The ZW38-55 vacuum circuit breaker is an outdoor single-phase bipolar high-voltage switching device that features simple structure, strong breaking capability, complete operating functions and no explosive hazard. With the rated voltage and frequency are 55kV and 50Hz respectively, this single phase circuit breaker is suitable to open and close loads as well as break fault current in the AT traction power supply system for electrified railway.
Especially applicable to occasions requiring frequent operations, this vacuum circuit breaker adopts vacuum interrupter as the arc extinguishing component. A spring-loaded cam linkage mechanism is used for operation. The energy storage as well as the opening and closing operations can be carried out manually or electrically. The electrical operation is controlled closely or remotely.
This vacuum circuit breaker has been used in Fujian, Guangdong, Hubei, Jiangxi, Shaanxi, and Heilongjiang provinces. The market evaluation is good. Silicone grease is adopted for the external insulation of our product, so the SF6 gas does not leak and there are basically no after-sales quality problems.
Normal Conditions of Use
Item | Data |
Ambient Air Temperature | Upper limit: 40℃ Lower limit: -30℃ for common areas, -40℃ for frigid areas |
Altitude | ≤1,000m |
Wind Pressure | ≤700Pa (equivalent to wind speed 34m/s) |
Ice thickness | ≤10mm |
Air Contamination Degree | Level IV (Ambient air should not be subjected to corrosive or flammable gases, water vapor and other obvious pollution.) |
Earthquake Intensity | ≤8 degree (There is no recurrent severe vibration; otherwise isolation measures should be taken.) |
Note: If the use conditions of the vacuum circuit breaker do not meet the above requirements, customers should consult with us.
No. | Item | Unit | Value |
1 | Rated Voltage | KV | 55 |
2 | Max. Voltage | KV | 63 |
3 | Rated Lightning Impulse Withstand Voltage Peak | KV | 325 |
4 | 1min Power Frequency Withstand Voltage | KV | 140 |
5 | Rated Frequency | Hz | 50 |
6 | Rated Operating Current | A | 1250/1600 |
7 | Rated Short-circuit Breaking Current | KA | 25/31.5 |
8 | Rated Peak Withstand Voltage | KA | 63/80 |
9 | Rated Short-circuit Closing Current | KA | 63/80 |
10 | Rated Short-time Withstand Voltage | KA | 25(4s)/31.5(4s) |
11 | First-Pole-to-Clear Factor | 1.5 | |
12 | Rise Rate of Recovery Voltage | KV/μs | 0.75 |
13 | Rated Short-circuit Current Breaking Times | Times | 20 |
14 | Rated Transient Recovery Voltage Peak | KV | 124 |
15 | Closing Time | ms | 110±10 |
16 | Opening Time | ms | 50±10 |
17 | Closing Speed | m/s | 1.3±0.5 |
18 | Opening Speed | m/s | 3.0±0.3 |
19 | Energy Storage Time of Motor | s | <20 |
20 | Motor Voltage | V | DC 110/220 |
21 | Motor Power | W | 400 |
22 | Motor Supply Current | A | 9/5±2 |
23 | Voltage of Opening and Closing Coils | V | DC 110/220 |
24 | Current of Opening and Closing Coils | A | 4/2.5 |
25 | Rated Pressure of SF6 Gas | MPa | 0.1( 20 ℃ ) |
26 | Annual Gas Leakage Rate | <1% | |
27 | Standard Operating Sequence | O-0.3s-CO-180s-CO | |
28 | Resistance of Main Circuit | μΩ | <80 |
29 | Total Weight | kg | 2100 |
30 | Mechanical Life | Times | 10,000 |
As an experienced vacuum circuit breaker manufacturer and supplier in China, BBE provides a comprehensive range of products, including outdoor vacuum circuit breaker, indoor single pole vacuum circuit breaker, gas insulated switchgear, etc.
Related Names
Bipolar Circuit Breaker | High Voltage Circuit Breaker