Home 600A, 15-35kV Deadbreak Tee Connector

600A, 15-35kV Deadbreak Tee Connector

600A, 15-35kV Deadbreak TeeConnector

The CEE 600A deadbreak tee connector is used to connect high voltage undergroundcable to dead-frontapparatus such as transformers, switches and switchgears. It is fully shielded,submersible, and rated 600A. This tee connector is manufactured incompliance with the ANSI/IEEE 386 standard. The capacitive test point on theinsulating plug allows testing the circuit without disturbing the boltedconnection. Meanwhile, a hot line voltage indicator can also be connectedthrough this test point. Our deadbreak tee connector is designed for use on soliddielectric cable with extruded semi-conductive shields and concentric neutral,with or without a jacket.

600A, 15-35kV Deadbreak Tee Connector



Application
The CEE 600A deadbreak teeconnector is used for dead-front underground installation in 600A distribution feeders. It can providecomplete shielded and fully submersible cable connection for apparatus such astransformers and switchgears.


 600A, 15kV Deadbreak Tee Connector.


Catalog No.

Conductor Cross Section (mm2)

Current Rating (A)

Note: Based on 8.7/ 10kV, 8.7/15kV XLPE cable range per GB 12706, IEC 60502-2: 1998 standards, For 3. 6/7.2kV or 6/10kV cable application, con-tact CEE Power System.

CEE TT-15/600-35

35

600

CEE TT-15/600-50

50

600

CEE TT-15/600-70

70

600

CEE TT-15/600-95

95

600

CEE TT-15/600-120

120

600

CEE TT-15/600-150

150

600

CEE TT-15/600-185

185

600

CEE TT-15/600-240

240

600

CEE TT-15/600-300

300

600

CEE TT-15/600-400

400

600

CEE TT-15/600-500

500

600


 


 600A, 25kV/35kV Deadbreak Tee Connector.


Catalog No

Conductor Cross Section (mm2)

Cable Insulation Range (mm)

CEE TT-35/600-50

50

24.0-27.5

CEE TT-35/600-70

70

27.0-29.5

CEE TT-35/600-95

95

29.0-31.5

CEE TT-35/600-120

120

31.0-32.5

CEE TT-35/600-150

150

32.0-35.0

CEE TT-35/600-185

185

32.0-35.0

CEE TT-35/600-240

240

35.0-38.5

CEE TT-35/600-300

300

38.0-41.5

CEE TT-35/600-400

400

41.0-44.5



Technical specification
 


Voltage Rating

15kV

25kV

35kV

Standard Voltage Class

15

25

35

Max. Rating Phase-to-Phase

14.4

26.3

36.6

Max. Rating Phase-to-Ground

8.3

15.2

21.1

AC 60/50Hz 1Minute Withstand

34

40

50

DC 15 Minute Withstand

53

78

103

BIL and Full Wave Crest

95

125

150

Minute Partial Discharge

11

19

26

Current Ratings

15kV

25kV

35kV

Continuous

600A

600A

600A

Switching

10 operations at 200A, 14.4kV

10 operations at 200A, 26.3kV

10 operations at 200A, 36.6kV

24h Overload

900A

900A

900A

Short Time

25kA rms sym. for 0.17s (60Hz)/0.2s(50Hz)

25kA rms sym. for 0.17s (60Hz)/0.2s(50Hz)

25kA rms sym. for 0.17s (60Hz)/0.2s(50Hz)

10kA rms sym. for 3.0s

10kA rms sym. for 3.0s

10kA rms sym. for 3.0s



Material

EPDM


As a China 630A, 15-35kV deadbreak tee connector manufacturer, CEE provides a comprehensive range of mediumvoltage power distribution equipment, including bushing surge arrester, coldshrink indoor termination, overhead short circuit fault indicator, to name afew. Our company has received the ISO9001 and ISO14001 certificates, and ourproducts have been CCC certified. We are located in Fuzhou City, Fujian Province, which providesus with easy access to convenient sea, land and air transportation.