The plastics insulated and sheathed control cable is produced according to the standards of GB/T9330-2008 as well as GB/T19666-2005 (flame retardant and fire resistant wires and cables), and it refers to IEC227 while the voltage withstand ability is better than the requirement of IEC227.
Service Property
1. Rated voltage U0/U: 450/750V
2. Max. working temperature: 70℃ for common type, and 90℃ for XLPE insulated type.
3. Min. bending radius: 6 times of the cable outer diameter for unarmored type, and 12 times of outer diameter for armored type.
4. Min. ambient temperature when laying: -40℃ for fixed laying, and -15℃ for unfixed laying.
The available color marks include 10 choices which are white, red, black, yellow, blue, green, orange, grey, brown and purple, but we usually use digital marks. This control cable is suitable for control circuit, monitoring circuit and protecting line with rated voltage of 450/750V AC or lower.
Item | Qualification | ||
Common Flame Retardant PVC | Low Halogen Low Smoke PVC | Halogen Free Low Smoke Polyolefin | |
Oxygen Index | 30-32 | 31-36 | 36-40 |
Smoke Density ≤ | 600 | 300 | With flame: 50Without flame: 260 |
Liberation Amount of Hydrogen Halide ≤mg/g | 580 | 100 | 5 |
Item | Qualification | ||||||||||||||||
Cross Section | 0.5 mm2 | 0.75 mm2 | 1.0 mm2 | 1.5 mm2 | 2.5 mm2 | 4.0 mm2 | 6.0 mm2 | 10.0 mm2 | |||||||||
DC Resistance at 20℃ Ω/km | Coating | Non-tinned | Tinned | Non-tinned | Tinned | Non-tinned | Tinned | Non-tinned | Tinned | Non-tinned | Tinned | Non-tinned | Tinned | Non-tinned | Tinned | Non-tinned | Tinned |
Category AB | - | - | 24.5 | 24.8 | 18.1 | 18.2 | 12.1 | 12.2 | 7.41 | 7.56 | 4.61 | 4.70 | 3.08 | 3.11 | 1.83 | 1.84 | |
Category R | |||||||||||||||||
Test Voltage | 3000V / 5min | ||||||||||||||||
Insulation Resistance | Conforms to national standard of GB/T9330-2008 | ||||||||||||||||
Flame-Retardant Property | Conforms to national standard of GB/T18380-2008 |
Item | Unit | Qualification | Standard |
Air Temperature | ℃ | 200 ± 3 | GB/T 295.11-2008 |
Test Time | min | 15 | |
Mechanical Load | N/cm2 | 20 | |
Max. Elongation with Load | % | 175 | |
Max. Permanent Elongation after Cooling | % | 15 |
Model | KVVP | KVVP2 | KVVRP | KVVRP2 | KVVP2-22 | KVVP3 |
Shielding Factor ≤ | 0.01 | 0.01 | 0.01 | 0.01 | 0.005 | 0.06 |
No. | Model | Product Description | Application |
1 | KVV | Cu core PVC insulated and sheathed control cable | These models are suitable for light current systems, high current systems or places with strong electromagnetic interference. |
2 | KVVP | Cu core PVC insulated and sheathed Cu wire woven shielded control cable | |
3 | KVVP2 | Cu core PVC insulated and sheathed Cu tape shielded control cable | |
4 | KVV22 | Cu core PVC insulated and sheathed steel tape armored control cable | |
5 | KVVR | Cu core PVC insulated and sheathed soft control cable | |
6 | KVVRP | Cu core PVC insulated and sheathed Cu wire woven shielded soft control cable | |
7 | KVVRP2-22 | Cu core PVC insulated and sheathed Cu tape shielded, steel tape armored soft control cable | |
9 | KVV22 | Cu core PVC insulated and sheathed steel tape armored control cable | |
10 | KVVP2-22 | Cu core PVC insulated and sheathed Cu tape shielded steel tape armored control cable | |
11 | KYJVP2-22 | Cu core XLPE insulated PVC sheathed Cu tape shielded steel tape armored control cable | |
12 | KYJV22 | Cu core XLPE insulated PVC sheathed steel tape armored control cable | |
13 | KYJV | Cu core XLPE insulated PVC sheathed control cable | These products possess outstanding electrical properties, and are resistant to chemical corrosion. Based on these, they are suitable for harsh environment and heavy-load condition. |
14 | KYJVP | Cu core XLPE insulated PVC sheathed Cu wire braid shielded control cable | |
15 | KYJVP2 | Cu core XLPE insulated PVC sheathed Cu tape shielded control cable | |
16 | KYJV22 | Cu core XLPE insulated PVC sheathed steel tape armored control cable | |
17 | KVJVR | Cu core XLPE insulated PVC sheathed soft control cable | |
18 | KYJVRP | Cu core XLPE insulated PVC sheathed Cu wire braid shielded soft control cable | |
19 | KJYVP2-22 | Cu core XLPE insulated PVC sheathed Cu tape shielded steel tape armored control cable | |
20 | DDZ-KV V | Cu core PVC insulated and sheathed low-smoke low-halogen flame retardant control cable | When these products are burning, they generate small amount of smoke and toxic gas, and they are flame retardant. Thus, they are applicable for public places that require flame retardant performance. |
21 | DDZ-KVVP | Cu core PVC insulated and sheathed Cu wire braid shielded low-smoke low-halogen flame retardant control cable | |
22 | DDZ-KVVP2 | Cu core PVC insulated and sheathed Cu tape shielded low-smoke low-halogen flame retardant control cable | |
23 | DDZ-KVV22 | Cu core PVC insulated and sheathed steel tape armored low-smoke low-halogen flame retardant control cable | |
24 | DDZ-KVV | Cu core PVC insulated and sheathed low-smoke low-halogen flame retardant control cable | |
25 | DDZ-KVVP | Cu core PVC insulated and sheathed Cu wire woven shielded low-smoke low-halogen flame retardant control cable | |
