The ZN65A-12/T3150-40 vacuum circuit breaker for generator is a new long-life type product developed by our company based on the latest domestic and foreign technologies. Its rated short circuit breaking current is 40kA.
In the type test of circuit breaker for power distribution, the breaking time at full capacity is up to 50 and the mechanical life reaches 60,000 times. This vacuum circuit breaker has also passed the type test of contact breakers. The DC component of the non-symmetry breaking current is more than 70%.
This vacuum circuit breaker features simple structure, stable and reliable operation, as well as convenient maintenance. It comes with a spring operating mechanism.
This product can not only be used as the ordinary protection device for power plants, substations and other transmission and distribution systems but also be used to control and protect some small generator outlet, steelmaking electric furnace and other equipment. Its performance achieves the highest level among similar domestic products.
Ordinary Type | Altitude: ≤1,000m |
Ambient Temperature: -25℃~ 40℃ (-40℃ is fine for special product) | |
Relative Humidity: Daily average≤95%, monthly average≤90% | |
Earthquake Intensity<8degree, no fire, explosion, corrosive gases, or severe shaking | |
Suitable-for-all-working-conditions Type | The vacuum circuit breaker for generator can be used in places where there is condensation and filth. |
No. | Item | Unit | Value |
1 | Rated Voltage | KV | 12 |
2 | Rated Current | A | 1600 2000 2500 3150 |
3 | Rated Short-circuit Breaking Current | KA | 40 |
4 | Rated Peak Withstand Current | KA | 110 |
5 | Rated Short-time Withstand Current | KA | 40 |
6 | Rated Short-circuit Closing Current | KA | 110 |
7 | Rated Short Circuit Duration | s | 4 |
8 | Rated Short-circuit Current Breaking Times | times | 50 |
9 | Rated Operating Sequence | Open-0.3s- Close open-180s-Close open | |
10 | Rated Frequency | Hz | 50 |
11 | Lightning Impulse Withstand Voltage | KV | 85 |
12 | 1min Power Frequency Withstand Voltage | KV | 50 |
13 | Closing Time | ms | 40~85 (47±7) |
14 | Opening Time | ms | 40~85 (52±7) |
15 | Breaking Time | ms | ≤80 |
16 | Mechanical Life | times | 10000 |
17 | Rated Power of the Energy Storage Motor | W | 200 |
18 | Rated Voltage of the Energy Storage Motor | V | AC, DC 110, 220 |
19 | Energy Storage Time | s | ≤15 |
20 | Rated Voltage of the Closing and Tripping Electromagnet | V | AC, DC 110, 220 |
21 | Rated Current of the Auxiliary Switch | A | AC 10, DC 5 |
22 | Maximum DC Component | 74% |
Note: 1. The closing time, opening time, and breaking time are calculated when the vacuum circuit breaker operates at the highest, rated, and lowest operating voltages respectively. The value inside the bracket is the rated operating time.
2. Please refer to the Certificate of Approval for the actual technical parameters.
As a professional vacuum circuit breaker for generator manufacturer and supplier in China, BBE offers a broad range of products, including gas insulated switchgear, withdrawable switchgear, low voltage distribution board, and more.