The LSW series water cooled water chiller is available with capacity ranging from 2 to 100 RT.
The standard configurations for this industrial chiller include the pump tank, high-efficiency scroll compressor, stainless steel plate evaporator and condenser, tandem and dual circuit, shell and tube heat exchanger, filter dryer, thermostatic expansion valve, and sight glass.
The optional configurations for this series water cooled water chiller include the water regulating pressure control, various pump configurations, automatic makeup water system, oversized pump and reservoir, as well as the heat exchanger system for potable water isolation.
Model | ||||||||||||||||
LSW-03 | LSW-05 | LSW-08 | LSW-10 | LSW-12 | LSW-15 | LSW-20S | LSW-25S | LSW-30S | LSW-40D | LSW-50D | LSW-60D | LSW-80D | LSW-100D | LSW-120L | ||
Refrigerating Capacity | 104kcal/h | 0.79 | 1.33 | 2.13 | 2.78 | 3.11 | 4.17 | 5.55 | 6.23 | 8.34 | 11.11 | 12.45 | 16.68 | 22.80 | 28.82 | 34.20 |
kW | 9.20 | 15.5 | 24.8 | 32.3 | 36.2 | 48.5 | 64.6 | 72.4 | 97 | 129.2 | 144.8 | 194 | 265.2 | 335.2 | 397.8 | |
Compressor | Quantity (set) | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 4 | 4 | 4 | 4 | 4 | 6 |
Input Power (kW) | 2.08 | 3.29 | 5.18 | 6.48 | 7.5 | 10.17 | 12.96 | 15 | 20.34 | 25.92 | 30 | 40.68 | 55.48 | 69.76 | 83.22 | |
Operating Current (A) | 3.83 | 6.49 | 10.22 | 13.3 | 15.39 | 21.41 | 26.6 | 30.79 | 40.14 | 42.29 | 55.26 | 74.94 | 102.2 | 128.51 | 153.3 | |
Refrigerant | Type | R22 | ||||||||||||||
Machine Power (kW) | 2.63 | 4.04 | 6.28 | 7.98 | 9 | 12.57 | 15.96 | 18 | 23.34 | 29.92 | 34 | 46.18 | 60.98 | 77.26 | 94.22 | |
Total Current (A) | 5.08 | 8.25 | 13.07 | 16.75 | 18.84 | 27.05 | 33.45 | 37.64 | 46.99 | 51.39 | 64.36 | 87.44 | 114.70 | 145.36 | 178.40 | |
Supply Voltage | 3φ 380V 50HZ | |||||||||||||||
Condenser | Type | Horizontal Shell and Tube Type High-efficiency Heat Exchanger | ||||||||||||||
Cooling Water Flow (t/h) | 4 | 5 | 8 | 10 | 12 | 15 | 20 | 25 | 25 | 30 | 40 | 50 | 65 | 80 | 100 | |
Water Pipe Joint | DN25 | DN25 | DN40 | DN40 | DN50 | DN50 | DN65 | DN65 | DN65 | DN65 | DN80 | DN80 | DN80 | DN80 | DN100 | |
Evaporator | Type | Tube-in-tube High-efficiency Evaporator | Horizontal Shell and Tube Type High-efficiency Heat Exchanger | |||||||||||||
Chilled Water Flow (t/h) | 3 | 4 | 6 | 8 | 10 | 12 | 15 | 20 | 20 | 25 | 25 | 35 | 40 | 50 | 65 | |
Water Pipe Joint | DN25 | DN25 | DN40 | DN40 | DN50 | DN50 | DN50 | DN65 | DN65 | DN65 | DN80 | DN80 | DN80 | DN80 | DN100 | |
Chilled Water Pump | Type | Stainless Steel Multistage Centrifugal Water Pump | ||||||||||||||
Input Power (kW) | 0.55 | 0.75 | 1.1 | 1.5 | 1.5 | 2.4 | 3 | 3 | 3 | 4 | 4 | 5.5 | 5.5 | 7.5 | 11 | |
Head (mH2O) | 28 | 30 | 28 | 34 | 33.5 | 40 | 33 | 28 | 28 | 31 | 31 | 32 | 34 | 33 | 37 | |
Safety Protection Device | High and Low Pressure Protection, Phase-sequence Protection, Overload Current Protection, Water Shortage Alarm, Delay Protection, Overheat Protection | |||||||||||||||
Nominal Volume of Water Tank (L) | 75 | 100 | 150 | 200 | 320 | 330 | 400 | 500 | 500 | External Type | ||||||
Overall Dimensions | Length (mm) | 880 | 880 | 1200 | 1200 | 1600 | 1600 | 1800 | 2000 | 2000 | 3000 | 2400 | 3200 | 2500 | 3500 | 3500 |
Width (mm) | 660 | 660 | 850 | 850 | 850 | 900 | 1200 | 1300 | 1200 | 1500 | 1400 | 1300 | 1400 | 1300 | 2000 | |
Height (mm) | 1050 | 1050 | 1210 | 1210 | 1230 | 1330 | 1380 | 1430 | 1380 | 2030 | 1420 | 1440 | 1720 | 1670 | 1900 | |
Total Weight (kg) | 130 | 195 | 260 | 260 | 350 | 500 | 650 | 650 | 950 | 1500 | 1800 | 2000 | 2100 | 2400 | 2700 |
Note:
1. The refrigeration system for the water cooled chiller works under the condition of:
(1) Chilled water inlet temperature: 12℃;
(2) Chilled water outlet temperature: 7℃;
(3) Cooling water inlet temperature: 30℃;
(4) Cooling water outlet temperature: 35℃
2. Chilled water temperature range: 5℃ to 30℃.
3. Power supply: 3Φ/380V±10%/50Hz; ±2% phase voltage difference.
4. The above are technical specifications of chilled water systems using R22 refrigerant. Please contact us directly for the specifications of water chiller systems utilizing refrigerant such as R134a, R407C, etc.
5. The above overall dimensions are subject to change without prior notice. If you need the latest dimensions, please contact us directly, and we will provide you with the mounting dimension drawing.