Shanghai Electric and Westinghouse Electric once jointly designed 300MW、600MW class generators. In addition, our company introduced, digested and absorbed the technology of 1000MW class generator of Siemens. On the basis of that, our company independently developed the third technology of water hydrogen cooled turbine generator and two-pole water hydrogen cooled turbine generator which can meet the needs of market. And the capacity of generator covers 200MW~1300MW.
Stator coils of water hydrogen cooled turbine generator are cooled by water while rotor coils and stator cores are cooled by hydrogen. A series of techniques are applied to water hydrogen cooled turbine generator. The structure which can resist creep and completely compensate the magnetic field is applied to stator cores. Spherical joint is applied in composite water-electric joint of stator coils. The end of the stator is filled with glue as a whole. Turn - to - turn insulation structure which is made by using seamless stitching technology is applied in rotor and the rotor does not need to repair in 10 years if there are no special circumstances.
(1) 350MW Water Hydrogen Cooled Turbine Generator
• Rated voltage: 20kV
• Rated current: 11887A
• Power factor: 0.85
• frequency: 50Hz
• Rotating speed: 3000r/min
• Excitation mode: Static excitation or brushless excitation
(2) 465MW Water Hydrogen Cooled Turbine Generator
• Rated voltage: 20kV
• Rated current: 15792A
• Power factor: 0.85
• frequency: 50Hz
• Rotating speed: 3000r/min
• Excitation mode: Static excitation or brushless excitation
(3) 660MW Water Hydrogen Cooled Turbine Generator
• Rated voltage: 20kV
• Rated current: 21169A
• Power factor: 0.9
• frequency: 50Hz
• Rotating speed: 3000r/min
• Excitation mode: Static excitation or brushless excitation
(4) 700MW Water Hydrogen Cooled Turbine Generator
• Rated voltage: 22kV
• Rated current: 20412 A
• Power factor: 0.9
• frequency: 50Hz
• Rotating speed: 3000r/min
• Excitation mode: Static excitation or brushless excitation
(5) 1000MW Water Hydrogen Cooled Turbine Generator
• Rated voltage: 27kV
• Rated current: 23778 A
• Power factor: 0.9
• frequency: 50Hz
• Rotating speed: 3000r/min
• Excitation mode: Static excitation or brushless excitation
(6) 1300MW Water Hydrogen Cooled Turbine Generator
• Rated voltage: 27kV
• Rated current: 30888 A
• Power factor: 0.9
• frequency: 50Hz
• Rotating speed: 3000r/min
• Excitation mode: Static excitation or brushless excitation
Two-pole water hydrogen cooled turbine generator has a superior performance. Its performance and reliability reach the world advanced level through continuous optimization and improvement. At the same time, it has got a series of national patent and it was selected into shanghai high and new technology achievement transformation project. In addition, it was honored as Shanghai Science and Technology Progress Award, National key new product and first prize of National Thermal Power Unit Competition.