JD194-BS series electrical multifunction transducer is specially designed for electric power systems, public facilities, intelligent buildings, industrial and mining enterprises as well as others, to meet their demands on electricity calculation, intelligent electricity monitoring, etc.
This product can accurately detect all the commonly used electrical parameters in three-phase power grid, and standard AC voltage and current inputs are both applicable. Aside from these, it is equipped with communication ports, and there are also some scalable functions, such as analog output, relay output, digital input diction, electricity pulse output, etc. Furthermore, this electrical multifunction transducer supports standard AC/DC voltage and current outputs.
Item | JD194-BS4P/Q4T | ||
Accuracy | Class 0.5 | ||
Input | Wiring Mode | 3P3W, 3P4W(Y) | |
Voltage | Nominal Value | 100V, 380V | |
Overload | Continuous: 1.2Ue Instantaneous: 2Ue/10s | ||
Power Consumption | <1VA | ||
Current | Nominal Value | 1A, 5A | |
Overload | Continuous: 1.2Ie Instantaneous: 10Ie/5s | ||
Power Consumption | <1VA | ||
Frequency | 45-65Hz | ||
Expanded Function | Energy Pulse | 2 ways, pulse width: 80ms±20% | |
Analog Output | RL≤500 Ω, 4-20mA, 4-12-20mA | ||
Digital Input | Passive dry contact | ||
Relay Output | Contact capacity: AC 5A/250V, DC 5A/30V | ||
Communication | RS485 port, Modbus-RTU | ||
Power Supply | Working Range | AC/DC 80-270V | |
Power Consumption | ≤5VA | ||
Environment | Operation | Temperature: -10~55℃Relative humidity: <93% RHNo corrosive gasAltitude: ≤2500m | |
Storage | Temperature: -20~75℃Relative humidity: ≤93% RH | ||
Insulation Strength | 2kV/50Hz/1min |
Model Selection
Related Names
Smart Electrical Measuring Transducer | Electrical Engineering Transmitter | Electrical Measuring Instrument