With the rated voltage of 40.5kV, the ZW18A-40.5/T1250-2500/25-31.5 outdoor vacuum circuit breaker is a three-phase AC 50Hz high voltage product. It can be used as the control or protection switch in substations, power planets, as well as industrial and mining enterprises, particularly suitable for occasions requiring frequent operations.
Use Environment
1. Altitude: ≤2,000m
2. Ambient Temperature: -40℃~ 40℃
3. Wind Pressure: ≤700Pa (wind speed ≤34m/s)
4. Earthquake Intensity: ≤8degree
5. Degree of Air Contamination: Grade IV
Note: Vacuum circuit breakers applicable to places with the altitude higher than 2,000m can also be provided, but customers should mention this when ordering.
Item | Unit | Value | ||
Rated Voltage | kV | 40.5 | ||
Rated Frequency | Hz | 50 | ||
Rated Insulation Level | 1min Power Frequency Withstand Voltage (phase to ground external insulation) | kV | 95 | |
80 | ||||
Lightning Impulse Withstand Voltage (Peak Value) | 185 | |||
Rated Current | A | 1250 | 1600 | |
Rated Short-circuit Breaking Current | kA | 25 | 31.5 | |
Rated Operating Sequence | O-0.3s-CO-180s-CO | |||
Rated Short-circuit Current Breaking Times | times | 20 | ||
Rated Short-circuit Closing Current (Peak Value) | kA | 63 | 80 | |
Rated Peak Withstand Current | kA | 63 | 80 | |
Rated Short-time Withstand Current | kA | 25 | 31.5 | |
Rated Short Circuit Duration | s | 4 | ||
Mechanical Life | times | 10000 | ||
Rated Operating Voltage | V | AC, DC 220V/110V | ||
Rated Operating Current Close, Open | A | 5, 2.5 | ||
Permissible Wearing Thickness of the Moving contact and Fixed Contact | mm | 3 | ||
Weight | kg | About 1200 |
We are a professional outdoor vacuum circuit breaker manufacturer and supplier in China. We also provide low voltage circuit breaker for ship, air circuit breaker, withdrawable switchgear, and more.