Application of HP9330C series 20-80kVA UPS
HP9330C series 20-80kVA UPS is particularly applicable to severs, data centers, critical network devices, sensitive electronic equipment, telecommunications, etc.
Features
1. N X parallel redundancy
The maximum of the inbuilt parallel mode is 8 pieces of UPS. In addition, battery is compatible in the parallel mode.
2. High-efficient DSP chip
Installed with digital DSP controlling chip, HP9330C series UPS products have precise data processing capacity. Furthermore, it is stable in output, and reliable in performance.
3. Outstanding electric property
The efficiency of the machine is 93%, and even reaches over 98% in the EC mode. The input power factor is as high as 0.99.
4. Twin-channel line input
HP9330C series UPS products can offer you safe power supply. You can choose either two-line input or one-line input according to the actual condition. Besides, smart battery is available.
Technical Parameters of HP9330C series 20-80kVA UPS
Product series | High Frequency Online UPS 20-80kVA (3PH/3PH) | ||||||||
Model | 20K | 20K-XL | 30K | 30K-XL | 40K | 40K-XL | 60K-XLISO | 80K-XLISO | |
Capacity | VA/W | 20KVA/16KW | 20KVA/16KW | 30KVA/24KW | 30KVA/24KW | 40KVA/32KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW |
Rectifier input | Rectifier type | IGBT-based vector controlled PFC (PF corrected) | |||||||
Input voltage | 380/400/415VAC(Accepted from 305 to 477 with ptebatt.use) | ||||||||
Input frequency | 50 or 60 Hz (accepted from 40 to 70) | ||||||||
Input current THD | 3% (without any filter) | ||||||||
Input power factor | ≥0.99 (with any filter) | ||||||||
Power walk-in | 5 to 30s (selectable) | ||||||||
Bypass input | Input voltage | 380/400/415VAC | |||||||
Battery | Battery type | VRLA (valve regulated lead acid) or wet / flooded or NiCd | |||||||
End-cell voltage | Selectable from 1.60 to 1.90Vdc / Cell (for VRLA) | ||||||||
DC ripple current(float) | <5% (of C 10 AH capacity) RMS value | ||||||||
DC ripple voltage(float and const V Ch) | <1% (RMS value) | ||||||||
Temp.conp. Charge | Standard (where internal batteries is 10,15,20,30,40 kVA) and optional (for all other battery configurations) | ||||||||
Output | Inverter type | IGBT-based vector, repetitive and PI controlled | |||||||
Output voltage | 380/400/415VAC ± 0.5 regulation (3-phase RMS average) | ||||||||
Output frequency | 50 or 60Hz with ± 0.05 regulation | ||||||||
Output voltage THD | 1% (max) | ||||||||
Max. load crest factor | 3:1 (compliant with IEC 62040-3) | ||||||||
Transient Volt. Resp | 10ms to recover ± 5% of nominal voltage for 0% to 100% or 100% to 0% step load | ||||||||
Max. leading PF load | Up to 0.9 | ||||||||
Voltage displacement | 120° ± 10° (with100% unbalanced load) | ||||||||
Overload | 110% for 60 minutes,125% for 10 minutes,150% for 1 minute | ||||||||
Efficiency | AC-AC | Up to 0.9 | |||||||
EMC-class | Class - A (applicable for both radiated and conducted) | ||||||||
Environmental | Storage temperature | -20 to 70℃ (UPS) and 25 ± 5 (battery) | |||||||
Operating temperature | 0 to 40℃ (UPS)and 25 ± 5 (battery) | ||||||||
Relative humidity | 0 to 95% (non-condensing) | ||||||||
Maximum altitude abovemean sea level | 1000m (as per IEC 62040/3) | ||||||||
Main unit | Dimension (W×D×H) mm | 420X600X1250 | 420X600X950 | 470X700X1750 | 470X700X1150 | 470X700X1750 | 470X700X1150 | 3600X800X1850 | 3600X800X1850 |
Weight(kg) | 158 | 82 | 220 | 110 | 224 | 114 | 282 | 306 | |
UPS enclosure IP | IP 20 (even with open front door) |
Standard
IEC 62040-3 EN 50091-1-1 ANSI C62.41 (IEEE 587)
IEC 62040-2 EN 50091-2
IEC 62040-1-1 EN 50091-3
IEC 60146-1-1 EN 60950
IEC 61000-4-2, 4, 5,6, 8,11 EN 60529