MTUDiesel Generator Set
Description of MTUDiesel Generator Set:
Electricity has become more and more important for the development of industry.MTU Diesel Generator Set is used to generate electricity to meet theelectricity requirement of establishments such as Hotels, Railway Stations,Telephone Exchange, Schools, and Shops etc. Our Company's Diesel GeneratorSets, especially three phase generators have got high reputation in the marketfor their maximum performance, reliability and longevity. Now, We have an average supply of over 4,000 diesel generatorsets a year.
Technicalparameters of MTU Diesel Generator Set:
Diesel Generator set | Rated Power (kW/KVA) | 1700/2125 |
Standby Power (kW/KVA) | 1870/2338 | |
Rated Current | 3068 | |
Engine | Model | 16V4000G61 |
Continuous Power (kW) | 1760 | |
Bore(mm)×Stroke(mm) | 165×190 | |
Rotation (r/min) | 1500 | |
Cylinder Numbers and grouping | 16, V Type | |
Discharge Volume(L) | 64.96 | |
Compression Ratio | 16:1 | |
Air Input | Turbo charge, intercooler | |
Max Air Input Resistance (mbar) | 30 | |
Max Air Discharge Back Pressure (kPa) | 50 | |
Air Combustion Volume (m³/h) | 7200 | |
Discharge Volume(m³/h) | 18720 | |
Minimum Air input/output Area (m²) | 8.3/6.1 | |
Air Discharge Temperature (°C) | 490 | |
Cooling Liquid Capacity (L) | 215 | |
Cooking water Alarming Temperature | 97 | |
Lube Oil Volume (L) | 290 | |
Lube oil Alarming Temperature (°C) | 95 | |
Rated Fuel Consumption (L/h) | 411 | |
Cooling | Radiator with fan | |
Governing | MDEC electronic governing | |
Alternator | Model | HCI734J |
Rated Power (kW/KVA) | 1720/2150 | |
Rated Voltage (V) | 400/230 | |
Rated Power factor | 0.8 | |
Exciting | Brushless, PMG exciting | |
Phase | Three phase | |
Cooling Air capacity (l/s) | 2640 | |
Protection Class | IP22 | |
Insulation Class | H | |
Controller | Circuit Breaker’s Rated Capacity (A) | 3200 |
Storage Battery | Rated Capacity (AH) | 4×200Ah 12V |