Home 8 Zones Wired Fire Alarm Control Panel

8 Zones Wired Fire Alarm Control Panel

The HM-1008 8 zones wired fire alarm control panel, taking usage of conventional input device, is compatible with shunt type device, 2-wire smoke detector, 4-wire smoke detector, emergency push button, and other relay normally open equipment. It comes out with the output parts including 4 sound output circuits (Sound1-4), three standard A-class relay output circuits (alarm, fault, and monitoring), and one EIA-485 output port for connecting external remote annunciator or optional remote relay module.


Via the keys carrying out the zone setting, the 8 zones wired fire alarm control panel makes all the wiring, alternating voltage and battery quantity in the state of being monitored. Each detection zone can be disabled and available with independent operation. In addition, the alarm sound output of the product can be edited and disabled.


Features
The product is provided with the following units. It also can realize many functions listed below.
1. Configuration
a. 4, 8 or 16 B-class initiating device circuits
b. Four B-class notification appliance circuits (NACs)
c. One A type alarm relay
d. One A type fault replay
e. One A type monitoring relay
f. System power of 3.0amps


2. Function
a. The product allows for at most 20 conventional detectors in one detection zone.
b. All detection zones support the connection with conventional detectors and any relay normally open equipment.
c. The modes of Auto and Manual can be set. The walk test is also available.
d. Each detection zone and the sound output can be disabled.
e. Setting the sound output manually is also allowed.
f. The 8 zones wired fire alarm control panel can also report the short circuit and open circuit of the detection zones.
g. It is available with the backup batteries design by accommodating two sealed lead acid batteries.
h. The product also supports the testing and disabling functions.

8 Zones Wired Fire Alarm Control Panel

Technical Specification
1. AC Power
a. Power Supply: 220V AC, 50Hz, 2.3amps
b. Min. Wire Size: #14 AWG (2.0mm²) with 600V Insulation


2. Battery (Lead Acid Type Only)
a. Max. Charging Circuit: Normal Floating Charge of 27.6V@0.8amp
b. Max. Charging Capacity: 18Ah Battery


3. Sound Output Device Circuit
a. General Alarm Zones: 1-16
b. Operation: Class B for All Detection Zones
c. Normal Operating Voltage: Nominal 24V DC (Max. Ripple of 100mV)
d. Alarm Current: 15mA (Threshold)
e. Short Circuit Current: 42mA (Maximum)
f. Max. Loop Resistance: 100ohms
g. End-of-line Resistor: 4.7K, 0.5 watt
h. Detector Loop Current: Sufficient to Ensure the Operation of Two Alarm Detectors in One Detection Zone
i. Standby Current: 7.26mA


4. Three Relays Output
Relay Contact Rating: 2.0 amps @ 30V DC, 2.0amps @ 30V AC


5. Non Resettable 24V DC Power
a. Max. Ripple Voltage: 10mVRMS
b. Operating Voltage: Nominal 24V
c. Max. Output DC Current: 500mA
d. Recommended Max. Standby Current: 150mA