This air-insulated load break switch is a control and protection device used in three phase AC 50Hz 24kv power distribution networks, suitable for power distribution stations of urban buildings, industrial production companies, mining sites, etc.
Environmental Conditions Ambient temperature: up to 40°C, greater than -25°C (can be stored at 30°C); Altitude: lower than 1000 m; Relative humidity: daily average ≤ 95% ( 20°C), monthly average ≤ 90% ( 20°C); Earthquake intensity: ≤ magnitude 8; The ambient air is not significantly polluted by corrosive gases, flammable gases, or vapors; Areas without severe vibration; Pollution level does not exceed level II;Item | Unit | Parameters | |
FZN25-24D/T630-20 | FZRN25-24D/125-315 | ||
Rated voltage | KV | 24 | |
Rated frequency | HZ | 50 | |
Rated current | A | 630 | 125 |
Power frequency withstand voltage(1min) | kV | arc extinguishing chamber 65; clearances toboth earthed and live parts 65 | |
Lightning impulsewithstand voltage(peak) | kV | clearances toboth earthed and live parts 125 | |
Rated short-time withstand current | kA | 20 | |
Rated short-circuit duration | S | 4 | |
Rated peak withstand current | kA | 50 | |
Rated closed-loop breaking current | A | 630 | |
Rated short-circuit breaking current | kA | 31.5 | |
Rated short-circuit making current | kA | 50 | |
Auxiliary circuit rated voltage | V | AC,DC/220,110 | |
Vacuum interrupter | Times | 10000/2000 | |
Earthing switch | 2000 |