Home Horizontal Type Air Handling Unit

Horizontal Type Air Handling Unit

Horizontal air cooling units are used for ventilation and refrigeration in a number of different building types, ranging from industrial shopping malls, to shopping malls and everything in between.

Horizontal Type Air Handling Unit
Download Technical Parameters

RFPL/W-/4H Series Return Air Condition

Model Air flow (m3/h) Rated cooling cap.(kW) Rated heating cap.(kW) Water flow (m3/h) Water D.P. (Kpa) ESP (Pa) Motor power (kW) Noise dB(A) Water pipe DN Drain pipe DN
020 2000 10.5 17.2 1.8 9.8 220 0.55 54 40 25
030 3000 15.7 25.7 2.7 13.6 220 0.75 55 40 25
040 4000 20.9 34.3 3.6 22.4 220 1.1 56 40 25
050 5000 26.2 42.9 4.5 23.6 220 1.5 58 40 25
060 6000 31.4 51.5 5.4 27.8 250 2.2 58 40 25
070 7000 36.6 60.1 6.3 32.3 250 2.2 58 50 25
080 8000 41.9 68.7 7.2 48.1 270 2.2 58 50 25
090 9000 47.1 77.2 8.1 43.5 270 2.2 59 50 25
105 10500 52.3 85.8 9.0 62.1 270 3.0 60 50 25
120 12000 62.8 103.0 10.8 48.5 270 3.0 61 50 25
135 13500 70.6 115.8 12.2 22.3 320 4.0 64 65 32
150 15000 78.5 128.7 13.5 62.5 320 4.0 66 65 32
180 18000 94.2 154.5 16.2 32.5 320 5.5 68 65 32
210 21000 109.9 180.2 18.9 37.3 350 7.5 68 65 32
240 24000 125.6 206.0 21.6 65.6 350 7.5 70 65 40
270 27000 141.3 231.7 24.3 58.2 350 7.5 71 65 40
300 30000 157.0 257.4 27.0 60.4 420 11.0 72 65 40
330 33000 172.7 283.2 29.7 75.1 420 11.0 72 80 40
350 35000 183.1 300.3 31.5 86.4 450 11.0 74 80 40
400 40000 209.3 342.3 36.0 71.4 450 11.0 75 80 40
450 45000 235.5 386.2 40.5 75.3 450 15.0 76 80 40
500 50000 261.6 429.1 45.0 81.7 450 15.0 76 80 40
Note 1.Cooling conditions:inlet air DB27℃,WB19.5℃,inlet water temperature 7℃/12℃
2.Heating conditions:inlet air DB21℃,inlet water temperature 60℃/50℃

RFPL/W-/6H Series Return Air Condition

Model Air flow (m3/h) Rated cooling cap.(kW) Rated heating cap.(kW) Water flow (m3/h) Water D.P. (Kpa) ESP (Pa) Motor power (kW) Noise dB(A) Water pipe DN Drain pipe DN
020 2000 15.1 24.8 2.60 22 220 0.55 54 40 25
030 3000 22.7 37.2 3.90 35 220 1.1 55 40 25
040 4000 30.2 49.6 5.20 46 220 1.1 56 40 25
050 5000 37.8 62.0 6.50 43 220 1.5 58 40 25
060 6000 45.3 74..4 7.80 54 250 2.2 58 40 25
070 7000 52.9 86.8 9.10 24 250 2.2 58 50 25
080 8000 60.5 99.2 10.40 35 270 2.2 58 50 25
090 9000 68.0 111.6 11.70 38 270 3.0 59 50 25
105 10500 79.4 130.2 13.65 43 270 3.0 60 50 25
120 12000 90.7 148.7 15.60 46 270 3.0 61 50 25
135 13500 102.0 167.3 17.55 48 320 4.0 64 65 32
150 15000 113.4 185.9 19.50 51 320 5.5 66 65 32
180 18000 136.0 223.1 23.40 23 320 5.5 68 65 32
210 21000 158.7 260.3 27.30 26 350 7.5 68 65 32
240 24000 181.4 297.5 31.20 35 350 7.5 70 65 40
270 27000 204.1 334.7 35.10 42 350 11.0 71 65 40
300 30000 226.7 371.9 39.0 44 420 11.0 72 65 40
330 33000 249.4 409.0 42.90 53 420 11.0 72 80 40
350 35000 264.5 433.8 45.50 63 450 11.0 74 80 40
400 40000 302.3 495.8 52.0 54 450 15.0 75 80 40
450 45000 340.1 557.8 58.50 61 450 15.0 76 80 40
500 50000 377.9 619.8 65.0 67 450 18.5 76 80 40
Note 1.Cooling conditions:inlet air DB27℃,WB19.5℃,inlet water temperature 7℃/12℃
2.Heating conditions:inlet air DB21℃,inlet water temperature 60℃/50℃
Features Use of a lightweight aluminum alloy frame makes it convenient for onsite dismounting and maintenance.
Internal and external double layer polyurethane color steel panels avoid the formation of cold bridges on the shell while operating.
The horizontal air cooling units are operated and tested using dynamic and static equilibrium tests before delivery.
Closed rolling bearings function as the automatic adjusting center of gravity, automatic locking and anti-pushing. Pre-filling of lube oil makes it unnecessary for maintenance in normal conditions.
The filter is a cleanable, reusable plate type.