Home HP9116C & HP9316C series 6-20kVA UPS

HP9116C & HP9316C series 6-20kVA UPS

HP9116C & HP9316C series 6-20kVA UPS


Applications of HP9116C & HP9316C series 6-20kVA UPS
HP9116C & HP9316C series 6-20kVA is quite suitable for servers, data centers, critical network devices, sensitive electronic equipment, telecommunications, etc.


Features of HP9116C & HP9316C series 6-20kVA UPS
1. Designed with true on-line double conversion technology, and employs advanced microprocessor control.
2. Wide input voltage.
3. Zero transfer time.
4. Protection against all types of power problems.
5. No add-on CNTL unit required for parallel connection.
6. Site wiring fault warning.
7. Low initial investment and flexible for future expansion.
8. Good reliability and performance for power sharing and redundancy.
9. Equipped with maintenance bypass switch.




10. Smart RS232 communication interface.
11. Intelligent slot is available.
12. Sealed, lead-acid, and maintenance free battery.


Features
1. Adopts LCD to display the detailed real-time UPS status.
2. Microprocessor control guarantees high reliability.
3. Equipped with boost and buck AVR to stabilize input voltage.
4. Built-in DC start function is designed to start UPS while AC power supply is unavailable.
5. HP9116C & HP9316C series UPS products are installed with smart RS-232 communication port. You can download software from the internet.
6. User-replaceable battery design.
7. Auto charge even though UPS is off.
8. Auto restart while AC recovery.
9. Provides modem or phone line surge protection.
10. Provides discharge, overcharge, and overload protection.
11. USB port is available upon request.

HP9116C & HP9316C series 6-20kVA UPS

Technical Specifications


Product series HP9116C 6 - 10kVA (1 PH / 1 PH)HP9316C 10 - 20kVA (3PH / 1PH)
Model number6KT10KT6KT-XL10KT-XL10KT-XL15KT-XL20KT-XL
Rated powerVolt-amps/Watts6kVA/4.2KW10kVA/8KW6kVA/4.2KW10kVA/7KW10Kva/7KW15Kva/10.5KW20Kva/14KW
InputLow line transfer176VAC ± 3VAC304VAC ± 3VAC
Low line comeback185VAC ± 3VAC322VAC ± 3VAC
High line transfer276VAC ± 3VAC478VAC ± 3VAC
High line comeback266VAC ± 3VAC461VAC ± 3VAC
Frequency range50Hz, 46-54Hz, 60Hz, 56-64Hz.
Power factor≥ 0.98≥ 0.95
PhaseSingle Phase with groundThree phase (4 Wires ground)
ConnectionHardwired
OutputVoltage220VAC or 230VAC or 240VAC
Voltage regulation± 1%
FrequencySynchronization range (line mode); 50 or 60Hz × (1 ± 0.05% ) Hz (battery mode)
Power factor0.7 or 0.8
Wave formPure sine wave
PhaseSingle phase
Voltage distortion≤ 2% THD (linear load), ≤ 6% THD (non - linear load)
Overload capability105%~130% for 10 min., more than 130% for 1 second
Current crest ratio3:1 max
ConnectionHardwired
BatteryTypeValve regulated, sealed, lead-acidExternal battery bank
Nominal DC voltage240VDC
Backup time (full load)7 min5 minDepends on the external battery capacity
Recharge time7 hours to 90%8 hours to 90%Depends on the external battery capacity
Charge current (max.)2A4.2A
Charge voltage274Vdc ± 1V
Transfer timeAC to DC0 ms
Inverter to bypass2.5 ms (typical)
IndicatorsStatusLoad level / battery level, battery, utility power, inverter, bypass, overload, fault.
Audible alarmBypassAlarm beeps every two seconds
Battery dischargeAlarm beeps every four seconds. Alarm beeps every one second if battery capacity is low.
OverloadAlarm beeps twice every one second
FaultAlarm beeps continuously
Maintenance bypass switchYes
Communications interfaceDB-9 PortRS-232 serial interface
Intelligent slotOptions: SNMP card, AS400 card or Win power CMC / (USB port)
Parallel portAvailability of up to three units in parallel for power redundancy and load sharing
EnvironmentOperating temperature0 ~ 40℃
Operating humidity20 ~ 90% non-condensing
Noise levelLess than 55dB@1 meterLess than 60dB@1 meter
Physical featureWeight net (Kg)909335383955
Body size W×D×H (mm)260×570×717