DUCV TelecomRectifier System
Designed for smallTelecommunication applications, DUCVtelecom rectifier system is composed of three key parts and they arefour DEV rectifier modules, one TJC2 monitor module and power distributionsection. For depth of 19”6Usub-rack, it is 340mm.Withregard to configuration, RS485 and 6 groups of dry contacts are available. Foroperation, system can work in accordance with the setting of the monitor. Whenthere is a failure, battery can supply power preset LVD level. After problemresolved, this machine can go back to work automatically. Besides that, this product can supply max 48VDC 200A 12kw and the detailed information is asfollows.
Detailed Specifications:
Model No. | DucV48200 | |
AC Input | ||
Nominal voltage | 220/230V AC with dreading to 110Vac | |
AC input range | Voltage | 90 – 290V AC |
Frequency | 45 – 66Hz | |
Power Factor | >0.99 | |
Max input current | 63A | |
DC Output | ||
Nominal output voltage | 53.5VDC | |
Range | 43.2V – 58V | |
Rated output current | 200A,Derating lower than 170Vac | |
DC Outputs (with MCB protected) | Important load | 16A x 2 |
Other load | 63A x 1,32A x 2,16A x 3 | |
Efficiency | 220V AC input | ≥91% |
110V AC input | ≥85% | |
Voltage variation | ≤±1% | |
Current balance | ≤±5% | |
Dynamic response time | ≥10ms | |
Battery Output | ||
Nominal voltage | 48VDC | |
Battery output (with MCB protected) | 2 x 100A | |
Others | ||
Protection | Input over/under voltage | Shutdown with auto recovery |
Power limitation | Adjustable | |
Shortcut | Shutdown with auto recovery | |
Over temperature | Dreading with auto recovery | |
Output over/under voltage | Shutdown with manual recovery | |
Low battery | Shutdown with auto recovery | |
Isolation | Input to output | 3kV AC/10mA/1min |
Input to ground | 1.5kV AC/10mA/1min | |
Output to ground | 500V AC/10mA/1min | |
Others | ||
Dimension | 483mm*266mm*303mm - 19"6U | |
Weight | ≤25kg | |
Ventilation | Twin thermal control fans | |
Working temperature | -20℃~ 55℃ (full load) | |
Storage temperature | -40℃~ 85℃ | |
Standard | ||
LVD | EN60950 | |
EMC | EN 61000-3-2, EN 61000-3-3, CISPR22, CISPR 24 |
DetailedSpecifications:
3 x 40A AC inputMCB – 3 phase
12 x 6-63A MCBprotected output – LVD
5 x 6-63A MCBprotected output – LBD
2 x 80A-125A battery MCB