Home ZN105-18/T6300-63 Vacuum Circuit Breaker for Generator

ZN105-18/T6300-63 Vacuum Circuit Breaker for Generator

According to the situation of control and protection circuit breaker for large-capacity load depending on imports in our power industry, our company developed this ZN105-18/T6300-63 vacuum circuit breaker for generator protection in 2008 by digesting and absorbing the German Siemens's 3AF technology imported in 1983. The rated current and rated short-circuit breaking current of this large-capacity circuit breaker are 6,300A and 63kA, respectively.

ZN105-18/T6300-63 Vacuum Circuit Breaker for Generator

Features
1. With the rated voltage and frequency of 18kV and 50Hz respectively, this indoor AC high voltage switching device reaches the international advanced level in technical performance and it fills in the blank of domestic vacuum circuit breaker in this parameter level.


2. This vacuum circuit breaker for generator adopts the integrated design of operating mechanism and switch. The specialized spring energy storage type operating mechanism can be operated by AC, DC or hand.


3. With strong breaking capability, complete operating functions, long mechanical life, no explosion hazard and other advantages, this indoor circuit breaker is suitable to work as the control or protection switch in power plants, large-scale substations, as well as industrial and mining enterprises.


4. Our vacuum circuit breaker has excellent insulation property. It can fully meet the using requirement in indoor areas with the filthy condition of Grade II.


Conditions of Use Environment
1. Altitude: ≤2,000m
2. Ambient Temperature: -25℃~ 40℃
3. Relative Humidity: Daily average≤95%, monthly average≤90%
4. Earthquake Intensity: <8degree
5. The vacuum circuit breaker for generator should be used in places without fire, explosion, corrosive gas, or severe shaking.


Technical Parameters
ItemUnitValue
Rated VoltagekV 18
Rated CurrentA 6300
Rated Short-circuit Breaking CurrentkA 63
Rated Peak Withstand CurrentkA 176
Rated Short-time Withstand CurrentkA 63
Rated Short-circuit Closing Current (Peak)kA 176
Rated Short Circuit Duration S 2
Rated Short-circuit Current Breaking Times5
Rated Operating SequenceClose open -15min- close open
Rated FrequencyHz 50
Lightning Impulse Withstand Voltage (Peak)Phase to phase, phase to groundkV 100
Vacuum breakkV 115
1min Power Frequency Withstand VoltagePhase to phase, phase to groundkV 53
Vacuum breakkV 63
Closing Time ms 40-65
Opening Timems 35-65
Breaking Timems 50-80
Mechanical Lifetimes 4000
Rated Power of the Energy Storage MotorW 550
Rated Voltage of the Energy Storage MotorV ≈ 220
Energy Storage Times ≤15
Rated Voltage of the Closing and Tripping ElectromagnetV 220
Rated Current of the Closing and Tripping ElectromagnetA Closing: 2Opening: 3
Rated Current of the Auxiliary SwitchA AC10 DC5
Rated Out-of-step Breaking Current kA 31.5
Rated Load Opening and Closing Timestimes 50
DC Component of the Rated Asymmetrical Breaking Current % Average: 67Maximum: 69
DC Component of the Rated Out-of-step Asymmetrical Breaking Current % 50~60

BBE is an experienced vacuum circuit breaker for generator manufacturer and supplier in China. We provide a wide array of products, including high voltage circuit breaker, low voltage circuit breaker, gas insulated switchgear (GIS), high voltage vacuum contactor, and more.