600A, 15-35kV Deadbreak TeeConnector
The CEE 600A deadbreak tee connector is used to connect high voltage undergroundcable to dead-frontapparatus such as transformers, switches and switchgears. It is fully shielded,submersible, and rated 600A. This tee connector is manufactured incompliance with the ANSI/IEEE 386 standard. The capacitive test point on theinsulating plug allows testing the circuit without disturbing the boltedconnection. Meanwhile, a hot line voltage indicator can also be connectedthrough this test point. Our deadbreak tee connector is designed for use on soliddielectric cable with extruded semi-conductive shields and concentric neutral,with or without a jacket.
Application
The CEE 600A deadbreak teeconnector is used for dead-front underground installation in 600A distribution feeders. It can providecomplete shielded and fully submersible cable connection for apparatus such astransformers and switchgears.
600A, 15kV Deadbreak Tee Connector.
Catalog No. | Conductor Cross Section (mm2) | Current Rating (A) | Note: Based on 8.7/ 10kV, 8.7/15kV XLPE cable range per GB 12706, IEC 60502-2: 1998 standards, For 3. 6/7.2kV or 6/10kV cable application, con-tact CEE Power System. |
CEE TT-15/600-35 | 35 | 600 | |
CEE TT-15/600-50 | 50 | 600 | |
CEE TT-15/600-70 | 70 | 600 | |
CEE TT-15/600-95 | 95 | 600 | |
CEE TT-15/600-120 | 120 | 600 | |
CEE TT-15/600-150 | 150 | 600 | |
CEE TT-15/600-185 | 185 | 600 | |
CEE TT-15/600-240 | 240 | 600 | |
CEE TT-15/600-300 | 300 | 600 | |
CEE TT-15/600-400 | 400 | 600 | |
CEE TT-15/600-500 | 500 | 600 |
600A, 25kV/35kV Deadbreak Tee Connector.
Catalog No | Conductor Cross Section (mm2) | Cable Insulation Range (mm) |
CEE TT-35/600-50 | 50 | 24.0-27.5 |
CEE TT-35/600-70 | 70 | 27.0-29.5 |
CEE TT-35/600-95 | 95 | 29.0-31.5 |
CEE TT-35/600-120 | 120 | 31.0-32.5 |
CEE TT-35/600-150 | 150 | 32.0-35.0 |
CEE TT-35/600-185 | 185 | 32.0-35.0 |
CEE TT-35/600-240 | 240 | 35.0-38.5 |
CEE TT-35/600-300 | 300 | 38.0-41.5 |
CEE TT-35/600-400 | 400 | 41.0-44.5 |
Technical specification
Voltage Rating | 15kV | 25kV | 35kV |
Standard Voltage Class | 15 | 25 | 35 |
Max. Rating Phase-to-Phase | 14.4 | 26.3 | 36.6 |
Max. Rating Phase-to-Ground | 8.3 | 15.2 | 21.1 |
AC 60/50Hz 1Minute Withstand | 34 | 40 | 50 |
DC 15 Minute Withstand | 53 | 78 | 103 |
BIL and Full Wave Crest | 95 | 125 | 150 |
Minute Partial Discharge | 11 | 19 | 26 |
Current Ratings | 15kV | 25kV | 35kV |
Continuous | 600A | 600A | 600A |
Switching | 10 operations at 200A, 14.4kV | 10 operations at 200A, 26.3kV | 10 operations at 200A, 36.6kV |
24h Overload | 900A | 900A | 900A |
Short Time | 25kA rms sym. for 0.17s (60Hz)/0.2s(50Hz) | 25kA rms sym. for 0.17s (60Hz)/0.2s(50Hz) | 25kA rms sym. for 0.17s (60Hz)/0.2s(50Hz) |
10kA rms sym. for 3.0s | 10kA rms sym. for 3.0s | 10kA rms sym. for 3.0s |
Material
EPDM
As a China 630A, 15-35kV deadbreak tee connector manufacturer, CEE provides a comprehensive range of mediumvoltage power distribution equipment, including bushing surge arrester, coldshrink indoor termination, overhead short circuit fault indicator, to name afew. Our company has received the ISO9001 and ISO14001 certificates, and ourproducts have been CCC certified. We are located in Fuzhou City, Fujian Province, which providesus with easy access to convenient sea, land and air transportation.