Home Cassette Fan Coil Unit

Cassette Fan Coil Unit

Ceiling mount fan coil units are applicable for large spaces with suspended ceilings, such as malls, hotel lobbies, banquet halls, hospitals, office buildings and other large-scale places.

Cassette Fan Coil Unit
Download Technical Parameters

European Style & Cassette Type Fan Coil Unit

Type 2pipes
Model - RFPC 34-2 51-2 68-2 80-2 85-2 102-2 136-2 170-2 204-2 238-2 289-2 340-2
200 300 400 450 500 600 800 1000 1200 1400 1700 2000
Air Flow (m³/h) H (m³/h) 340 510 680 765 850 1020 1360 1700 2040 2380 2890 3400
M 280 390 520 580 640 790 1030 1700 2040 2380 2890 2600
L 180 260 350 390 430 520 690 860 1030 1200 1600 1900
Cooling Total capacity H KW 2 2.7 3.7 4.2 4.5 5.6 7 9.1 10.8 12.6 15.3 17.6
M KW 1.8 2.3 3.1 3.8 4.2 4.3 5.7 7.9 8.6 10 11.7 13.5
L KW 1.6 1.8 2.6 2.8 3 3.6 4.5 6 6.8 8 9.3 9.9
Sensible capacity H KW 1.5 1.9 2.6 2.9 3.5 3.9 5 6.4 7.7 9 11.5 14.8
M KW 1.3 1.7 2 2.6 3.2 3.3 4.3 5.9 6.5 7.5 8.4 11.1
L KW 1.2 1.4 1.8 1.9 2.8 2.9 3.6 4.8 5.4 6.4 6.8 7.8
Water Flow I/h 345 470 640 720 780 970 1260 1710 1920 2160 2640 3027
Water P.D kPa 7 9 11 14 16 18 19 17 19 22 36 48
Heating Heating capacity H KW 2.8 4.2 5.6 6.3 7 8.4 11.2 13.9 16.7 19.5 23.7 25.5
M 2.5 3.4 4.5 5.5 6.3 6.5 8.5 12 12.6 15.6 17.5 18.6
L 2 2.7 4 4.5 5 5.2 6.7 9 10.2 12 13.8 13
Power supply 220-240V/1PH/50HZ(60HZ)
Power Input W 37 39 41 42 43 45 46 47 50 52 57 65
Sound pressure dB(A) 37 39 41 42 43 45 46 47 50 52 57 65
Fan Type Centrifugal Fan
Model Ф315
Qty 1 1 1 1 1 1 1 1 1 1 1 1
Motor Type     3-speed
Qty     1 1 1 1 1 1 1 1 1 1 1 1
Coil Rows 2
Mix.working pressure MPa 1.6Mpa
Tube Dia inch 3/8''
Dimension Unit body mm 580x580x250 705x705x290 832x832x290 960x960x290
Panel assembly mm 680x680x30 830x830x30 980x980x30 1140x1140x30
Connection Water inlet/outlet inch ZG3/4'' / ZG3/4''
Condensate discharge inch 26
Weight Kg 20 20 20 20 25 25 25 34 34 34 50 52

European Style & Cassette Type Fan Coil Unit

Type 4pipes
Model - RFPC 68-2 1 80-2 1 85-2 1 102-2 1 136-2 1 170-2 1 204-2 1 238-2 1 289-2 1 340-2 1
400 450 500 600 800 1000 1200 1400 1700 2000
Air Flow (m³/h) H (m³/h) 680 765 850 1020 1360 1700 2040 2380 2890 3400
M 520 580 640 790 1030 1290 1500 1800 2100 2600
L 350 390 430 520 690 860 1030 1200 1600 1900
Cooling capacity(W) Total capacity H KW 2.6 2.8 3.1 3.6 4.8 6 7 8.4 10.3 11.5
M KW 2 2.2 2.4 2.8 3.7 4.7 6 6.5 7.5 8.3
L KW 1.4 1.6 1.8 2.1 3 3.6 4.6 5 5.7 6.3
Sensible capacity H KW 1.8 2 2.2 2.5 3.4 4.2 4.9 5.9 8.5 9.5
M KW 1.5 1.6 1.8 2.1 2.8 3.5 4.5 4.9 6.2 6.9
L KW 1.1 1.2 1.4 1.7 2.4 2.9 3.7 4 4.7 5.2
Water Flow I/h 450 468 540 625 830 1050 1400 1500 1800 2000
Water P.D kPa 11 13 17 17 19 21 23 25 27 29
Heating capacity(W) Heating capacity H KW 2.6 3.1 3.5 4.3 4.9 6.5 7.2 8.7 11.9 15.2
M 2 2.3 2.7 3.2 4.3 5.4 5.6 7.6 8.7 11.3
L 1.4 1.7 2.1 2.5 3.5 4.2 4.3 5.8 6.6 8.7
Power supply 220-240V/1PH/50HZ(60HZ)
Power Input W 62 68 76 96 132 152 189 220 330 340
Sound pressure dB(A) 41 42 43 45 46 47 50 52 57 65
Fan Type Centrifugal Fan
Model Ф315
Qty 1 1 1 1 1 1 1 1 1 1
Motor Type 3-speed
Qty 1 1 1 1 1 1 1 1 1 1
Coil Rows 2
Mix.working pressure MPa 1.6Mpa
Tube Dia inch 3/8''
Dimension Unit body mm 580x580x250 705x705x290 832x832x290 960x960x290
Panel assembly mm 680x680x30 830x830x30 980x980x30 1140x1140x30
Connection Water inlet/outlet inch ZG3/4'' / ZG3/4''
Condensate discharge inch 26
Weight Kg 21 21 26 26 26 35 35 35 53 53

Notes

The data in the above tables are all for high range air flow cases with respective excessive pressures.
Cooling capacity refers to the value with cooling inflow water at a temperature of 7℃, temperature difference between inlet and outlet at 5℃, and temperature of inlet air at DB=27℃, WB=19.5℃.
Heating capacity refers to the value of heating inflow water at a temperature of 60℃, temperature difference between inlet and outlet at 5℃, temperature of inlet air at DB=21℃, and the same water flow as cooling case.
Standard power is 50Hz. 60Hz power is optional. Please inform us when ordering if needed. Features No water pump, natural drainage and stable operation. The electric control panel does not easily become damaged.
4-way air flow so that the temperature is evenly distributed throughout the room.
Convenient installation and low installation costs: Compared to concealed fan coil unit, a ceiling mount fan coil unit doesn't need an inlet and outlet, pipe connection or insulation treatment.

Recommended Products