This load break switch is designed to be mounted on pole for outdoor applications, with manual and electrical operations. Supported by Toshiba VSP5-12 technology, it is a maintenance-free switch device.
The load break switch uses SF6 gas as the insulating gas, coupled with vacuum arc-extinguishing.
Designed with functions of fault detection, protection and communication, load break switch is applicable to 10kV overhead power lines, capable of automatic breaking of single phase earth fault and automatic isolating of short-circuit fault between phases.
Environmental Conditions Ambient temperature: up to 40°C, greater than -45°C; Wind speed: not exceeding 35m/s; Altitude: lower than 1000m; Earthquake intensity: ≤ magnitude 8; Relative humidity: daily average ≤ 95%, monthly average ≤ 90%; Ice coating thickness: ≤ 10mm; Areas without risks of fire, explosion, pollution, chemical corrosion and severe vibration; Methods of neutral point earthing: unearthed neutral point, Peterson coil (or arc suppression coil) earthing, low resistance earthing; Technical ParametersItem | Unit | Parameters | ||
Rated voltage | kV | 12 | ||
Across the isolating distance insulation level | Power frequency | kV | 48 | |
Lightning impulse withstand voltage(peak) | kV | 85 | ||
To earth, between the poles insulation level | Power frequency | Dry | kV | 42 |
Wet | kV | 34 | ||
Lightning impulse withstand voltage(peak) | kV | 75 | ||
Rated current | A | 630 | ||
Rated short circuit breaking current | kA | 20,25 | ||
Opening operation of rated short circuit breaking | Times | 30 | ||
Rated short-time withstand current | kA | 20,25 | ||
Rated duration of short circuit | s | 4 | ||
Rated short circuit making current (peak) | kA | 50,63 | ||
Rated peak withstand current | kA | 50,63 | ||
Mechanical Endurance | Times | 10000 | ||
Breaking times of rated breaking current | Times | 10000 | ||
Gross weight | kg | 180 Rated voltage |