26 | DDZ-KVVP2-22 | Cu core PVC insulated and sheathed Cu tape shielded steel tape armored low-smoke low-halogen flame retardant control cable | |
27 | WDZ-KYYR | Cu core PE insulated and sheathed low-smoke halogen free flame retardant soft control cable | |
28 | WDZ-KYYRP | Cu core PE insulated and sheathed Cu wire woven shielded low-smoke halogen free flame retardant soft control cable | |
29 | WDZ-KYYP2-22 | Cu core PE insulated and sheathed Cu tape shielded steel tape armored low-smoke halogen free flame retardant control cable | |
30 | WDZ-KYY | Cu core PE insulated and sheathed low-smoke halogen free flame retardant control cable | Little toxic gas and smoke will be created if it catches fire, and it also shows good flame retardant property. Meanwhile, our product won't corrode electronic device, and it is suitable for many places, such as subway, airport, high-rise building, nuclear power station, computer control center, etc. |
31 | WDZ-KYYP | Cu core PE insulated and sheathed Cu wire woven shielded low-smoke halogen free flame retardant control cable | |
32 | WDZ-KYYP2 | Cu core PE insulated and sheathed Cu tape shielded low-smoke halogen free flame retardant control cable | |
33 | WDZ-KYY22 | Cu core PE insulated and sheathed steel tape armored low-smoke halogen free flame retardant control cable | |
34 | WDZ-KYY32 | Cu core PE insulated and sheathed thin steel wire armored low-smoke halogen free flame retardant control cable | |
35 | ZR-KVV | Cu core PVC insulated and sheathed flame retardant control cable | The flame won't spread if it is fired, and this product is suitable for fireproofing place. |
36 | ZR-KVVP | Cu core PVC insulated and sheathed Cu wire woven shielded flame retardant control cable | |
37 | ZR-KVVP2 | Cu core PVC insulated and sheathed Cu tape shielded flame retardant control cable | |
38 | ZR-KVVP22 | Cu core PVC insulated and sheathed Cu wire shielded and steel tape armored flame retardant control cable | |
39 | ZR-KVVP32 | Cu core PVC insulated and sheathed Cu wire shielded thin steel wire armored flame retardant control cable | |
40 | ZR-KVVR | Cu core PVC insulated and sheathed flame retardant soft control cable | |
41 | ZR-KVVRP | Cu core PVC insulated and sheathed Cu wire woven shielded flame retardant soft control cable | |
42 | ZR-KVVP2-22 | Cu core PVC insulated and sheathed, steel tape shielded and armored, flame retardant control cable | |
43 | KYV | Cu core PE insulated PVC sheathed control cable | These models possess high insulation resistance, strong water proof property as well as good cold resistant performance, and they are used for humid places with low laying temperature. |
44 | KYVP | Cu core PE insulated PVC sheathed Cu wire woven shielded control cable | |
45 | KYVP2 | Cu core PE insulated PVC sheathed Cu tape shielded control cable | |
46 | KYV22 | Cu core PE insulated PVC sheathed steel tape armored control cable | |
47 | KYV32 | Cu core PE insulated PVC sheathed thin steel wire armored control cable | |
48 | KYVR | Cu core PE insulated PVC sheathed soft control cable | |
49 | KYVRP | Cu core PE insulated PVC sheathed Cu wire woven shielded soft control cable | |
50 | KYVP2-22 | Cu core PE insulated PVC sheathed Cu tape shielded steel tape armored control cable |
Item | Code | Description |
Flame-retardant | / | There is no letter for non-flame retardant type. |
ZR | Flame retardant type | |
ZRA | Flame retardant rating: A | |
ZRB | Flame retardant rating: B | |
ZRC | Flame retardant rating: C | |
DDZ | Low-halogen low-smoke flame retardant | |
WDZ | Halogen free low-smoke flame retardant | |
Series | K | Control cable |
Insulating Material | V | PVC |
Y | Polythene | |
YJ | XLPE | |
F | Fluoroplastics (F46) | |
Sheathing Material | V | PVC |
Screening Material | / | Non-screening |
P | Cu wire woven | |
P1 | Tinned Cu wire woven | |
P2 | Cu tape | |
P3 | Al-plastic composite tape | |
Armoring Material | 22 | Steel tape |
32 | Thin steel wire | |
Conductor | R | Stranded soft core, and A stands for single strand conductor, while B stands for seven-strand twisted conductor. |
Specification | Core number × cross section of conductor (N × S)Core number (N): 2, 3, 4, 5, ……61 Cross section (S): 0.5, 0.75, 1.0, 1.5, 2.5, 4, 6, 10 mm2 |
Note: Here are two examples to further illustrate the table above.
Example 1: For a Cu core PVC insulated and sheathed Cu tape shielded control cable with 14 cores, if the conductor is A type with cross section of 1.5mm2, this product is names as KVVP2 14×1.5 (A).
Example 2: Under the condition that a control cable uses Cu core, XLPE insulation, PVC sheath as well as Cu wire woven screen, and the conductor is B type with 14 cores whose cross section is 4.0mm2, it is expressed as KYJVP 14×4 (B).
Delivery Length
1. The cable coil length is 100m, and the drum length should be longer than 100m.
2. Short cable with length of no less than 20 meters is also accepted, but its amount should not exceed 5% of the total length for product with 24 cores or fewer, while the proportion should be below 10% for product having more than 24 cores.
3. The cable length can be negotiated, and the length error is within ±0.5%.