Used in the AC 126kV/50Hz power systems, the LW36-126 SF6 circuit breaker is particularly suitable for breaking important loads. It can work not only as the control and protection switch in power transmission and distribution systems but also as the network interconnecting circuit breaker for control and protection of power systems.
With the biggest characteristic of low gauge pressure, this SF6 circuit breaker is able to operate properly at the temperature of -40℃.
Ambient Temperature | 40℃~ 40℃, Daily Temperature Difference ≤35℃ |
Altitude | ≤1000m |
Wind Speed | ≤34m/s (Equivalent to 700Pa on Cylindrical Surface) |
Sunlight Intensity | ≤1000W/m2 (at Noon on Fine Day) |
Monthly Average Relative Humidity | ≤90% |
Earthquake Acceleration | Horizontal≤0.2g Vertical≤0.1g |
Ice Thickness | ≤10mm |
Air Pollution Degree | Not exceed the Level IV in GB/T5582 |
Installation Site | Indoors and Outdoors |
S/N | Item | Unit | Data | |
1 | Rated Voltage | kV | 126 | |
2 | Rated Power Frequency Withstand Voltage (1min) | Phase to Phase and Phase to Ground 230 | ||
Break to Break 230 73* | ||||
3 | Rated Lightning Impulse Withstand Voltage | Phase to Phase and Phase to Ground 550 | ||
Break to Break 550 103* | ||||
4 | Power Frequency Withstand Voltage When the Gauge Pressure of SF6 is Zero (5min) | Phase to Phase and Phase to Ground 95 | ||
Break to Break 95 | ||||
5 | Rated Frequency | Hz | 50 | |
6 | Rated Current | A | 3150 | |
7 | Rated Short-circuit Breaking Current | kA | 40 | |
8 | Rated Peak Withstand Current | 100 | ||
9 | Rated Short-time Withstand Current | 40 | ||
10 | Rated Short-circuit Closing Current | 100 | ||
11 | First-Pole-to-Clear Factor | 1.5 | ||
12 | Rated Short Circuit Duration | s | 4 | |
13 | Rated Out-of-Phase Breaking Current (OP2) | kA | 10 | |
14 | Short Line Fault Breaking Current | kA | 36,30 | |
15 | Rated Circuit Charging Breaking Current | A | 31.5 | |
16 | Rated Operating Sequence | O- 0.3s- CO- 180s- CO | ||
17 | Rated Pressure of SF6 Gas (Gauge Pressure at 20℃) | MPa | 0.4 | |
18 | Warning/Locking Pressure (Gauge Pressure at 20℃) | 0.36/0.32 | ||
19 | Annual Gas Leakage Rate | %/Year | ≤0.5 | |
20 | Moisture Content of Gas | PPM (V) | ≤150 | |
21 | Mechanical Service Life | Times | 6000 | |
22 | Radio Interference Level | μV | ≤500 | |
23 | Making Time | ms | ≤70 | |
24 | Electrical Service Life | Times | ≥20 | |
25 | SF6 Gas Mass Used for Each Set | kg | 7 | |
26 | Mass of Each Circuit Breaker | 1500 | ||
27 | Creepage Distance | Break to Break | mm | 3150 |
Break to Ground | 3150 |
We are a professional circuit breaker manufacturer and supplier in China. We also provide molded case circuit breaker, gas insulated switchgear, outdoor double pole vacuum circuit breaker, and more.