100 times | 8le,25 times | 10le | 30X104 | 28 |
JCZ5-7.2/630 | 10le,100 times | 8le,25 times | 10le | 30X104 | 28 |
Notes: “le” –– Rated Operational Current
Indoor Vacuum Contactor, JCZ5-12/200/400/630 Technical Parameters
Model | Rated voltage (V) | Rated current | Main contact | Power frequency withstand voltage(V) |
Main circuit | Control circuit | (main circuit) A | Contact gap (mm) | Overtravel (mm) | Terminal pressure (N) | Main circuit | Auxiliary circuit | Control circuit |
JCZ5-12/200 | 10000 | 110,220 | 200 | 5 | 1.5±0.5 | >85N | 42000 | 2500 | 2000 |
JCZ5-12/400 | 10000 | 100,220 | 400 | 5 | 1.5 土 0.5 | >85N | 42000 | 2500 | 2000 |
JCZ5-12/630 | 10000 | 110,220 | 630 | 5 | 1.5±0.5 | >85N | 42000 | 2500 | 2000 |
Model | Making capacity | Breaking capacity | Max. breaking current (A) | Electrical endurance operations | Weight(kg) |
JCZ5-12/200 | 10le,100 times | 8le,25 times | 10le | 30X10⁴ | 35 |
JCZ5-12/400 | 10le,100 times | 8le,25 times | 10le | 30X10⁴ | 35 |
JCZ5-12/630 | 10le,100 times | 8le,25 times | 10le | 30X10⁴ | 35 |
Notes: “le” –– Rated Operational Current
JCZ5-7.2/200,400,630 JCZ5-7.2/200,400,630 JCZ5-12/200,400,630 JCZ5-12/200,400,630