This single-phase AC electric railway 27.5kV XLPE insulated power cable conforms to the standards of TB/T 2822-1997 as well as Q/321011 KLA32-2010, and it is applied for places with single phase, AC, power frequency, and rated voltage of 27.5kV, such as power line for electric railway, power line for auto-transformer, feeder lines of traction substation, partition station, switching station and auto-transformer, etc.
Max. Allowable Short Circuit Current Nominal Cross Section (mm2) | 150 | 185 | 240 | 300 | 400 |
Max. Allowable Short Circuit Current (kA) | 21.4 | 26.4 | 34.3 | 42.9 | 57.2 |
Note: The short circuit lasts for 1 second, and the starting temperature is 90℃.
Code Explanations Product Code | TD | PE inner sheath (isolation unit) | Y |
Low-halogen low-smoke | DD | Non-magnetic metal armoring | 7 |
Halogen free low smoke | WD | Outer sheath |
Copper conductor | (T) Omitted | PVC-based low halogen low smoke flame retardant outer sheath | 2 |
XLPE insulation | YJ | PE-based halogen free low smoke flame retardant outer sheath | 3 |
Model Descriptions Model | Descriptions |
TDDD-YJY72 | Cu core XLPE insulated aluminum wire armored low halogen low smoke flame retardant PVC sheathed power cable |
TDWD-YJY73 | Cu core XLPE insulated aluminum wire armored halogen free low smoke flame retardant PE sheathed power cable |
Specifications Model | No. of Core | Rated Voltage (kV) | Preferred Conductor Cross Section Area (mm2) |
TDDD-YJY72 TDWD-YJY73 | 1 | 27.5 | 150, 185, 240, 300, 400 |
Note: Other specifications are also available upon request.
Qualifications No. | Item | Unit | Standard Value |
1 | DC resistance of conductor | Ω/km | GB/T 3956 |
2 | Partial discharge test at 1.73U0 | pC | ≤10 |
3 | 5min AC voltage test | kV | 97 |
4 | Cable sheath electrical test | kV | 15 |
5 | Hot set test (200℃, 15min, 20N/cm) elongation / permanent elongation | % | ≤175 / ≤15 |
6 | Bending test and subsequent partial discharge test | pC | ≤5 |
7 | Tan delta test | | ≤10×10-4 |
8 | Thermal cycling test and subsequent partial discharge test | pC | ≤5 |
9 | Impulse voltage test and subsequent AC voltage test | pC | ≤5 |
10 | 4h voltage test | kV | 110 |
Structural Parameters Model | Specification | Nominal Insulation Thickness (mm) | Outer Diameter (mm) | Theoretical Weight (kg/km) |
TDDD-YJY72 TDWD-YJY73 | 1×150 | 12 | 61.4 | 4441 |
1×185 | 12 | 63.2 | 4896 |
1×240 | 12 | 65.8 | 5590 |
1×300 | 12 | 67.9 | 6413 |
1×400 | 12 | 71 | 7549 |
Working Condition
1. Max. working temperature of conductor: 90℃
2. Max. temperature of conductor during short circuit: 250℃. The short circuit should lasts less than 5 seconds.
3. Min. ambient temperature when laying: 0℃
4. Min. bending radius: 15 times of cable overall diameter
5. This single-phase AC power cable is suitable for direct burying, and it can be installed in pipeline, cable duct, underground tunnel, etc. In addition, partially laying in the open air is also acceptable, and our product can be immersed in water frequently or periodically.