The instrument signal cable for instrument circuit meets the Q/321011KLA58-2004 standard which is equal to BS5308-86. Our product shows some outstanding properties, such as low capacitance, low inductance, good shielding effect, strong anti-interference ability, etc. As a result, the explosion proof performance is better when compared with common computer cable and control cable.
Service Property
1. Rated voltage U0/U: 300/500V, 450/750V
2. Max. working temperature: 70℃ for common type, 90℃ for XLPE insulated type, and 105℃ for models ending with "105".
3. Min. ambient temperature: -40℃ for fixed laying, and -15℃ for non-fixed laying.
4. Min. bending radius: 6 times of cable outer diameter for non-armored type, and 12 times of outer diameter for armored type.
Based on these features, this instrument signal cable usually works as weak signal transmission line for places that require anti-explosion performance, such as distributed control system, control system of automatic inspection, etc.
Item | Unit | Data | ||
XLPE/PE Insulation | PVC Insulation | |||
Working Capacitance at 1kHz (core-core) ≤ | pF/m | 90 | 180 | |
Capacitance Imbalance at 1kHz ≤ | pF/m | 1 | / | |
Distributed Inductance ≤ | pH/m | 0.6 | 0.6 | |
LR Ratio ≤ | 0.5 mm2 | pH/Ω | 20 | 20 |
0.75 mm2 | 20 | 20 | ||
1.0 mm2 | 25 | 25 | ||
1.5 mm2 | 35 | 5 | ||
Anti-Outer Magnetic Field Interference (400A/m) ≤ | mV | 5 | 5 | |
Anti-Electrostatic Induction (20k/V) ≤ | mV | 80 | 80 | |
Anti-Radio Frequency Interference (120dB, within the range of 20-200MHz) ≤ | 60 | 60 | ||
Insulation Resistivity at 20℃ ≥ | MΩ·km | 1000 | 25 | |
Test Voltage | V/1min | 2000 | 2000 | |
Flame Retardant Property | Meets the requirements of GB/T18380-2008 |
Note: The flame retardant requirement is not applicable for non-flame retardant cable.
Item | Code | Description |
Flame Retardant | / | Non-flame retardant product |
ZR | Flame retardant product | |
ZRA | Flame retardant rating: A | |
ZRB | Flame retardant rating: B | |
ZRC | Flame retardant rating: C | |
DDZ | Low-halogen low-smoke flame retardant | |
WDZ | Halogen free low-smoke flame retardant | |
Series | IA | Instrument signal cable for instrument circuit |
Insulating Material | Y | Polythene |
YJ | XLPE | |
V | PVC | |
Shielding Material | P | Cu wire woven |
P1 | Tinned Cu wire woven | |
P2 | Cu-plastic composite wire | |
P3 | Al-plastic composite wireIn addition, P and P2, P2 and P3 can be combined into compound screen. | |
Sheathing Material | Y | Light and heat resistant polythene |
J | PVC | |
Armoring Material | 22 | Steel tape |
32 | Thin steel wire | |
Conductor Material | A | Single strand conductor |
B | 7-strand twisted conductor | |
R | Multi-strand soft conductor | |
Heat Resisting Property | / | The letter is omitted if the maximum working temperature is 70℃. |
90 | Max. working temperature: 90℃ | |
105 | Max. working temperature: 105℃ | |
Specification | Pair number × wire number × cross section: N × n × SN: 1, 2, 3, ……24n: 2, 3S: 0.5, 0.75, 1.0, 1.5, 2.5 mm2 |
No. | Model | Product Description | Application |
1 | IAVPV | Cu core PVC insulated and sheathed, Cu wire woven individually shielded instrument signal cable | The PVC or PE insulated cable features excellent electrical performance as well as anti-interference property, and it is suitable for places with strong interference. |
2 | IAVPVP | Cu core PVC insulated and sheathed, Cu wire woven individually and collectively shielded instrument signal cable | |
3 | LAVP2V | Cu core PVC insulated and sheathed, Cu-plastic composite film individually shielded instrument signal cable | |
4 | IAVP2VP2 | Cu core PVC insulated and sheathed, Cu-plastic composite film individually and collectively shielded instrument signal cable | |
5 | IAVP3V | Cu core PVC insulated and sheathed, Al-plastic composite film individually shielded instrument signal cable | |
6 | IAVP3VP3 | Cu core PVC insulated and sheathed, Al-plastic composite film individually and collectively shielded instrument signal cable | |
7 | IAVPVR | Cu core PVC insulated and sheathed, Cu wire woven individually shielded soft instrument signal cable | |
8 | IAVPVPR | Cu core PVC insulated and sheathed, Cu wire woven individually and collectively shielded soft instrument signal cable | |
9 | IAYPV | Cu core polythene insulated PVC sheathed, Cu wire woven individually shielded instrument signal cable | |
10 | IAYPVP | Cu core polythene insulated PVC sheathed, Cu wire woven individually and collectively shielded instrument signal cable | |
11 | IAYP2V | Cu core polythene insulated PVC sheathed, Cu-plastic composite film individually shielded instrument signal cable | |
12 | IAYP2VP2 | Cu core polythene insulated PVC sheathed, Cu-plastic composite film individually and collectively shielded instrument signal cable | |
13 | IAYP3V | Cu core polythene insulated PVC sheathed, Al-plastic composite film individually shielded instrument signal cable | |
14 | IAYP3VP3 | Cu core polythene insulated PVC sheathed, Al-plastic composite film individually and collectively shielded instrument signal cable | |
15 | IAYPVR | Cu core polythene insulated PVC sheathed, Cu wire woven individually shielded soft instrument signal cable | |
16 | IAYPVPR | Cu core polythene insulated PVC sheathed, Cu wire woven individually and collectively shielded soft instrument signal cable | |
17 | IAYJPV | Cu core XLPE insulated PVC sheathed, Cu wire woven individually shielded instrument signal cable | These XLPE insulated products possess better performance when compared with PVC or PE insulated type, and they have superb electrical, thermal, mechanical and corrosion resisting properties. |
18 | IAYJPVP | Cu core XLPE insulated PVC sheathed, Cu wire woven individually and collectively shielded instrument signal cable | |
19 | IAYJP2V | Cu core XLPE insulated PVC sheathed, Cu-plastic composite film individually shielded instrument signal cable | |
20 | IAYJP2VP2 | Cu core XLPE insulated PVC sheathed, Cu-plastic composite film individually and collectively shielded instrument signal cable | |
21 | IAYJP3V | Cu core XLPE insulated PVC sheathed, Al-plastic composite film individually shielded instrument signal cable | |
22 | IAYJP3VP3 | Cu core XLPE insulated PVC sheathed, Al-plastic composite film individually and collectively shielded instrument signal cable | |
23 | IAYJPVR | Cu core XLPE insulated PVC sheathed, Cu wire woven individually shielded soft instrument signal cable | |
24 | IAYJPVRP | Cu core XLPE insulated PVC sheathed, Cu wire woven individually and collectively shielded soft instrument signal cable |
Related Names