Home 16 Zones Wired Fire Alarm Control Panel

16 Zones Wired Fire Alarm Control Panel

The HM-1016 16 zones wired fire alarm control panel employs the conventional input device. It is compatible with shunt type device, 2-wire smoke detector, 4-wire smoke detector, emergency push button, and other relay normally open equipment. The output parts incorporate 4 sound output circuits (Sound1-4), three standard A-class relay output circuits (alarm, fault, and monitoring), and one EIA-485 output port which is applied for realizing external connection with remote annunciator or optional remote relay module.


This 16 zones wired fire alarm control panel enables zone setting via the keys. It monitors all the wiring, alternating voltage, and battery quantity. The independent operation is allowed for each detection zone which can be disabled. The alarm sound output of the product can also be edited and disabled.


Configuration
1. 4, 8 or 16 B-class initiating device circuits (IDCs)
2. Four B-class notification appliance circuits (NACs)
3. One A type alarm relay
4. One A type fault replay
5. One A type monitoring relay
6. System power of 3.0amps


Features
1. The 16 zones wired fire alarm control panel allows all the detection zones to connect the conventional detector and any relay normally open equipment.
2. Each the detection zone can allow at most 20 detectors.
3. The product also enables setting the mode of Auto and Manual. It can carry out the walk test.
4. Every detection zone can be disabled.
5. The sound output can be disabled.
6. The user can set the sound output manually.
7. The 16 zones wired fire alarm control panel is also available with the function of reporting the short circuit and open circuit.
8. The backup battery design allows the product to accommodate two sealed lead acid batteries.
9. The product provides the testing and disabling functions.

16 Zones Wired Fire Alarm Control Panel

Technical Specification
1. AC Power

a. Power Supply: 220V AC, 50Hz, 2.3amps
b. Min. Wire Size: #14 AWG (2.0mm²) with 600V Insulation


2. Battery (Lead Acid Type Only)
a. Max. Charging Circuit: Normal Floating Charge of 27.6V@0.8amp
b. Max. Charging Capacity: 18Ah Battery


3. Sound Output Device Circuit
a. General Alarm Zones: 1-16
b. Operation: Class B for All Detection Zones
c. Normal Operating Voltage: Nominal 24V DC (Max. Ripple of 100mV)
d. Alarm Current: 15mA (Threshold)
e. Short Circuit Current: 42mA (Maximum)
f. Max. Loop Resistance: 100ohms
g. End-of-line Resistor: 4.7K, 0.5 watt
h. Detector Loop Current: Sufficient to Ensure the Operation of Two Alarm Detectors in One Detection Zone
i. Standby Current: 7.26mA


4. Three Relays Output
Relay Contact Rating: 2.0 amps @ 30V DC, 2.0amps @ 30V AC


5. Non Resettable 24V DC Power
a. Max. Ripple Voltage: 10mVRMS
b. Operating Voltage: Nominal 24V
c. Max. Output DC Current: 500mA
d. Recommended Max. Standby Current: 150mA